Plan Review Details - Permit 21071627
Plan Review Stops For Permit 21071627
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-09-14 Cont ID  
Sent By cpuell Date 2021-09-14 Time 13:07 Rev Time 0.00
Received By cpuell Date 2021-09-14 Time 13:07 Sent To  
Notes
2021-09-14 13:10:23WORK TO BE DONE ON THE BACK BUILDING WHICH HAS AN
 ADDRESS OF 241 9TH ST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-11-01 Cont ID  
Sent By jgomez Date 2021-11-01 Time 10:44 Rev Time 0.00
Received By jgomez Date 2021-11-01 Time 09:55 Sent To  
Notes
2021-11-01 09:56:36BUILDING APPROVED WITH PROVISO:
 1- GARAGE STRUCTURAL BUCK DETAIL: NEED TO PROVIDE
 COMPLETE FASTENING SPECIFICATIONS FOR NEW 2X6 P.T. STUD
 WALL RECEIVING THE STRUCTURAL BUCK.
 2- PROVIDE PRODUCT APPROVAL FOR ENTRY DOOR AND EXTERIOR
 BATH DOOR AS SHOWN ON PLANS.
 3- WINDOW MULLIONS: NEED TO SPECIFY MULLION SIZE.
 4-ENGINEER OF RECORD TO REVIEW/APPROVED ABOVE PRODUCT
 APPROVALS.
 NOTE: PROVIDE INFORMATION PRIOR TO INSTALLATION TO
 AVOID CONFLICTS/DELAYS. ALL PRODUCT APPROVALS TO BE
 APPROVED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By jgomez Date 2021-10-20 Time 14:30 Rev Time 0.00
Received By jgomez Date 2021-10-20 Time 09:42 Sent To  
Notes
2021-10-20 14:30:14BUILDING APPROVED WITH PROVISO:
 1- GARAGE STRUCTURAL BUCK DETAIL: NEED TO PROVIDE
 COMPLETE FASTENING SPECIFICATIONS FOR NEW 2X6 P.T. STUD
 WALL RECEIVING THE STRUCTURAL BUCK.
 2- PROVIDE PRODUCT APPROVAL FOR ENTRY DOOR AND EXTERIOR
 BATH DOOR AS SHOWN ON PLANS.
 3- WINDOW MULLIONS: NEED TO SPECIFY MULLION SIZE.
 NOTE: PROVIDE INFORMATION PRIOR TO INSTALLATION TO
 AVOID CONFLICTS/DELAYS. ALL PRODUCT APPROVALS TO BE
 APPROVED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jgomez Date 2021-09-01 Time 13:32 Rev Time 0.00
Received By jgomez Date 2021-09-01 Time 09:32 Sent To  
Notes
2021-09-01 13:33:37RESIDENTIAL (R3) ALTERATION LEVEL 3, BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071627.
  
 NOTE:
 LEVEL 3 ALTERATION. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE AS REQUIRED
 BY SEC. 604 FBC-EXISTING BUILDING, SEC. 901.2
 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
  
 1-ENERGY CALCULATIONS SUBMITTED:
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. PROVIDE THE OWNER'S NAME. THE PERMIT OFFICE IS
 CITY OF WEST PALM BEACH NOT PALM BEACH COUNTY. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C)REVISE ITEM #1 ON PAGE 1 OF 4. THIS IS NOT NEW
 CONSTRUCTION.
 SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION
 ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?.
 "DETACHED" IS NOT THE ANSWER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)CLEARLY PROVIDE THE NAME OF PERSON PERFORMING THE
 ANALYSIS AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 F)PROVIDE CORRECT INFORMATION IN THE SPACES SECTION ON
 PAGE 2 OF 4. IS MISSING THE NUMBER OF OCCUPANTS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4 IS
 INCORRECT. THE ROOF OF THIS BUILDING IS PREDOMINANTLY
 FLAT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH
 PLANS. SEE ELEVATIONS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 RECONSTRUCTION OF THE STAIRWAY SHOWING COMPLIANCE WITH
 SEC. R311.7 FBC-RESIDENTIAL.
  
 3- REVISE SPECIFICATIONS ON WALL SECTIONS AND DETAILS
 TO SHOW COMPLIANCE WITH THE DWELLING-GARAGE FIRE
 SEPARATION AS REQUIRED BY SEC. R302.6 FBC-RESIDENTIAL.
  
 4- SECTION A ON SHEET A-5 DOESN'T PROVIDE ANY
 SPECIFICATIONS FOR THE CEILING CONSTRUCTION BELOW THE
 BALCONY AND ABOVE THE OUTDOOR KITCHEN. PROVIDE COMPLETE
 INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- PROVIDE COMPLETE STRUCTURAL BUCK DETAIL AND
 FASTENING SPECIFICATIONS FOR NEW OVERHEAD GARAGE DOOR.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 6- PROVIDE DOOR STRUCTURAL BUCK DETAIL SHOWING
 COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 7- SHEET A-4: THERE ARE SEVERAL NOTES REFERENCING THE
 2014 RESIDENTIAL CODE. THE CURRENT CODE IS
 FBC-RESIDENTIAL SEVENTH EDITION (2020). REVISE ALL
 NOTES REFERENCING THE OLD CODE.
 CHAPTER 553.73 F.S.
  
 8- SECTIONS AND DETAILS NEED TO SPECIFY 7/8" STUCCO
 THICKNESS FOR EXTERIOR APPLICATIONS AS REQUIRED BY SEC.
 R702.2.2 AND TABLE R702.1(1) FBC-RESIDENTIAL.
  
 9- SECTIONS AND DETAILS NEED TO SPECIFY TWO WATER
 RESISTIVE BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS
 REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL.
  
 10- PROVIDE ICC EVALUATION REPORT FOR THE SPRAYED FOAM
 R-20 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 CLEARLY SPECIFY IF THERE IS ANY WINDOW WITH THE SILL
 BELOW 24".
 NOTE: IF REQUIRED, THEN WINDOW OPENING CONTROL DEVICE
 NEEDS TO COMPLY WITH ASTM F2090. PROVIDE INFORMATION
 FOR DEVICE TO BE INSTALLED.
  
 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)EXTERIOR SWING DOORS AS SHOWN ON PLANS. FRENCH DOORS
 AND ENTRY AND BATHROOM DOORS.
 B)OVERHEAD GARAGE DOOR.
 C)WINDOWS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 13-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-22 Cont ID  
Sent By fgiaquin Date 2021-10-22 Time 19:52 Rev Time 0.00
Received By fgiaquin Date 2021-10-22 Time 18:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By fgiaquin Date 2021-08-10 Time 21:38 Rev Time 0.00
Received By fgiaquin Date 2021-08-10 Time 20:26 Sent To  
Notes
2021-08-10 21:38:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ZONING MUST APPROVE SECOND ELECTRICAL SERVICE ON
 GARAGE STRUCTURE. NEC 230.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-10-28 Cont ID  
Sent By ccole Date 2021-10-28 Time 07:52 Rev Time 0.00
Received By ccole Date 2021-10-28 Time 07:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-10-18 Cont ID  
Sent By ccole Date 2021-10-18 Time 14:27 Rev Time 0.00
Received By ccole Date 2021-10-18 Time 13:01 Sent To  
Notes
2021-10-18 14:27:172ND REVIEW FBC-2020 RES.
 PERMIT- 21071627
 10/18/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-3 & G-1: THE NEW RISER SHOWS THE GAS FROM
 THE MAIN HOUSE SUPPLYING THE GAS GRILL AT THE GUEST
 HOUSE. THE CONTRACTOR AND OWNER ARE ADVISED TO CONSULT
 WITH FPU FOR INFORMATION ABOUT GAS METERING AS A
 SEPARATE METER MAY BE REQUIRED. FPU CUSTOMER SERVICE
 NUMBER IS 1-800-427-7712.
  
 2) G-1 GAS RISER:
 A) PROVIDE THE TOTAL LENGTH OF THE PIPING, AND THE
 INDIVIDUAL BRANCH AND CUT PIPE LENGTHS- SECTION
 G2413.4.1.
 B) PROVIDE THE PIPE SIZING TABLES IN ACCORDANCE WITH
 SECTION G2413.4.
  
 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL
 FOR THE GAS GRILL- SECTION G2408.1 & G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By ccole Date 2021-08-13 Time 15:49 Rev Time 0.00
Received By ccole Date 2021-08-13 Time 15:25 Sent To  
Notes
2021-08-13 15:49:451ST REVIEW FBC-2020 RES.
 PERMIT- 21071627
 8/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ELECTRICAL PLAN INDICATES A GAS WATER HEATER AND
 A PROPANE GAS GRILL. PLEASE PROVIDE THE FOLLOWING
 DRAWINGS, DETAILS AND SPECIFICATIONS PER SECTION
 107.2.1 & 107.3.5.3 WPB.
  
 A) PROVIDE A GAS PIPING RISER DRAWING- SECTION G2413.1
 FBC RES.
  
 B) PROVIDE AN EQUIPMENT SCHEDULES FOR THE WATER HEATER
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS- G2408.1 & G2448.1 FBC RES.
  
 C) PROVIDE THE MAKE AND MODEL OF THE GAS GRILL AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUAL- G2408.1 & G2447.1 FBC RES.
  
 D) PROVIDE PLAN AND ELEVATION VIEW DRAWINGS OF THE
 BUILT-IN GAS GRILL SHOWING CLEARANCES TO COMBUSTIBLES
 AND OVERHEAD CONSTRUCTION PER THE MANUFACTURER'S
 RECOMMENDATIONS. PLEASE NOTE THAT MANY OF THE GRILL
 MANUFACTURER?S DO NOT ALLOW INSTALLATIONS IN ENCLOSED
 OR PARTIALLY ENCLOSED STRUCTURES WITH OVERHEAD
 CONSTRUCTION UNLESS A HOOD AND EXHAUST VENT SYSTEM IS
 INSTALLED- G2408.1 & G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-02 Cont ID  
Sent By lmarchan Date 2021-11-02 Time 08:03 Rev Time 0.00
Received By lmarchan Date 2021-11-01 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-01 Cont ID  
Sent By jgomez Date 2021-11-01 Time 10:52 Rev Time 0.00
Received By jgomez Date 2021-10-25 Time 11:20 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-22 Cont ID  
Sent By fgiaquin Date 2021-10-22 Time 19:53 Rev Time 0.00
Received By fgiaquin Date 2021-10-05 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-14 Cont ID  
Sent By cthroop Date 2021-09-14 Time 11:01 Rev Time 0.00
Received By cthroop Date 2021-08-05 Time 09:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-11-08 Cont ID  
Sent By lmarchan Date 2021-11-08 Time 11:38 Rev Time 0.00
Received By lmarchan Date 2021-11-01 Time 08:02 Sent To  
Notes
2021-11-08 11:38:30NO IMPACT FEES DUE - LEM
2021-11-01 11:27:1511/01/21 - IMACT FEE QUESTIONNAIRE UPLOADED - EMAILED
 IMPACT FEE OFFICE. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jgomez Date 2021-09-01 Time 13:39 Rev Time 0.00
Received By jgomez Date 2021-09-01 Time 13:39 Sent To  
Notes
2021-09-01 13:40:07IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-10-06 Cont ID  
Sent By medwards Date 2021-10-06 Time 14:55 Rev Time 0.00
Received By medwards Date 2021-10-06 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-16 Cont ID  
Sent By medwards Date 2021-08-16 Time 12:51 Rev Time 0.00
Received By medwards Date 2021-08-16 Time 11:15 Sent To  
Notes
2021-08-16 12:54:031) THE MECHANICAL CONTRACTOR WILL NEED TO ADD THEIR
 LICENSE NUMBER ON THE MECHANICAL SUB PERMIT. 107.2.1
 2) PLEASE PROVIDE SPECIFICATIONS FOR THE OUTDOOR GRILL.
 IF THE INSTALLATION INSTRUCTIONS REQUIRE A HOOD ABOVE
 THE GRILL PLEASE SUBMIT THE SPECIFICATIONS FOR THE HOOD
 AS WELL. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-10-28 Cont ID  
Sent By ccole Date 2021-10-28 Time 07:51 Rev Time 0.00
Received By ccole Date 2021-10-28 Time 07:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-19 Cont ID  
Sent By ccole Date 2021-10-19 Time 07:32 Rev Time 0.00
Received By ccole Date 2021-10-18 Time 13:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-08-13 Cont ID  
Sent By ccole Date 2021-08-13 Time 15:25 Rev Time 0.00
Received By ccole Date 2021-08-13 Time 14:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-01 Cont ID  
Sent By jgomez Date 2021-11-01 Time 10:08 Rev Time 0.00
Received By jgomez Date 2021-11-01 Time 10:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By jgomez Date 2021-10-20 Time 14:52 Rev Time 0.00
Received By jgomez Date 2021-10-20 Time 14:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-16 Cont ID  
Sent By medwards Date 2021-08-16 Time 13:00 Rev Time 0.00
Received By medwards Date 2021-08-16 Time 13:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-10-27 Cont ID  
Sent By ckimmerl Date 2021-10-27 Time 13:25 Rev Time 0.00
Received By ckimmerl Date 2021-10-27 Time 13:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-10-12 Cont ID  
Sent By ckimmerl Date 2021-10-12 Time 15:12 Rev Time 0.00
Received By ckimmerl Date 2021-10-12 Time 15:12 Sent To  
Notes
2021-10-12 15:12:311. PLEASE PROVIDE A SITE SURVEY. NEED TO
 CLARIFY/CONFIRM IF THE PROPOSED GROUND AC UNIT ON THE
 WESTERN FACADE ENCROACHES INTO THE SIDE SIDEBACK.
 ALTERNATIVELY CAN RELOCATE AC UNIT OUT OF SIDE SETBACK.
  
 CODE STATES: SEC. 94-305 (B)(4) - MECHANICAL EQUIPMENT.
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK. WINDOW AIR-CONDITIONING UNITS MAY
 NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED SIDE
 SETBACK.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-13 Cont ID  
Sent By aaponte Date 2021-09-13 Time 16:08 Rev Time 0.00
Received By ckimmerl Date 2021-09-13 Time 16:00 Sent To  
Notes
2021-09-13 16:05:48- PLEASE PROVIDE A SURVEY, ADDITIONAL SITE INFORMATION,
 AND DIMENSIONS ON THE PROPOSED PLANS. NEED TO
 CLARIFY/CONFIRM IF THE PROPOSED GROUND AC UNIT ON THE
 WESTERN FACADE ENCROACHES INTO THE SIDE SIDEBACK.
 - CODE STATES: SEC. 94-305 (B)(4) - MECHANICAL
 EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK. WINDOW AIR-CONDITIONING
 UNITS MAY NOT PROJECT MORE THAN 18 INCHES INTO A
 REQUIRED SIDE SETBACK.
 - IF AC UNIT DOES NOT ENCROACH INTO SIDE SETBACK, WOULD
 REQUIRE A HEDGE TO SCREEN UNIT FROM VIEW.