Plan Review Details - Permit 21080139
Plan Review Stops For Permit 21080139
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 11:51 Rev Time 0.00
Received By shill Date 2021-08-21 Time 11:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-08-12 Cont ID  
Sent By pleduc Date 2021-08-12 Time   Rev Time 0.00
Received By pleduc Date 2021-08-12 Time 13:18 Sent To  
Notes
2021-08-12 13:20:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF FLOOR UNDERLAYMENT WITH A
 SPEC SHEET BUT NO SPECIFICATIONS SHEETS FOR THE
 FINNISHED FLOOR PRODUCT THAT MEET THE REQUIREMENTS PER
 NFPA
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 11:56 Rev Time 0.00
Received By shill Date 2021-08-11 Time 11:32 Sent To  
Notes
***NONE***