| 2021-08-26 09:23:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21080147 1411 N FLAGLER DR # 6700 |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.THE REVISED PLUMBING RISER AND PLAN VIEW INDICATE A |
| | REAR OUTLET WATER CLOSET WILL BE REQUIRED FOR THE |
| | PATIENT TOILET ROOM. PER WPB FBC 107.2.1, SPECIFY, |
| | PROVIDE DESIGNATION, REVISE FIXTURE SCHEDULE ON P0.1 |
| | AND SUBMIT. |
| | |
| | 2.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER |
| | SPECIFICATION/INSTALLATION MANUAL(S) FOR THE KEMPER |
| | BALANCING VALVE AND KHS FLOW SPLITTERS. |
| | |
| | 3. PER WPB FBC 107.2.1, INDICATE THE KEMPER BALANCING |
| | VALVE ON WATER HEATER DETAIL ON P0.1. |
| | |
| | 4.IT IS ALSO NOTED AT THIS TIME THAT THE EXPANSION TANK |
| | IN THE WATER HEATER DETAIL ON P0.1 IS LOCATED UPSTREAM |
| | OF THE CHECK VALVE. FBC PL 607.3, PLACE EXPANSION TANK |
| | BETWEEN THE CHECK VALVE AND THE WATER HEATER. |
| | |
| | 5.REVISED FLOOR PLAN P1.1 FOR PATIENT TOILET ROOM DOES |
| | NOT MATCH BATHROOM FIXTURE CONFIGURATION ON A-1.0. PER |
| | FBC 107.2.1, CLARIFY AND RECONCILE. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21080147 1411 N FLAGLER DR # 6700 |