Plan Review Details - Permit 21071433
Plan Review Stops For Permit 21071433
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2022-08-24 Cont ID  
Sent By jgomez Date 2022-08-24 Time 18:07 Rev Time 0.00
Received By jgomez Date 2022-08-24 Time 17:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-08-03 Cont ID  
Sent By jgomez Date 2022-08-03 Time 18:58 Rev Time 0.00
Received By jgomez Date 2022-08-03 Time 18:56 Sent To  
Notes
2022-08-03 19:00:17RESIDENTIAL (R3) ADDITION, FIFTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071433
  
  
 PREVIOUS COMMENT:
 6- DESIGN PRESSURES OF GARAGE DOOR NOA 20-0416.02 DON'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT
 OF RECORD. NEED PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
 NOTE: NEW PRODUCT APPROVAL TO BE REVIEWED/APPROVED BY
 ARCHITECT PRIOR TO SUBMITTAL.
  
 RESPONSE:
 REPEAT COMMENT (FIVE TIMES). NEW NOA 20-1015.11
 SUBMITTED STILL DON'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT OF RECORD ON SHEET A-1 AND
 SHEET CVR
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-07-06 Cont ID  
Sent By jgomez Date 2022-07-06 Time 11:07 Rev Time 0.00
Received By jgomez Date 2022-07-05 Time 17:45 Sent To  
Notes
2022-07-06 11:08:17RESIDENTIAL (R3) ADDITION, FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071433
  
  
 1- OK.
 2- OK.
 3- OK.
 4- OK.
 5- OK.
  
 PREVIOUS COMMENT:
 6- DESIGN PRESSURES OF GARAGE DOOR NOA 20-0416.02 DON'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT
 OF RECORD. NEED PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
 NOTE: NEW PRODUCT APPROVAL TO BE REVIEWED/APPROVED BY
 ARCHITECT PRIOR TO SUBMITTAL.
  
 RESPONSE:
 REPEAT COMMENT. NEW NOA 20-1015.11 SUBMITTED STILL
 DON'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT OF RECORD.
  
 7- OK.
  
 NEW COMMENTS BASED ON INFORMATION SUBMITTED:
 8- NEW DRAWINGS A-2, A-3 AND P-1 WERE SUBMITTED. THE
 ORIGINAL SCOPE OF WORK FOR THIS PERMIT WAS FOR THE
 EXTENSION OF THE GARAGE. THE NEW DRAWINGS SHOW A NEW
 BEDROOM AND A NEW BATHROOM ADDITION. IT IS NOT CLEAR
 WHERE THIS ADDITION WILL TAKE PLACE. NEED TO PROVIDE
 COMPLETE SET OF DRAWINGS SHOWING THE ENTIRE HOUSE
 LAYOUT AND THE PROPOSED ADDITION. PROPOSED ADDITION
 WILL NEED ELECTRICAL, PLUMBING, MECHANICAL, ROOFING,
 ZONING AND IMPACT FEES REVIEWS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 9- ROOFING UNDERLAYMENT
 A)PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE
 NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001
  
 10- PROVIDE PRODUCT APPROVALS AS REQUIRED BY FAC
 61G1520.3001 FOR (NEW PRODUCT APPROVAL TO BE
 REVIEWED/APPROVED BY ARCHITECT PRIOR TO SUBMITTAL):
 A) NEW ROOFING SPECIFIED ON PLANS.
 B) NEW WINDOWS.
 C)NEW EXTERIOR DOORS
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS,
 INCLUDING DESIGN PROFESSIONAL FEES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-28 Cont ID  
Sent By jgomez Date 2022-02-28 Time 16:19 Rev Time 0.00
Received By jgomez Date 2022-02-28 Time 14:24 Sent To  
Notes
2022-02-28 16:24:43RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071433
  
 ORIGINAL COMMENT:
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
  
 RESPONSE:
 UNABLE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE. PLANS
 SUBMITTED SHOW A COPY OF A DIGITAL SIGNATURE. I WAS
 ABLE TO VERIFY THE DIGITAL SIGNATURE ON THE ARCHITECT'S
 RESPONSE LETTER BUT NOT ON THE DRAWINGS. PLANS NEED TO
 HAVE ORIGINAL DIGITAL SIGNATURE TO VERIFY ARCHITECT'S
 DIGITAL SIGNATURE.
 NOTE: SUBMIT ALL PLANS WITH ORIGINAL DIGITAL SIGNATURE.
  
 2- OK.
 3- OK.
 4- OK.
 5- OK.
  
 ORIGINAL COMMENT:
 6- GARAGE DOOR NOA 20-1015.22 SUBMITTED IS ONLY FOR UP
 TO 9'-0" WIDE DOOR. NEED TO PROVIDE PRODUCT APPROVAL
 FOR GARAGE DOOR SIZE SPECIFIED ON PLANS.
 FAC 61G20-3.001.
 NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SPECIFIED
 BY THE ARCHITECT OF RECORD.
  
 RESPONSE:
 DESIGN PRESSURES OF GARAGE DOOR NOA 20-0416.02 DON'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT
 OF RECORD. NEED PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
 NOTE: NEW PRODUCT APPROVAL TO BE REVIEWED/APPROVED BY
 ARCHITECT PRIOR TO SUBMITTAL.
  
 ORIGINAL COMMENT:
 7- PROVIDE FIRE RATING SPECIFICATIONS FOR GARAGE DOOR
 LEADING TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL. NOTE: EXISTING DOOR
 CAN NOT BE USED UNLESS PROOF IS PROVIDED SHOWING
 COMPLIANCE.
  
 RESPONSE:
 CONSTRUCTION PLAN ON SHEET A-1 WAS REVISED BY THE
 ARCHITECT SPECIFYING 20 MINUTE FIRE RATED DOOR. THIS IS
 OK. NO NEED TO SUBMIT SPECIFICATIONS FOR FIRE RATED
 DOOR. THIS WILL BE VERIFIED BY THE INSPECTOR IN THE
 FIELD.
 NOTE: MAKE SURE DOOR IS FIRE RATED AS PER ARCHITECT'S
 SPECIFICATIONS. FLORIDA PRODUCT APPROVAL FL8845-R6
 SUBMITTED IS FOR EXTERIOR DOORS AND DOESN'T SHOW THE
 FIRE RATING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-11 Cont ID  
Sent By jgomez Date 2022-01-11 Time 15:06 Rev Time 0.00
Received By jgomez Date 2022-01-11 Time 11:21 Sent To  
Notes
2022-01-11 15:07:29RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071433
  
 ORIGINAL COMMENT:
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
  
 RESPONSE:
 SOME PLANS STILL DON'T HAVE THE ARCHITECT'S DIGITAL
 SIGNATURE. ALSO, PLANS SUBMITTED SHOW A COPY OF A
 DIGITAL SIGNATURE. PLANS NEED TO HAVE ORIGINAL DIGITAL
 SIGNATURE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE.
 NOTE: SUBMIT ALL PLANS WITH ORIGINAL DIGITAL SIGNATURE.
  
 2- OK.
 3- OK.
 4- OK.
 5- OK.
  
 ORIGINAL COMMENT:
 6- GARAGE DOOR NOA 20-1015.22 SUBMITTED IS ONLY FOR UP
 TO 9'-0" WIDE DOOR. NEED TO PROVIDE PRODUCT APPROVAL
 FOR GARAGE DOOR SIZE SPECIFIED ON PLANS.
 FAC 61G20-3.001.
 NOTE: COORDINATE DESIGN PRESSURES WITH THOSE SPECIFIED
 BY THE ARCHITECT OF RECORD.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT:
 7- PROVIDE FIRE RATING SPECIFICATIONS FOR GARAGE DOOR
 LEADING TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL. NOTE: EXISTING DOOR
 CAN NOT BE USED UNLESS PROOF IS PROVIDED SHOWING
 COMPLIANCE.
 I APOLOGIZE FOR NO WRITING THIS COMMENT ON MY FIRST
 REVIEW. I WROTE IT ON MY INITIAL CHECKLIST NOTES, BUT
 SOMEHOW I FORGOT TO WRITE IT ON THE OFFICIAL REVIEW
 CHECKLIST.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-13 Cont ID  
Sent By jgomez Date 2021-10-13 Time 13:40 Rev Time 0.00
Received By jgomez Date 2021-10-13 Time 10:23 Sent To  
Notes
2021-10-13 13:42:33RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071433
  
 NOTE:
 SEC. 606 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
  
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
 NOTE: PLANS MAY BE UPLOADED TO PROJECTDOX WITH A
 DIGITAL SIGNATURE OR HARD COPIES WITH LICENSED DESIGN
 PROFESSIONAL SEAL AND SIGNATURE MAY BE DROPPED (OR
 MAILED) TO CITY HALL FOR RECORDS RETENTION.
  
 2- SHEET CVR:
 A)BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE AS REQUIRED.
 SEC. R301.2.1.4 FBC-RESIDENTIAL.
  
 B) CURRENT BUILDING CODE (2020) REFERENCES ASCE 7-16
 NOT ASCE 7-10. REVISE AS REQUIRED.
 SEC. 553.73 F.S.
  
 C)CLEARLY SPECIFY THE ULTIMATE DESIGN WIND SPEED AND
 THE NOMINAL DESIGN WIND SPEED. ALSO, REVISE DESIGN WIND
 PRESSURES TO CORRESPOND TO EXPOSURE "D" AS REQUIRED BY
 ITEM #2(A) ABOVE. AND, CLARIFY IF THE GIVEN DESIGN
 PRESSURES ARE ULTIMATE DESIGN WIND SPEEDS OR NOMINAL
 DESIGN WIND SPEEDS. SEC. R301.2.1.3 FBC-RESIDENTIAL.
  
 D)BUILDING CLASSIFICATION IS INCORRECT. TYPE IIIB
 CONSTRUCTION REQUIRES 2 HOUR FIRE RATED WALLS.
 TYPICALLY, SINGLE FAMILY RESIDENCES DON'T HAVE 2 HOUR
 FIRE RATED WALLS. REVISE AS REQUIRED OR PROVIDE
 DOCUMENTATION SHOWING THAT EXISTING HOUSE AND PROPOSED
 WALLS HAVE 2 HOUR FIRE RATED BEARING WALLS.
 TABLE 601 FBC-BUILDING.
  
 E)BUILDING AND ZONING DEPARTMENTS ARE INCORRECT. THIS
 IS CITY OF WEST PALM BEACH NOT CITY OF DELRAY. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 4- SHEET A-1:
 A)TYP. GARAGE DOOR DETAIL IS MISSING THE FASTENING
 SPECIFICATIONS FOR THE STRUCTURAL BUCK. DESIGNER OF
 RECORD IS RESPONSIBLE FOR THE SPECIFICATION. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 B) COORDINATE DESIGN WIND PRESSURES WITH ITEM # 2(C)
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- SHEET A-4:
 A)FOOTING F1 IS NOT CLEAR. FOOTING SIZE SPECIFIED ON
 THE FOOTING SCHEDULE AND FOOTING SHOWN ON THE TYP.
 EXTERIOR WALL DON'T MATCH. ALSO. CLARIFY WHY THE
 FOOTING DEPTH IS ONLY 5 INCHES?. FOOTING NEEDS TO BE
 12" BELOW GRADE. SEC. R403.1.4 FBC-RESIDENTIAL. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B)TYPICAL WALL SECTION: THERE ARE NOT SPECIFICATIONS
 FOR THE NEW BOND BEAM. CLARIFY WHY NOTES ON WALL
 SECTION SPECIFIES EXISTING DOUBLE BEAM IF THIS IS A NEW
 WALL? SEC. 107.2.1 CITY AMENDMENTS.
  
 C)THERE ARE NO SPECIFICATIONS FOR THE VERTICAL
 REINFORCEMENT ON CONCRETE FILLED COLUMNS. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 D) CLARIFY WHAT IS THE "2'-0" TYP" NOTE SHOWN ON THE
 FOUNDATION PLAN FOR?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- GARAGE DOOR NOA 20-1015.22 SUBMITTED IS ONLY FOR UP
 TO 9'-0" WIDE DOOR. NEED TO PROVIDE PRODUCT APPROVAL
 FOR GARAGE DOOR SIZE SPECIFIED ON PLANS.
 FAC 61G20-3.001.
 NOTE: COORDINATE DESIGN PRESSURES WITH ITEM #2(C)
 ABOVE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2022-08-23 Cont ID  
Sent By fgiaquin Date 2022-08-23 Time 19:33 Rev Time 0.00
Received By fgiaquin Date 2022-08-22 Time 22:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2022-08-13 Cont ID  
Sent By fgiaquin Date 2022-08-13 Time 08:33 Rev Time 0.00
Received By fgiaquin Date 2022-08-13 Time 08:05 Sent To  
Notes
2022-08-13 08:33:19NO RESPONSE TO PREVIOUS ELEC PLAN REVIEW COMMENTS?

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-07-06 Cont ID  
Sent By fgiaquin Date 2022-07-06 Time 23:03 Rev Time 0.00
Received By fgiaquin Date 2022-07-06 Time 21:28 Sent To  
Notes
2022-07-06 23:03:40NO ELEC SHOWN FOR NEW BATHROOM SHOWN ON P-1. PLEASE
 PROVIDE COMPLETEL ELECTRICAL DRAWINGS SHOWING ALL NEW
 PROPOSED WORK. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By fgiaquin Date 2022-02-15 Time 22:27 Rev Time 0.00
Received By fgiaquin Date 2022-02-15 Time 21:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-17 Cont ID  
Sent By fgiaquin Date 2021-09-17 Time 22:59 Rev Time 0.00
Received By fgiaquin Date 2021-09-17 Time 22:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-08-24 Cont ID  
Sent By jgomez Date 2022-08-24 Time 18:08 Rev Time 0.00
Received By jgomez Date 2022-08-16 Time 08:41 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-08-13 Cont ID  
Sent By fgiaquin Date 2022-08-13 Time 08:33 Rev Time 0.00
Received By fgiaquin Date 2022-08-03 Time 18:29 Sent To  
Notes
2022-08-03 18:57:4808/03/22 EMAIL RECEIVED FROM SUN BAND BUILDERS.
  
 HI MR. GOMEZ,
 PLEASE ASSIST.
 THESE WERE INCORRECTLY UPLOADED AND ARE NOT APPLICABLE
 TO THE ABOVE-REFERENCED PROJECT:
 ? A2 - PROJECT WILL NOT REQUIRE A NEW ROOF. WE ARE
 EXTENDING GARAGE UNDER EXISTING ROOF - PLEASE SEE SCOPE
 OF WORK ON CVR
 ? A3
 ? P1 - PROJECT WILL NOT REQUIRE PLUMBING - PLEASE SEE
 SCOPE OF WORK ON CVR
 ? NOA 20-1015.11- INCORRECT NOA
 [email protected]
 SUN BAND BUILDERS CONSTRUCTION, INC.
 ---------- ORIGINAL MESSAGE ----------
 FROM: SUNBAND WILSON
 TO: "[email protected]"
 , "[email protected]"
 DATE: 08/02/2022 5:26 PM
 SUBJECT: 21071433\DRAWINGS - - PLEASE REMOVE THE
 FOLLOWING DRAWINGS
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-06 Cont ID  
Sent By jgomez Date 2022-07-06 Time 11:12 Rev Time 0.00
Received By jgomez Date 2022-05-16 Time 12:50 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-28 Cont ID  
Sent By jgomez Date 2022-02-28 Time 16:26 Rev Time 0.00
Received By jgomez Date 2022-02-03 Time 17:15 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-11 Cont ID  
Sent By jgomez Date 2022-01-11 Time 15:08 Rev Time 0.00
Received By jgomez Date 2021-12-15 Time 09:57 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-13 Cont ID  
Sent By jgomez Date 2021-10-13 Time 13:56 Rev Time 0.00
Received By jgomez Date 2021-08-19 Time 14:59 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2022-08-04 Cont ID  
Sent By jgomez Date 2022-08-04 Time 09:23 Rev Time 0.00
Received By jgomez Date 2022-08-04 Time 09:23 Sent To  
Notes
2022-08-04 09:23:43GARAGE EXTENSION ONLY. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-07-06 Cont ID  
Sent By jgomez Date 2022-07-06 Time 11:12 Rev Time 0.00
Received By jgomez Date 2022-07-06 Time 11:12 Sent To  
Notes
2022-07-06 11:12:40IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-03-02 Cont ID  
Sent By jgomez Date 2021-10-13 Time 13:51 Rev Time 0.00
Received By jgomez Date 2021-10-13 Time 13:51 Sent To  
Notes
2021-10-13 13:52:08GARAGE EXTENSION ONLY. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2022-07-06 Cont ID  
Sent By medwards Date 2022-07-06 Time 06:31 Rev Time 0.00
Received By medwards Date 2022-07-06 Time 06:31 Sent To  
Notes
2022-07-06 06:32:05NO MECHANICAL WORK SHOWN FOR THIS PROJECT.ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-08-30 Cont ID  
Sent By medwards Date 2021-08-30 Time 09:47 Rev Time 0.00
Received By medwards Date 2021-08-30 Time 09:47 Sent To  
Notes
2021-08-30 09:48:12NO MECHANICAL WORK SHOWN FOR THIS PROJECT.ME

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-08-05 Cont ID  
Sent By rwbrown Date 2022-08-05 Time 06:01 Rev Time 0.00
Received By rwbrown Date 2022-08-05 Time 06:01 Sent To  
Notes
2022-08-05 06:02:22THIS IS FOR GARAGE ONLY AND NO PLUMBING IS TO BE DONE
 ON THIS PERMIT

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-21 Cont ID  
Sent By rwbrown Date 2022-05-21 Time 10:18 Rev Time 0.00
Received By rwbrown Date 2022-05-21 Time 10:17 Sent To  
Notes
2022-05-21 10:18:481ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3108.1 - THE BAR SINK IS NOT A BATHROOM
 GROUP FIXTURE AND CANNOT BE INCLUDED IN THE WET VENT
 SYSTEM. WET VENT SYSTEMS SHALL INCLUDE ONLY BATHROOM
 GROUP FIXTURES. ALL OTHER FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE LAST WET VENTED BATHROOM GROUP
 FIXTURE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-08-04 Cont ID  
Sent By jgomez Date 2022-08-04 Time 09:43 Rev Time 0.00
Received By jgomez Date 2022-08-04 Time 09:43 Sent To  
Notes
2022-08-04 09:44:35GARAGE EXTENSION ONLY AS SHOWN ON ORIGINAL PERMIT. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-07-06 Cont ID  
Sent By jgomez Date 2022-07-06 Time 11:23 Rev Time 0.00
Received By jgomez Date 2022-07-06 Time 11:14 Sent To  
Notes
2022-07-06 11:23:36ROOFING REVIEW:
  
 1- PROVIDE PRODUCT APPROVALS AS REQUIRED BY FAC
 61G1520.3001 FOR (NEW PRODUCT APPROVAL TO BE
 REVIEWED/APPROVED BY ARCHITECT PRIOR TO SUBMITTAL):
 A) NEW ROOFING SPECIFIED ON PLANS.
 B) NEW WINDOWS.
 C)NEW EXTERIOR DOORS
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2022-08-24 Cont ID  
Sent By jgomez Date 2022-08-24 Time 17:30 Rev Time 0.00
Received By jgomez Date 2022-08-24 Time 17:30 Sent To  
Notes
2022-08-24 17:31:06DIGITAL SIGNATURE FOR DRAWINGS SP-1 AND E-1 ARE
 UPLOADED TO THE SIGNATURE FOLDER ON 3/2/2022. . JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2022-08-04 Cont ID  
Sent By jgomez Date 2022-08-04 Time 09:40 Rev Time 0.00
Received By jgomez Date 2022-08-04 Time 09:23 Sent To  
Notes
2022-08-04 09:43:37DIGITAL SIGNATURE FOR DRAWINGS SP-1 AND E-1 ARE
 UPLOADED TO THE SIGNATURE FOLDER ON 3/2/2022. . JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-07-06 Cont ID  
Sent By jgomez Date 2022-07-06 Time 11:11 Rev Time 0.00
Received By jgomez Date 2022-07-06 Time 11:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-03-02 Cont ID  
Sent By jgomez Date 2022-03-02 Time 10:39 Rev Time 0.00
Received By jgomez Date 2022-03-02 Time 10:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-02-28 Cont ID  
Sent By jgomez Date 2022-02-28 Time 16:25 Rev Time 0.00
Received By jgomez Date 2022-02-28 Time 16:25 Sent To  
Notes
2022-02-28 16:25:35SIGNATURE REVIEW:
  
 ORIGINAL COMMENT:
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
  
 RESPONSE:
 UNABLE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE. PLANS
 SUBMITTED SHOW A COPY OF A DIGITAL SIGNATURE. I WAS
 ABLE TO VERIFY THE DIGITAL SIGNATURE ON THE ARCHITECT'S
 RESPONSE LETTER BUT NOT ON THE DRAWINGS. PLANS NEED TO
 HAVE ORIGINAL DIGITAL SIGNATURE TO VERIFY ARCHITECT'S
 DIGITAL SIGNATURE.
 NOTE: SUBMIT ALL PLANS WITH ORIGINAL DIGITAL SIGNATURE.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-11 Cont ID  
Sent By jgomez Date 2022-01-11 Time 15:04 Rev Time 0.00
Received By jgomez Date 2022-01-11 Time 15:04 Sent To  
Notes
2022-01-11 15:05:11SIGNATURE REVIEW:
  
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
 NOTE: PLANS MAY BE UPLOADED TO PROJECTDOX WITH A
 DIGITAL SIGNATURE OR HARD COPIES WITH LICENSED DESIGN
 PROFESSIONAL SEAL AND SIGNATURE MAY BE DROPPED (OR
 MAILED) TO CITY HALL FOR RECORDS RETENTION.
  
 RESPONSE:
 SOME PLANS STILL DON'T HAVE THE ARCHITECT'S DIGITAL
 SIGNATURE. ALSO, PLANS SUBMITTED SHOW A COPY OF A
 DIGITAL SIGNATURE. PLANS NEED TO HAVE ORIGINAL DIGITAL
 SIGNATURE TO VERIFY ARCHITECT'S DIGITAL SIGNATURE.
 NOTE: SUBMIT ALL PLANS WITH ORIGINAL DIGITAL SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-13 Cont ID  
Sent By jgomez Date 2021-10-13 Time 13:55 Rev Time 0.00
Received By jgomez Date 2021-10-13 Time 13:55 Sent To  
Notes
2021-10-13 13:56:15SIGNATURE REVIEW:
  
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. PLANS NEED TO HAVE ARCHITECT'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003 FAC.
 NOTE: PLANS MAY BE UPLOADED TO PROJECTDOX WITH A
 DIGITAL SIGNATURE OR HARD COPIES WITH LICENSED DESIGN
 PROFESSIONAL SEAL AND SIGNATURE MAY BE DROPPED (OR
 MAILED) TO CITY HALL FOR RECORDS RETENTION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2022-08-10 Cont ID  
Sent By vbroglia Date 2022-08-10 Time 16:26 Rev Time 0.00
Received By afowlkes Date 2022-08-10 Time 16:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-05-26 Cont ID  
Sent By afowlkes Date 2022-05-26 Time 13:32 Rev Time 0.00
Received By afowlkes Date 2022-05-26 Time 13:32 Sent To  
Notes
2022-07-06 09:14:1807/06/22 FAILED - ACCORDING TO THE PLUMBING PLAN, YOU
 ARE PROPOSING TO BUILD A NEW BATHROOM AND NEW GUEST
 BEDROOM IN ADDITION TO THE GARAGE EXTENSION. THESE
 IMPROVEMENTS ARE NOT SHOWN ON THE SITE PLAN, PLEASE
 CONFIRM THE SCOPE OF WORK AND/OR REMOVE THESE
 IMPROVEMENTS FROM THE PLAN IF THEY ARE NOT APPLICABLE.
  
 ALECANDER FOWLKES
 [email protected]
 5618221431

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By asangele Date 2022-02-15 Time 10:24 Rev Time 0.00
Received By asangele Date 2022-02-15 Time 10:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-13 Cont ID  
Sent By awooten Date 2021-09-13 Time   Rev Time  
Received By awooten Date 2021-09-13 Time   Sent To  
Notes
***NONE***