Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-12-20 Cont ID  
Sent By rmcphers Date 2021-12-20 Time 08:08 Rev Time 0.00
Received By rmcphers Date 2021-12-20 Time 08:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 08:16 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 08:07 Sent To  
Notes
2021-12-14 08:16:33ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) IN PROJECTDOX "DRAWINGS" FOLDER - DETAIL PAGE 06 IS
 TOPPED WITH A COVER PAGE - PLEASE REUPLOAD DETAIL PAGE
 06.
  
 2) DRAWING 04 SHOWS PRODUCT APPROVAL (FL16440 R22) TO
 BE USED - YOU HAVE PROVIDED (NOA18-0108.21) - PLEASE
 REVISE DRAWING 04 TO SHOW THE CORRECT PRODUCT APPROVAL
 TO BE USED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-04 Cont ID  
Sent By jbrooks Date 2021-11-04 Time 13:00 Rev Time 0.00
Received By jbrooks Date 2021-11-04 Time 07:44 Sent To  
Notes
2021-11-04 13:00:32JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER MIAMI-DADE COUNTY NOA NO.
 18-0108.20 SYSTEM TYPE D(1) LIMITATIONS #7. PLEASE NOTE
 THIS PROJECT IS LOCATED IN AN EXPOSURE C CATEGORY.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), ROOF
 HEIGHT(S).
 3. FBC B 107.3.4.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.: 18-0108.20 SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-07 Cont ID  
Sent By ccole Date 2021-09-07 Time 08:30 Rev Time 0.00
Received By ccole Date 2021-09-07 Time 08:30 Sent To  
Notes
2021-09-07 08:32:03COMMENTS FROM THE 1ST REVIEW LISTED BELOW WERE NOT
 ADDRESSED. PLEASE COMPLY.
  
 ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOFING -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 OR 9 ON
 THE PRODUCT APPROVAL. SHOW THE WIND DESIGN DATA USED ON
 THE ADDITIONAL ATTACHMENT DETAILS PER 2020 FBC AND ASCE
 7-16 - WIND SPEED - EXPOSURE - RISK CATEGORY - ETC.
 2) DRAWINGS PROVIDED NEEDS TO SHOW THE WIND DESIGN DATA
 USED FOR THE WIND DESIGN FBC 1603.1.4 - FBC WPB
 107.2.1.1
 3) DRAWINGS PAGE 6 DETAIL "B" AND "C" NEED TO SHOW THE
 EDGE BLOCKING (WOOD NAILER SIZE) ATTACHMENT SIZE,
 LENGTH AND ON CENTER SPACING. FBC WPB 107.2.1.1
 4) PLEASE SHOW THE ROOF SLOPE AND BUILDING HEIGHT FBC
 WPB 107.2.1.1
 5) PLEASE PROVIDE A STRUCTURAL ANALYSIS FROM A DESIGN
 PROFESSIONAL SHOWING THAT THE EXISTING BUILDING CAN
 HANDLE THE ADDITIONAL ROOF LOADS - FBC EXISTING
 BUILDING 707.2 ADDITION OR REPLACEMENT OF ROOFING OR
 REPLACEMENT OF EQUIPMENT. WHERE ADDITION OR REPLACEMENT
 OF ROOFING OR REPLACEMENT OF EQUIPMENT RESULTS IN
 ADDITIONAL DEAD LOADS, STRUCTURAL COMPONENTS SUPPORTING
 SUCH REROOFING OR EQUIPMENT SHALL COMPLY WITH THE
 GRAVITY LOAD REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING.
 6) DRAWING LABELED "PDC BUILDING H - PERMIT SET.PDF" IN
 PROJECTDOX "SUPORTING DOC" FOLDER IS A PACKAGE OF
 DRAWINGS - PLEASE SEPARATE THE PACKAGE OF DRAWINGS IN
 THE "DRAWING" FOLDER IN PROJECTDOX.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-27 Cont ID  
Sent By rmcphers Date 2021-08-27 Time 10:17 Rev Time 0.00
Received By rmcphers Date 2021-08-27 Time 09:28 Sent To  
Notes
2021-08-27 10:10:23ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOFING -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 OR 9 ON
 THE PRODUCT APPROVAL. SHOW THE WIND DESIGN DATA USED ON
 THE ADDITIONAL ATTACHMENT DETAILS PER 2020 FBC AND ASCE
 7-16 - WIND SPEED - EXPOSURE - RISK CATEGORY - ETC.
 2) DRAWINGS PROVIDED NEEDS TO SHOW THE WIND DESIGN DATA
 USED FOR THE WIND DESIGN FBC 1603.1.4 - FBC WPB
 107.2.1.1
 3) DRAWINGS PAGE 6 DETAIL "B" AND "C" NEED TO SHOW THE
 EDGE BLOCKING (WOOD NAILER SIZE) ATTACHMENT SIZE,
 LENGTH AND ON CENTER SPACING. FBC WPB 107.2.1.1
 4) PLEASE SHOW THE ROOF SLOPE AND BUILDING HEIGHT FBC
 WPB 107.2.1.1
 5) PLEASE PROVIDE A STRUCTURAL ANALYSIS FROM A DESIGN
 PROFESSIONAL SHOWING THAT THE EXISTING BUILDING CAN
 HANDLE THE ADDITIONAL ROOF LOADS - FBC EXISTING
 BUILDING 707.2 ADDITION OR REPLACEMENT OF ROOFING OR
 REPLACEMENT OF EQUIPMENT. WHERE ADDITION OR REPLACEMENT
 OF ROOFING OR REPLACEMENT OF EQUIPMENT RESULTS IN
 ADDITIONAL DEAD LOADS, STRUCTURAL COMPONENTS SUPPORTING
 SUCH REROOFING OR EQUIPMENT SHALL COMPLY WITH THE
 GRAVITY LOAD REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING.
 6) DRAWING LABELED "PDC BUILDING H - PERMIT SET.PDF" IN
 PROJECTDOX "SUPORTING DOC" FOLDER IS A PACKAGE OF
 DRAWINGS - PLEASE SEPARATE THE PACKAGE OF DRAWINGS IN
 THE "DRAWING" FOLDER IN PROJECTDOX.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status P Date 2022-01-03 Cont ID  
Sent By rmcdouga Date 2022-01-03 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2022-01-03 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-12-20 Cont ID  
Sent By rmcphers Date 2021-12-20 Time 08:09 Rev Time 0.00
Received By rmcphers Date 2021-12-16 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 08:19 Rev Time 0.00
Received By rmcphers Date 2021-12-09 Time 07:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-04 Cont ID  
Sent By jbrooks Date 2021-11-04 Time 13:03 Rev Time 0.00
Received By jbrooks Date 2021-11-03 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-09-07 Time   Rev Time 0.00
Received By aoliver Date 2021-08-31 Time 06:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-27 Cont ID  
Sent By rmcphers Date 2021-08-27 Time 10:17 Rev Time 0.00
Received By rmcphers Date 2021-08-26 Time 10:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-01-03 Cont ID  
Sent By rmcdouga Date 2022-01-03 Time 16:15 Rev Time 0.00
Received By rmcdouga Date 2022-01-03 Time 16:15 Sent To  
Notes
2022-01-03 16:17:05SIGNED AND SEALED PLANS SHEETS 1-8 WERE SENT TO
 STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-12-20 Cont ID  
Sent By rmcphers Date 2021-12-20 Time 08:09 Rev Time 0.00
Received By rmcphers Date 2021-12-20 Time 08:09 Sent To  
Notes
2021-12-20 08:09:53SIGNATURE REVIEW
  
 ALL OF THE DRAWINGS - DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 08:17 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 08:17 Sent To  
Notes
2021-12-14 08:19:21SIGNATURE REVIEW
  
 ALL OF THE DRAWINGS - DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-04 Cont ID  
Sent By jbrooks Date 2021-11-04 Time 13:03 Rev Time 0.00
Received By jbrooks Date 2021-11-04 Time 07:44 Sent To  
Notes
2021-11-04 13:01:27JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL OR DROP OFF ONE ORIGINAL SIGNED
 AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE TO:
 PETER VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By ccole Date 2021-09-07 Time 08:33 Rev Time 0.00
Received By ccole Date 2021-09-07 Time 08:32 Sent To  
Notes
2021-09-07 08:46:31SIGNATURE REVIEW
 9/7/2021
  
 1) THE ROOF PLANS SHALL BE DIGITALLY SIGNED AND SEALED
 BY THE ARCHITECT IN ACCORDANCE WITH FL STATUTE 481.221
 AND SECTION 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
 SIGNED AND SEALED DRAWINGS TRANSMITTED ELECTRONICALLY
 PROJECTDOX NEED TO BE DIGITALLY SIGNED BY ARCHITECT TO
 BE USED IN ELECTRONIC PLAN REVIEW. DRAWINGS DO NOT SHOW
 IN "ADOBE READER" AS DIGITALLY/ELECTRONICALLY SIGNED. -
 OR - IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  