| Plan Review Stops For Permit 21080247 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
P |
Date |
2021-09-02 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-09-02 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-09-02 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2021-09-02 16:48:46 | ADDRESSES UNDER PCN 74434328090160010: | | | | | | 2013 @ HAPPY ST | | | 2069 @ HAPPY ST | | | 484 @ 17TH ST | | | 425 @ 18TH ST |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-08-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2021-08-26 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-08-26 06:02:40 | PLEASE APPLY FOR 4 PERMITS, YOU CAN USE ONE SET OF | | | PLANS, BUT WE NEED FOUR PERMITS AS THE POLES ARE ON | | | DIFFERENT STREET, @ ADDRESSES NEED TO BE CREATED FOR | | | ALL THE PERMITS TO REFLECT THE NEW LOCATION OF THE | | | POLES. PLEASE CONTACT [email protected] OR CALL | | | 561-805-6659 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-08-10 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-08-10 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-08-10 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2021-08-10 15:08:15 | PLEASE APPLY FOR 4 PERMITS, YOU CAN USE ONE SET OF | | | PLANS, BUT WE NEED FOUR PERMITS AS THE POLES ARE ON | | | DIFFERENT STREET, @ ADDRESSES NEED TO BE CREATED FOR | | | ALL THE PERMITS TO REFLECT THE NEW LOCATION OF THE | | | POLES. PLEASE CONTACT [email protected] OR CALL | | | 561-805-6659 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-11-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-17 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-17 |
Time |
07:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-08-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-12 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-12 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-22 |
Time |
18:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-22 |
Time |
18:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-11-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-17 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-02 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-22 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-09-01 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-08-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-08-26 |
Time |
06:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-08-24 |
Time |
09:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-08-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-12 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-09 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-11-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-17 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-17 |
Time |
07:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-22 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-22 |
Time |
18:22 |
Sent To |
|
|
| Notes |
| 2021-10-22 18:24:42 | 10/22/21 PLANS THAT THE CONTRACTOR SIGNED WERE UPLOADED | | | TO THE SIGNATURE FOLDER. THIS IS ONLY FOR DIGITALLY | | | SIGNED PLANS PREPARED BY A DESIGN PROFESSIONAL, | | | ARCHITECT OR ENGINEER. | | | | | | UPLOAD PDFS TO THE DRAWINGS FOLDER. EACH PAGE SHOULD BE | | | SIGNED BY THE CONTRACTOR. SEE JAKE'S PREVIOUS COMMENT, | | | CONTRACTOR CANNOT SIGN A PLAN THAT WAS PREPARED BY A | | | DESIGN PROFESSIONAL. | | | | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) CONTRACTOR CAN NOT SIGN SOMEONE ELSES PLANS. | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | LAND DESIGN TITLA BLOCK ON PAGE WOULD BE THE PERSON OF | | | RECORD. | | | | | | IF THIS IS 480VOLT WORK IT IS TO BE SIGNED BY AN | | | ENGINEER. 471.003(H2A) | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-08-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-25 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-25 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2021-08-25 13:58:38 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) CONTRACTOR CAN NOT SIGN SOMEONE ELSES PLANS. | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | LAND DESIGN TITLA BLOCK ON PAGE WOULD BE THE PERSON OF | | | RECORD. | | | | | | IF THIS IS 480VOLT WORK IT IS TO BE SIGNED BY AN | | | ENGINEER. 471.003(H2A) | | 2021-08-24 09:49:11 | SIGNED PLANS IN SIGNATURE FOLDER AO |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-08-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-12 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-12 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2021-08-12 15:22:25 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2021-09-24 |
|
|
Cont ID |
|
| Sent By |
av |
Date |
2021-09-24 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-09-24 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|