Plan Review Details - Permit 21080156
Plan Review Stops For Permit 21080156
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-09-09 Cont ID  
Sent By lmarchan Date 2021-09-09 Time 11:06 Rev Time 0.00
Received By lmarchan Date 2021-09-09 Time 11:06 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By pvalenti Date 2021-09-07 Time 06:16 Rev Time 0.00
Received By pvalenti Date 2021-09-07 Time 06:13 Sent To  
Notes
2021-09-07 06:17:42PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-10-15 Cont ID  
Sent By pvalenti Date 2021-10-15 Time 07:33 Rev Time 0.00
Received By pvalenti Date 2021-10-15 Time 07:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-04 Cont ID  
Sent By pvalenti Date 2021-10-04 Time 07:53 Rev Time 0.00
Received By pvalenti Date 2021-10-04 Time 07:38 Sent To  
Notes
2021-10-04 07:54:52PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED
 (SUBMIT APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By pvalenti Date 2021-09-07 Time 06:18 Rev Time 0.00
Received By pvalenti Date 2021-09-07 Time 06:13 Sent To  
Notes
2021-09-07 06:29:26PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 WATER DOWN METHOD DURING DEMOLITION:
  
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFORMATION INCLUDING WATER TANK CAPACITY AND A LETTER
 THAT STATES THE WATER USED WILL BE POTABLE WATER FROM
 OFF-SITE LOCATION ONLY AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER IS DESIRED, THEN A PARTIAL RELEASE
 WILL BE
 NOTED ON THEIR FORM.
 IF A BACKFLOW PREVENTER DEVICE IS DESIRED, A SEPARATE
 PERMIT FOR A BACKFLOW PREVENTER DEVICE IS REQUIRED.
 BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561-822-2244.
  
  
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT
 DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED
 FOR RODENTS.
  
 6. COMPLETE THE DEMO DEBRIS FORM:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED,
 FBC 107.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By rrossano Date 2021-10-15 Time   Rev Time 0.00
Received By rrossano Date 2021-10-15 Time   Sent To  
Notes
2021-10-15 08:25:57PASSED WITH PROVISO:
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-08-31 Cont ID  
Sent By rrossano Date 2021-08-31 Time   Rev Time  
Received By rrossano Date 2021-08-31 Time   Sent To  
Notes
2021-08-31 12:38:06PROVIDE ALL REQUIRED ASSOCIATED DOCUMENTS - STORMWATER
 POLLUTION PREVENTION PLAN, AND UTILITY SIGNOFFS -
 WATER/SEWER, PEST, FPL, FPU, ASBESTOS ETC.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 [email protected] WWW.WPB.ORG/ENGINEERING

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-09-07 Cont ID  
Sent By fmittner Date 2021-09-07 Time 15:19 Rev Time 0.00
Received By fmittner Date 2021-09-07 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-15 Cont ID  
Sent By pvalenti Date 2021-10-15 Time 14:34 Rev Time 0.00
Received By pvalenti Date 2021-09-24 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-08 Cont ID  
Sent By lmarchan Date 2021-09-08 Time 08:55 Rev Time 0.00
Received By lmarchan Date 2021-08-13 Time 09:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-09-07 Cont ID  
Sent By pvalenti Date 2021-09-07 Time 06:18 Rev Time 0.00
Received By pvalenti Date 2021-09-07 Time 06:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-07 Cont ID  
Sent By fmittner Date 2021-09-07 Time 15:19 Rev Time 0.00
Received By fmittner Date 2021-09-07 Time 15:19 Sent To  
Notes
***NONE***