Plan Review Details - Permit 21080054
Plan Review Stops For Permit 21080054
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-08-13 Cont ID  
Sent By cpuell Date 2021-08-13 Time 09:13 Rev Time 0.00
Received By cpuell Date 2021-08-13 Time 09:13 Sent To  
Notes
2021-08-13 09:14:46GAS METER LOCATED BEHIND COTTAGE IN REAR HOWEVER IT
 WILL BE SERVICING MAIN HOUSE ONLY. HALF ADDRESS HAD
 BEEN READDRESSED FROM 728 1/2 AVON RD TO 728 AVON RD #
 2

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-03 Cont ID  
Sent By cpuell Date 2021-08-03 Time 12:59 Rev Time 0.00
Received By cpuell Date 2021-08-03 Time 12:59 Sent To  
Notes
2021-08-03 12:59:17WHICH BUILDING IS THE WORK TO BE DONE, NORTH OR SOUTH?
 THE SOUTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED
 TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6559 TO READDRESS THE
 HALF ADDRESS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-08-13 Cont ID  
Sent By lcrespo Date 2021-08-13 Time 09:14 Rev Time 0.00
Received By lcrespo Date 2021-08-13 Time 09:14 Sent To  
Notes
2021-08-13 09:15:1108/13/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 10:14 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 09:31 Sent To  
Notes
2021-08-10 10:14:5308/10/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT
 SYSTEM. A COMPLETE EVALUATION OF ALL GAS SYSTEMS AND
 EQUIPMENT WILL BE DONE AT THE FIELD, AND IF NOT TO
 CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT
 THE OWNER'S EXPENSE. PLEASE INCLUDE THE CURRENT AND NEW
 GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE
 OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. METAL PIPES INSTALLED OUTDOORS SHALL BE ELEVATED NOT
 LESS THAN 3 1/2 INCHES ABOVE THE GROUND AND WERE
 INSTALLED ACROSS ROOF SURFACES PER THE 2020 FBC SEC
 G2415.9 (404.9) ABOVE-GROUND PIPING.
  
 3. GAS RISER DIAGRAM REQUIRED AND ON ISOMETRIC DRAWING
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2, AND WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS.
  
 4. WHEN USING THE LONGEST LENGTH OF PIPING FROM THE
 POINT OF DELIVERY TO THE MOST REMOTE OUTLET AND THE
 LOAD ON THE SECTION. SHOW THE DISTANCE FROM THE POINT
 OF DELIVERY (GAS METER) TO THE MOST REMOTE OUTLET IN
 THE BUILDING AND/OR SYSTEM PER THE 2020 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 5. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. TELL US IF (LP OR NATURAL) PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 8. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC.
 G2413.
  
 9. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE
 PLAN PER THE 2020 FBC RES. SEC. G2413.2.
  
 10. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 11. PLEASE SUBMIT THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER
 THE 2020 FBC RES. SEC. G2413.3.
  
 12. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE
 ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
 13. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 14. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 15. IF APPLICABLE, PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 16. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION. WOULD YOU PLEASE PROVIDE A BONA FIDE
 SIGNED CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC.
 109.3 BUILDING PERMIT VALUATIONS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-13 Cont ID  
Sent By lcrespo Date 2021-08-13 Time 09:15 Rev Time 0.00
Received By lcrespo Date 2021-08-13 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 10:16 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 11:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-08-13 Cont ID  
Sent By lcrespo Date 2021-08-13 Time 09:14 Rev Time 0.00
Received By lcrespo Date 2021-08-13 Time 09:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 10:16 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 09:31 Sent To  
Notes
***NONE***