Plan Review Details - Permit 21080182
Plan Review Stops For Permit 21080182
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-11-17 Cont ID  
Sent By pvalenti Date 2021-11-17 Time 16:23 Rev Time 0.00
Received By pvalenti Date 2021-11-17 Time 16:23 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-11-09 Cont ID  
Sent By jwitmer Date 2021-11-09 Time 11:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 07:50 Rev Time 0.00
Received By jwitmer Date 2021-08-31 Time 17:32 Sent To  
Notes
2021-09-01 07:50:28COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-21 Cont ID  
Sent By jwitmer Date 2021-12-21 Time 11:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-23 Cont ID  
Sent By jwitmer Date 2021-11-23 Time 15:27 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-23 15:27:37WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21080182
 ADD: 4700 BROADWAY AVE.
 CONT: RETAIL CONTRACTORS
 TEL: 352-302-5496
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 3RDREVIEW
 DATE: TUES. NOV. 23RD/2021
 ACTION: DENIED
 ****NO TRANSMITTAL LETTER **** WAS SUBMITTED LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION
 OF THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) COMPLIED.
 2) 3RD REQUEST. 1ST ROUND OF COMMENTS THE FIXTURE &
 HARDWARE PLAN SHOWS NEW COOLERS & FREEZERS. THE PLANS
 ARE SILENT AS TO IF THE CONDENSERS ARE GOING TO BE
 REMOTE ROOF TOP CONDENSERS, IF SO SHOW COMPLIANCE WITH
 THE 2020 FBC-B:
  
 2A) 3RD REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M-
 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2B) 3RD REQUEST. 1ST ROUND OF COMMENTS
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS. 2020 FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31) (G)
 PRE-ENGINEERED A/C STANDS
  
 2C) 3RD REQUEST. 1ST ROUND OF COMMENTS THE ROOF TOP A/C
 STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE DESIGNER
 OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 2D) 3RD REQUEST. 1ST ROUND OF COMMENTS LATERAL
 FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP EQUIPMENT,
 CURBS, FANS OR A/C STANDS, AND OR VENTS, DETAILED
 ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2020
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2E) 3RD REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR
 APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE
 ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO
 CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO
 ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR
 EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL
 NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL.
  
 2F) 3RD REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR
 APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE
 ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO
 CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO
 ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR
 EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL
 NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL. 2017 FBC-B
 1011.16 LADDERS.
  
 3-4) COMPLIED.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-09 Cont ID  
Sent By jwitmer Date 2021-11-09 Time 11:09 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-09 11:09:05WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21080182
 ADD: 4700 BROADWAY AVE.
 CONT: RETAIL CONTRACTORS
 TEL: 352-302-5496
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 09TH/2021
 ACTION: DENIED
 ****NO TRANSMITTAL LETTER **** WAS SUBMITTED LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION
 OF THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1) SEMI-COMPLIED. 1ST ROUND OF COMMENTS. THE 3
 SUBMITTED PLANS FIXTURE / HARDWARE PLAN, FLOOR PLAN &
 MERCHANDISE PLAN WERE NOT DESIGNED BY EITHER A ENGINEER
 OR ARCHITECT, THE CONTRACTOR (QUALIFIER) MUST TAKE
 OWNERSHIP OF ALL 3 PLANS. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2) 2ND REQUEST. 1ST ROUND OF COMMENTS THE FIXTURE &
 HARDWARE PLAN SHOWS NEW COOLERS & FREEZERS. THE PLANS
 ARE SILENT AS TO IF THE CONDENSERS ARE GOING TO BE
 REMOTE ROOF TOP CONDENSERS, IF SO SHOW COMPLIANCE WITH
 THE 2020 FBC-B:
  
 2A) 2ND REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M-
 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2B) 2ND REQUEST. 1ST ROUND OF COMMENTS
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS. 2020 FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31) (G)
 PRE-ENGINEERED A/C STANDS
  
  
 2C) 2ND REQUEST. 1ST ROUND OF COMMENTS THE ROOF TOP A/C
 STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE DESIGNER
 OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 2D) 2ND REQUEST. 1ST ROUND OF COMMENTS LATERAL
 FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP EQUIPMENT,
 CURBS, FANS OR A/C STANDS, AND OR VENTS, DETAILED
 ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2020
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2E) 2ND REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR
 APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE
 ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO
 CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO
 ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR
 EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL
 NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL.
  
 2F) 2ND REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR
 APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE
 ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO
 CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO
 ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR
 EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL
 NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL. 2017 FBC-B
 1011.16 LADDERS.
  
 3) 2ND REQUEST. 1ST ROUND OF COMMENTS THE FIXTURE &
 HARDWARE PLAN SHOWS NEW CHECKOUT COUNTERS. THE CHECK
 OUT COUNTERS DO NOT SHOW AN ACCESSIBLE SIDE APPROACH TO
 ANY OF THE 3 REGISTERS, PLEASE SHOW COMPLIANCE WITH THE
 2020 FBC-ACCESSIBILITY CODE SECTIONS:
  
 3A) 2ND REQUEST. 1ST ROUND OF COMMENTS THE FIXTURE &
 HARDWARE FLOOR PLAN DOES NOT SHOW CLEAR FLOOR SPACE AT
 THE CHECK OUT COUNTER, FOE EITHER A FORWARD AND OR SIDE
 APPROACH SHOW COMPLIANCE WITH 305.5 POSITION.
  
 3B) 2ND REQUEST. 1ST ROUND OF COMMENTS THERE IS NO
 ELEVATION VIEWS OF THE CHECKOUT COUNTERS GIVING THE
 HEIGHT AND COMPLIANCE WITH 904.4 SALES AND SERVICE
 COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL
 COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION
 OF THE COUNTERTOP SHALL EXTEND THE SAME DEPTH AS THE
 SALES OR SERVICE COUNTER TOP.
  
 4) 2ND REQUEST. 1ST ROUND OF COMMENTS THE PLANS ARE
 SILENT ARE THE SHELVING UNITS GOING TO BE SECURED TO
 THE FLOOR OR MOVEABLE? 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 08:52 Rev Time 0.00
Received By jwitmer Date 2021-08-31 Time 17:32 Sent To  
Notes
2021-09-01 08:53:39WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21080182
 ADD: 4700 BROADWAY AVE.
 CONT: RETAIL CONTRACTORS
 TEL: 352-302-5496
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 01/2021
 ACTION: DENIED
 1) THE 3 SUBMITTED PLANS FIXTURE / HARDWARE PLAN, FLOOR
 PLAN & MERCHANDISE PLAN WERE NOT DESIGNED BY EITHER A
 ENGINEER OR ARCHITECT, THE CONTRACTOR (QUALIFIER) MUST
 TAKE OWNERSHIP OF ALL 3 PLANS. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2) THE FIXTURE & HARDWARE PLAN SHOWS NEW COOLERS &
 FREEZERS. THE PLANS ARE SILENT AS TO IF THE CONDENSERS
 ARE GOING TO BE REMOTE ROOF TOP CONDENSERS, IF SO SHOW
 COMPLIANCE WITH THE 2020 FBC-B:
  
 2A) 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2B) FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS. 2020 FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31) (G)
 PRE-ENGINEERED A/C STANDS
  
  
 2C) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 2D) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2E) 2020 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL
 WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE
 GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE
 LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET
 WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE
 PARAPET WALL.
  
 2F) 2020 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL
 WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE
 GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE
 LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET
 WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE
 PARAPET WALL. 2017 FBC-B 1011.16 LADDERS.
  
 3) THE FIXTURE & HARDWARE PLAN SHOWS NEW CHECKOUT
 COUNTERS. THE CHECK OUT COUNTERS DO NOT SHOW AN
 ACCESSIBLE SIDE APPROACH TO ANY OF THE 3 REGISTERS,
 PLEASE SHOW COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY
 CODE SECTIONS:
  
 3A) THE FIXTURE & HARDWARE FLOOR PLAN DOES NOT SHOW
 CLEAR FLOOR SPACE AT THE CHECK OUT COUNTER, FOE EITHER
 A FORWARD AND OR SIDE APPROACH SHOW COMPLIANCE WITH
 305.5 POSITION.
  
 3B) THERE IS NO ELEVATION VIEWS OF THE CHECKOUT
 COUNTERS GIVING THE HEIGHT AND COMPLIANCE WITH 904.4
 SALES AND SERVICE COUNTERS. SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE
 ACCESSIBLE PORTION OF THE COUNTERTOP SHALL EXTEND THE
 SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 4) THE PLANS ARE SILENT ARE THE SHELVING UNITS GOING TO
 BE SECURED TO THE FLOOR OR MOVEABLE? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-11 Cont ID  
Sent By jleahy Date 2021-12-11 Time 12:36 Rev Time 0.00
Received By jleahy Date 2021-12-11 Time 12:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-11-05 Cont ID  
Sent By jleahy Date 2021-11-05 Time 12:22 Rev Time 0.00
Received By jleahy Date 2021-11-05 Time 12:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-06 Cont ID  
Sent By jleahy Date 2021-08-06 Time 07:45 Rev Time 0.00
Received By jleahy Date 2021-08-06 Time 07:38 Sent To  
Notes
2021-08-06 07:47:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW CIRCUITS FOR NEW FREEZERS. 215.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-23 Cont ID  
Sent By pleduc Date 2021-11-23 Time   Rev Time 0.00
Received By pleduc Date 2021-11-23 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-06 Cont ID  
Sent By pleduc Date 2021-08-06 Time   Rev Time 0.00
Received By pleduc Date 2021-08-06 Time 12:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-21 Cont ID  
Sent By jwitmer Date 2021-12-21 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2021-12-15 Time 06:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-11 Cont ID  
Sent By jleahy Date 2021-12-11 Time 12:37 Rev Time 0.00
Received By jleahy Date 2021-11-22 Time 06:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-09 Cont ID  
Sent By jwitmer Date 2021-11-09 Time 11:10 Rev Time 0.00
Received By jwitmer Date 2021-10-29 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-09-01 Time   Rev Time 0.00
Received By cdecoeur Date 2021-08-05 Time 07:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2021-12-17 Cont ID  
Sent By medwards Date 2021-12-17 Time 15:41 Rev Time 0.00
Received By medwards Date 2021-12-17 Time 15:41 Sent To  
Notes
2021-12-17 15:42:31NO MECHANICAL WORK BEING COMPLETED UNDER THIS PERMIT.
 THE COOLERS ARE FULLY SELF CONTAINED. ME

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-11-24 Cont ID  
Sent By medwards Date 2021-11-24 Time 08:08 Rev Time 0.00
Received By medwards Date 2021-11-24 Time 08:08 Sent To  
Notes
2021-11-24 08:09:123RD CYCLE REVIEW:
  
 PLEASE RESPOND TO MY FIRST REVIEW COMMENTS BELOW:
  
 ARE THE NEW COOLERS AND FREEZER SELF CONTAINED UNITS OR
 ARE THE CONDENSERS ON THE ROOF? IF THEY ARE ON THE ROOF
 A SEPERATE PERMIT AND REVIEW WILL BE REQUIRED FOR
 THESE.IF THE CONDENSING UNITS ARE ON THE ROOF PLEASE
 SUBMIT THE SPECIFICATIONS FOR THEM IN THE REQUIRED
 SEPARATE REVIEW PACKAGE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-04 Cont ID  
Sent By medwards Date 2021-11-04 Time 06:03 Rev Time 0.00
Received By medwards Date 2021-11-04 Time 06:03 Sent To  
Notes
2021-11-04 06:04:29PLEASE RESPOND TO MY FIRST REVIEW COMMENTS BELOW:
  
 ARE THE NEW COOLERS AND FREEZER SELF CONTAINED UNITS OR
 ARE THE CONDENSERS ON THE ROOF? IF THEY ARE ON THE ROOF
 A SEPERATE PERMIT AND REVIEW WILL BE REQUIRED FOR
 THESE.IF THE CONDENSING UNITS ARE ON THE ROOF PLEASE
 SUBMIT THE SPECIFICATIONS FOR THEM IN THE REQUIRED
 SEPARATE REVIEW PACKAGE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-09 Cont ID  
Sent By medwards Date 2021-08-09 Time 07:34 Rev Time 0.00
Received By medwards Date 2021-08-09 Time 07:34 Sent To  
Notes
2021-08-09 07:37:53ARE THE NEW COOLERS AND FREEZER SELF CONTAINED UNITS OR
 ARE THE CONDENSERS ON THE ROOF? IF THEY ARE ON THE ROOF
 A SEPERATE PERMIT AND REVIEW WILL BE REQUIRED FOR
 THESE.IF THE CONDENSING UNITS ARE ON THE ROOF PLEASE
 SUBMIT THE SPECIFICATIONS FOR THEM IN THE REQUIRED
 SEPARATE REVIEW PACKAGE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-08-20 Cont ID  
Sent By ccole Date 2021-08-20 Time 12:37 Rev Time 0.00
Received By ccole Date 2021-08-20 Time 12:37 Sent To  
Notes
2021-08-20 12:45:41NO PLUMBING PLANS SUBMITTED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-21 Cont ID  
Sent By jwitmer Date 2021-12-21 Time 11:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To SIGNATURE
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 08:52 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 08:52:29THE 3 SUBMITTED PLANS FIXTURE / HARDWARE PLAN, FLOOR
 PLAN & MERCHANDISE PLAN WERE NOT DESIGNED BY EITHER A
 ENGINEER OR ARCHITECT, THE CONTRACTOR (QUALIFIER) MUST
 TAKE OWNERSHIP OF ALL 3 PLANS. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  