Plan Review Details - Permit 21080098
Plan Review Stops For Permit 21080098
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-09-30 Cont ID  
Sent By lmarchan Date 2021-09-30 Time 12:12 Rev Time 0.00
Received By lmarchan Date 2021-09-30 Time 12:12 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-09-28 Cont ID  
Sent By pvalenti Date 2021-09-28 Time 13:44 Rev Time 0.00
Received By pvalenti Date 2021-09-28 Time 13:44 Sent To  
Notes
2021-09-28 13:51:24 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS COMMENTS:
  
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-08-20 Time   Rev Time  
Received By   Date 2021-08-20 Time   Sent To  
Notes
2021-08-21 13:00:49PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 12:59 Rev Time 0.00
Received By shill Date 2021-08-21 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-18 Cont ID  
Sent By fgiaquin Date 2021-10-18 Time 20:47 Rev Time 0.00
Received By fgiaquin Date 2021-10-18 Time 20:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-15 Cont ID  
Sent By fgiaquin Date 2021-09-15 Time 22:34 Rev Time 0.00
Received By fgiaquin Date 2021-09-15 Time 21:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-16 Cont ID  
Sent By cwalker Date 2021-08-16 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-18 Cont ID  
Sent By fgiaquin Date 2021-10-18 Time 20:47 Rev Time 0.00
Received By fgiaquin Date 2021-09-27 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2021-09-15 Cont ID  
Sent By fgiaquin Date 2021-09-15 Time 22:35 Rev Time 0.00
Received By fgiaquin Date 2021-08-13 Time 15:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-08-24 Cont ID  
Sent By medwards Date 2021-08-24 Time 11:06 Rev Time 0.00
Received By medwards Date 2021-08-24 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-28 Cont ID  
Sent By pvalenti Date 2021-09-28 Time 13:18 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:48 Sent To  
Notes
2021-09-28 13:19:1221080098 3800 WASHINGTON RD # 1108
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21080098 3800 WASHINGTON RD # 1108
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-02 Cont ID  
Sent By pvalenti Date 2021-09-02 Time 15:44 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:48 Sent To  
Notes
2021-09-02 15:45:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080098 3800 WASHINGTON RD # 1108
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.EXISTING FLOOR PLAN SHOWS BATH #1 WITH BATHTUB.
 PROPOSED PLAN SHOWS A SHOWER. ELECTRICAL PLAN SHOWS A
 SHOWER, SHOWER PAN DETAIL, CURB DETAIL AND VANITY
 DETAIL. SCOPE OF WORK ONLY INDICATES KITCHEN
 REPLACEMENT. PER WPB FBC 107.2.1, CLARIFY.
  
 2.NEW KITCHEN SINK IS RELOCATED FROM EXISTING SINK
 LOCATION AND A DISHWASHER HAS BEEN ADDED. PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING NOTES.
 ?A) MODIFY IN WALL EXISTING HOT AND COLD WATER PIPE TO
 ACCOMMODATE NEW KITCHEN SINK. COMPLY WITH FBC PL 604,
 605, 606.
 ?B) MODIFY IN WALL EXISTING KITCHEN WASTE FIXTURE DRAIN
 TO ACCOMMODATE NEW KITCHEN SINK. COMPLY WITH FBC PL
 909.1 AND TABLE 909.1.
 ?C) PER FBC PL 604.9, A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES (DISHWASHER AND
 ICE LINE) ARE UTILIZED. WATER-HAMMER ARRESTORS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010
 ?D) PER FBC PL 409.4, THE WASTE CONNECTION OF A
 RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE
 BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK,
 DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE
 DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE
 WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND
 BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM
 OR COUNTER TOP.
 ?E) PER FBC PL 412.3, INDIVIDUAL SHOWER AND TUB-SHOWER
 COMBINATION VALVES SHALL BE BALANCED-PRESSURE,
 THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
  
 3.PER WPB FBC 107.2.1, INDICATE ANY ICE MAKER AND IF
 THERE IS ONE, SHOW HOW WATER IS TO BE PROVIDED AND HOW
 CONDENSATE WOULD BE REMOVED IF APPLICABLE.
  
 4. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR FLOOR
 PENETRATION SHOWER DRAIN RELOCATION TUB TO SHOWER.
 COMPLY WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21080098 3800 WASHINGTON RD # 1108

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-27 Cont ID  
Sent By jleahy Date 2021-10-27 Time 14:44 Rev Time 0.00
Received By jleahy Date 2021-10-27 Time 14:44 Sent To  
Notes
2021-10-27 14:45:42CONTRACTOR TO BRING IN A SIGNED COPY FOR OUR RECORDS
 JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-28 Cont ID  
Sent By pvalenti Date 2021-09-28 Time 13:42 Rev Time 0.00
Received By pvalenti Date 2021-09-28 Time 13:42 Sent To  
Notes
2021-09-28 13:44:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-15 Cont ID  
Sent By fgiaquin Date 2021-09-15 Time 22:35 Rev Time 0.00
Received By fgiaquin Date 2021-09-15 Time 22:35 Sent To  
Notes
***NONE***