Plan Review Details - Permit 21080065
Plan Review Stops For Permit 21080065
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-03 Cont ID  
Sent By cthroop Date 2021-09-03 Time 06:25 Rev Time 0.00
Received By cthroop Date 2021-09-02 Time 16:42 Sent To  
Notes
2021-09-03 06:54:58BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/RPX306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 REF. OPENING #5 ON SHUTTER SCHEDULE AND FL31658-R2 FOR
 THE FOLLOWING COMMENTS:
  
 1. PER PRODUCT APPROVAL, NOTE #6. THIS IS A MOTOR
 DRIVEN ROLL-UP SHUTTER. AN ELECTRICAL PERMIT IS
 REQUIRED. SEE COMMENTS UNDER ELECTRICAL REVIEW.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE PRODUCT APPROVAL FOR ROLL-UP MECHANISM AND
 HOOD ASSEMBLY.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PER PRODUCT APPROVAL, PAGE 7, FASTENER SCHEDULE,
 FASTENERS SHALL BE 1/4" ALL-POINTS SOLID SET.
  
 REF. OPENINGS 1 THRU 4 AND 6 THRU 10 ON SHUTTER
 SCHEDULE AND FL1850-R13 FOR THE FOLLOWING COMMENT:
  
 4. SEE PRODUCT APPROVAL, PAGE 12, FASTENER SCHEDULE,
 FASTENERS SHALL BE TAPCONS W/ADVANCED THREAD FORM
 TECHNOLOGY.
  
 REF. SHUTTER SCHEDULE FOR THE FOLLOWING COMMENT:
  
 5. TYPE OF ANCHOR SPECIFIED. WHEN MORE THAN ONE TYPE OF
 DEVICE IS INSTALLED, INCLUDE ALL TYPES OF ANCHORS USED.
 ANCHORS SHALL BE SPECIFIC PER NOTE #1 ON SHUTTER
 SCHEDULE.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-02 Cont ID  
Sent By cthroop Date 2021-09-02 Time 18:47 Rev Time 0.00
Received By cthroop Date 2021-09-02 Time 18:15 Sent To  
Notes
2021-09-02 18:52:38ELECTRICAL PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/RPX306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: FLOOR PLAN INDICATES OPENING #5 WILL BE A MOTOR
 DRIVEN ROLL UP SHUTTER.
  
 1. PROVIDE AN ELECTRICAL PERMIT.
 105.1 REQUIRED.
  
 2. PROVIDE AN ELECTRICAL DISCONNECT FOR THE MOTOR
 CONNECTION.
 E4101.5 DISCONNECTING MEANS.
  
 3. PROVIDE AN UPDATED PANEL SCHEDULE. IDENTIFY MOTOR
 CIRCUT.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-03 Cont ID  
Sent By cthroop Date 2021-09-03 Time 06:55 Rev Time 0.00
Received By cthroop Date 2021-08-11 Time 11:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-03 Cont ID  
Sent By cthroop Date 2021-09-03 Time 05:45 Rev Time 0.00
Received By cthroop Date 2021-09-02 Time 18:39 Sent To  
Notes
2021-09-03 06:05:09SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/RPX306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 REF. DESIGN WIND LOADS PER ASCE 7-16
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT. SEE NOTICE
 BELOW:
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 NOTICE:
  
 FOR RESIDENTIAL PROPERTIES, DESIGN WIND LOADS ARE NOT
 REQUIRED TO BE PREPARED BY A DESIGN PROFESSIONAL. THE
 CONTRACTOR MAY PROVIDE DESIGN WIND LOADS. REFERENCE FBC
 R CHPT. 3.
  
 YOU MAY RE-SUBMIT THE DESIGN WIND LOADS WITH A VALID
 DIGITAL SIGNATURE OF A DESIGN PROFESSIONAL, SUBMIT
 DESIGN WIND LOADS PREPARED BY THE CONTRACTOR OR TAKE NO
 ACTION.
 IF NO ACTION TAKEN, I AM REQUIRED TO LOCK THEM FROM
 PRINTING DUE TO AN INVALID SIGNATURE OF THE DESIGN
 PROFESSIONAL BUT WILL NOT FAIL YOUR 2ND REVIEW BASED ON
 THIS.
  
 I CAN VERIFY THE SITE DESIGN WIND LOADS PER FBC R CHPT.
 3 BUT A PREPARDD DESIGN WIND LOAD CHART EXPEDITES THE
 REVIEW PROCESS.
  