| 2021-08-24 10:27:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | NFPA 99-18 = HEALTH CARE FACILITIES CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21080223 1515 N FLAGLER DR # 301 |
| | |
| | 1ST REVIEW |
| | MED GAS COMMENTS:DENIED |
| | |
| | PROVISO: PER NFPA 99-18, 15.1.5, AN INSPECTION OF THE |
| | EXISTING PIPING SYSTEMS SHALL BE MADE BY THE AUTHORITY |
| | HAVING JURISDICTION TO DETERMINE THAT CONTINUED USE OF |
| | SAID SYSTEMS DOES NOT CONSTITUTE A DISTINCT HAZARD TO |
| | LIFE. IF SUCH DETERMINATION IS MADE, THE EXISTING |
| | SYSTEMS MAY CONTINUE TO BE USED. |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE THE RISK CATEGORY AND |
| | ASSESSMENT AS DETERMINED BY NFPA 99-18; 4.1 THROUGH |
| | 4.3. THE FOLLOWING COMMENTS ARE APPLICABLE TO A |
| | CATEGORY 2. HOWEVER, THEY ARE SUBJECT TO CHANGE BASED |
| | UPON INFORMATION PROVIDED IN RESPONSE. |
| | |
| | 2. IT IS UNCLEAR AS TO THE PURPOSE OF THE EXISTING ZONE |
| | VALVE. DOES PLAN VIEW INDICATE EXISTING PIPING FROM |
| | ZONE VALVE TO PROCEDURE 1 WITH NEW PROPOSED PIPING TO |
| | BE ADDED TO THAT ZONE? PER WPB FBC 107.2.1, CLARIFY. |
| | PER WPB FBC 107.2.1, PROVIDE A RISER DIAGRAM FOR THE |
| | OXYGEN AND NITROGEN PIPING NEW AND EXISTING PIPING |
| | WITHIN ZONE AND DOWN FEED FROM EXISTING. |
| | |
| | 3. SHOW EXISTING SOURCE ROOM(S) FOR OXYGEN AND NITROGEN |
| | AND EXISTING PIPING FROM SOURCE TO EXISTING ZONE VALVE. |
| | SHOW ANY OTHER EXISTING BRANCH PIPING AND ZONE VALVES. |
| | A RISER DIAGRAM FOR THIS PIPING IS NOT REQUIRED OTHER |
| | THAN DOWN FEED INTO EXISTING ZONE VALVE. |
| | |
| | 4. PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING |
| | MASTER ALARM STATION. |
| | |
| | 5. PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING |
| | OXYGEN AND NITROGEN SUPPLY ROOM(S). PER WPB FBC 104.3, |
| | CONFIRM THAT APPROPRIATE SIGNAGE IS ON DOOR TO ROOM. |
| | SEE NFPA 99-18; 15.4.2.2.8, 15.4.2.2.9. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATIONS |
| | FOR O2 AND NO PIPING SYSTEM INCLUDING BUT NOT LIMITED |
| | TO PIPE, FITTINGS, JOINTS; SEE NFPA 99-18, 15.4.4.2 |
| | |
| | 7. PER WPB FBC 107.2.1, SHOW OR INDICATE HOW NITROUS |
| | OXIDE SCAVENGING IS TO BE ACCOMPLISHED. SEE NFPA 99-18, |
| | 15.3.3.6. |
| | |
| | 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR MEDICAL |
| | GAS EQUIPMENT AND COMPONENTS INCLUDING BUT NOT LIMITED |
| | TO OUTLETS, VALVES, GAUGES, CONTROLS. |
| | |
| | 9. PER WPB FBC 107.2.1, INDICATE THE BUILDING SYSTEM |
| | CATEGORY THAT THIS FACILITY OPERATES UNDER. SEE NFPA |
| | 99-18, 4.1 THROUGH 4.1.4. |
| | |
| | 10. PER WPB FBC 107.2.1, ADD NOTE, PIPING SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH NFPA 99-18, TABLE |
| | 15.4.5.6.5 |
| | |
| | 11. PER WPB FBC 107.2.1, ADD NOTE, PROVIDE |
| | DOCUMENTATION OF FOR OXYGEN AND NITROUS OXIDE PIPE, |
| | FITTINGS, VALVES, GAS/VACUUM OUTLETS/INLETS AND OTHER |
| | PIPING COMPONENTS HAVE BEEN CLEANED FOR OXYGEN BY THE |
| | MANUFACTURER PRIOR TO INSTALLATION IN ACCORDANCE WITH |
| | CGA G-4.1 AS REQUIRED BY NFPA 99-18, 15.4.4.2.1. NOTE; |
| | FITTINGS SHALL BE PERMITTED TO BE CLEANED BY A SUPPLIER |
| | OR AGENCY OTHER THAN THE MANUFACTURER WITH PROPER |
| | DOCUMENTATION. |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE NOTE STATING PER NFPA |
| | 99-18, 15.4.2.1.1, 15.4.2.1.2, MEDICAL GAS (OXYGEN AND |
| | NITROUS OXIDE) INSTALLERS SHALL BE CERTIFIED IN |
| | ACCORDANCE WITH ASSE 1060. INSTALLER SHALL NOT USE HIS |
| | CERTIFICATION TO OVERSEE INSTALLATION BY NON-CERTIFIED |
| | INDIVIDUALS. |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE NOTE STATING PER NFPA |
| | 99-18, 15.4.2.1.3, 15.4.2.1.3, BRAZING OF MEDICAL GAS |
| | (OXYGEN AND NITROUS OXIDE) SYSTEMS SHALL BE PERFORMED |
| | BY INDIVIDUALS WHO ARE QUALIFIED ACCORDANCE WITH |
| | 15.4.6.1. PRIOR TO INSTALLATION REQUIRING BRAZING, THE |
| | INSTALLER (CERTIFIED) SHALL PROVIDE DOCUMENTATION OF UP |
| | TO DATE BRAZING PROCEDURES AND INDIVIDUAL BRAZERS |
| | SHOWING COMPLIANCE WITH 15.4.6.1. |
| | |
| | 13. PER WPB FBC 104.3, PROVIDE NOTE STATING INSTALLERS |
| | CERTIFICATIONS SHOWING COMPLIANCE WITH ASSE 1060 AND |
| | BRAZERS CERTIFICATIONS SHOWING COMPLIANCE WITH |
| | 15.4.6.1. |
| | |
| | 14. PER WPB FBC 104.3, PROVIDE NOTE STATING TIE IN OF |
| | NEW PIPING TO EXISTING SYSTEMS SHALL COMPLY WITH NFPA |
| | 99-18, 15.4.7.5.7 THROUGH 15.4.7.5.7.5. |
| | |
| | 15. PER WPB FBC 104.3, PROVIDE NOTE STATING PER NFPA |
| | 99-18, 15.4.2.11, LABELING/IDENTIFICATION OF PIPING |
| | SYSTEMS SHALL COMFORM TO TABLE 5.1.11. |
| | |
| | END OF COMMENTS. |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE PRIOR REVIEW. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21080223 1515 N FLAGLER DR # 301 |
| | |
| | |