Plan Review Details - Permit 21080055
Plan Review Stops For Permit 21080055
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-08-03 Cont ID  
Sent By cpuell Date 2021-08-03 Time 17:04 Rev Time 0.00
Received By cpuell Date 2021-08-03 Time 17:04 Sent To  
Notes
2021-08-03 17:05:35BUILDING TO BE REROOFED IS THE GARAGE, THE PRIMARY
 ADDRESS OF 5611 SPRUCE AVE IS CORRECT AS IT IS THE
 PARCEL ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By jbrooks Date 2021-08-18 Time 12:30 Rev Time 0.00
Received By jbrooks Date 2021-08-18 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By jbrooks Date 2021-08-04 Time 09:01 Rev Time 0.00
Received By jbrooks Date 2021-08-04 Time 07:49 Sent To  
Notes
2021-08-04 09:01:28JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150.
 SUBMITTED MIAMI-DADE COUNTY NOA 17-0222.09 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A THROUGH E (3). ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. GENERAL
 LIMITATION #7 IS SPECIFICALLY REFERRED TO IN THIS NOA.
 SUBMIT FASTENER DENSITY CALCULATIONS PREPARED, SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT, OR REGISTERED ROOF
 CONSULTANT.
 2. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART
 OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS
 BY YOUR BUILDING INSPECTOR.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-08-06 Cont ID  
Sent By fmittner Date 2021-08-06 Time 15:22 Rev Time 0.00
Received By fmittner Date 2021-08-06 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-18 Cont ID  
Sent By jbrooks Date 2021-08-18 Time 12:30 Rev Time 0.00
Received By jbrooks Date 2021-08-17 Time 12:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-09 Cont ID  
Sent By pvalenti Date 2021-08-09 Time 08:35 Rev Time 0.00
Received By pvalenti Date 2021-08-03 Time 15:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By jleahy Date 2021-08-18 Time 10:10 Rev Time 0.00
Received By jleahy Date 2021-08-18 Time 10:10 Sent To  
Notes
2021-08-18 10:11:23SIGNED CALCULATION SENT TO STORAGE JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By jbrooks Date 2021-08-04 Time 09:03 Rev Time 0.00
Received By jbrooks Date 2021-08-04 Time 09:03 Sent To  
Notes
2021-08-04 09:04:15JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL OR DROP OFF ONE ORIGINAL SIGNED
 AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE TO:
 PETER VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6673.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved