| Plan Review Stops For Permit 21071534 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2023-01-03 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-01-03 |
Time |
20:28 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-12-27 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2023-01-03 20:28:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE LOW FOR AMOUNT OF WORK. PLEASE PROVIDE COST | | | BREAKDOWN SHOWING ALL MATERIALS AND LABOR. FBC 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2020 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-03-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-05 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-03-05 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2022-03-05 14:15:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE NOT ADDRESSED. PLEASE SEE LAST PLAN REVIEW | | | COMMENTS FBC 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-12-06 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-12-06 |
Time |
20:49 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-12-06 |
Time |
20:12 |
Sent To |
|
|
| Notes |
| 2021-12-06 20:49:25 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL PROVIDE | | | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. FBC 109.3 | | | PROVIDE CONTRACT SIGNED BY BOTH OWNER AND ELECTRICAL | | | CONTRACTOR QUALIFIER. FBC 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-12-28 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-12-28 |
Time |
|
Rev Time |
|
| Received By |
bdolan |
Date |
2022-12-28 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2022-12-28 12:52:24 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND TESTING FOR FINAL APPROVAL. | | | | | | CAPT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-12-03 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-12-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
jcclark |
Date |
2021-12-03 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2021-12-03 10:40:20 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | JOSEPH CLARK | | | OFFICE OF THE FIRE MARSHAL | | | 561-804-4748 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-01-03 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-01-03 |
Time |
20:28 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-12-21 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-05 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-02-24 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-12-06 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-12-06 |
Time |
20:50 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-11-01 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-12-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-22 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-22 |
Time |
14:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-11-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-30 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-30 |
Time |
07:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-01-03 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-01-03 |
Time |
20:28 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-01-03 |
Time |
18:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-03-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-05 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-12-06 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-12-06 |
Time |
20:50 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-12-06 |
Time |
20:49 |
Sent To |
|
|
| Notes |
| 2021-12-06 20:50:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL PROVIDE | | | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | | | | |
|
|