| Plan Review Stops For Permit 21071268 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2021-10-27 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-10-27 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-10-27 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2021-09-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-09-22 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-09-22 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2021-09-22 10:44:37 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | ASBESTOS COMMENTS: | | | | | | FAILED PLAN REVIEW, COMMERCIAL: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-07-30 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-07-30 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2021-07-30 11:01:39 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | ASBESTOS REQUIREMENTS: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2021-11-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-11-30 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-30 |
Time |
09:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2021-11-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-11-20 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-20 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2021-11-20 10:18:06 | BUILDING DEMO PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | 4TH REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SCHEDULE AND PASS A 703 PLUMBING FINAL FOR PLUMBING | | | PERMIT 21100873 (PLUMBING CAP OFF). | | | | | | NOTICE: YOU MAY E-MAIL ME WHEN THIS IS COMPLETE AND I | | | WILL APPROVE THE DEMO PERMIT. CT | | | | | | ALL OTHER REVIEWS ARE COMPLETE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-10-27 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-10-27 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-10-27 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2021-10-27 15:15:25 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | | DEMO PERMIT PER FLORIDA BUILDING | | | CODE, BUILDING 3303: | | | | | | 3. UTILITY RELEASE ? CITY OF WEST PALM BEACH WATER | | | DEPARTMENT, REQUEST FOR METER PULL, ON | | | THEIR FORM "DEMOLITION APPLICATION" | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT?SERVICES/FORMS/B | | | UILDING?PERMIT?FORMS | | | | | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | | THEN A PARTIAL RELEASE WILL BE | | | NOTED ON THEIR FORM. | | | BACKFLOW IS DESIRED ? BEFORE SCHEDULING THE 703, THE | | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE | | | CITY?S | | | UTILITIES DEPT, 561?822?2244. | | | FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO | | | 561?822?2183. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-09-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-09-22 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-09-22 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2021-09-22 10:59:24 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | | DEMO PERMIT PER FLORIDA BUILDING | | | CODE, BUILDING 3303: | | | | | | | | | | | | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER | | | DEPARTMENT, REQUEST FOR METER PULL, ON | | | THEIR FORM "DEMOLITION APPLICATION" | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | | THEN A PARTIAL RELEASE WILL BE | | | NOTED ON THEIR FORM. | | | BACKFLOW IS DESIRED - BEFORE SCHEDULING THE 703, THE | | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE | | | CITY?S | | | UTILITIES DEPT, 561-822-2244. | | | FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO | | | 561-822-2183. | | | | | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | | APPLICATION TO BUILDING DIVISION); | | | SCHEDULE A FINAL PLUMBING #703. | | | | | | 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST | | | CONTROL COMPANY STATING THAT | | | DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED | | | FOR RODENTS. | | | | | | 6. COMPLETE THE DEMO DEBRIS FORM: | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR | | | THE FORM TO [email protected]. | | | | | | 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-07-30 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-07-30 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2021-07-30 11:08:39 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | | DEMO PERMIT PER FLORIDA BUILDING | | | CODE, BUILDING 3303: | | | | | | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) | | | RELEASE OF SERVICE CONFIRMATION | | | | | | 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) | | | RELEASE OF SERVICE CONFIRMATION | | | | | | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER | | | DEPARTMENT, REQUEST FOR METER PULL, ON | | | THEIR FORM "DEMOLITION APPLICATION" | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | | THEN A PARTIAL RELEASE WILL BE | | | NOTED ON THEIR FORM. | | | BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW | | | DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S | | | UTILITIES DEPT, 561-822-2244. | | | | | | FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO | | | 561-822-2183. | | | | | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | | APPLICATION TO BUILDING DIVISION); | | | SCHEDULE A FINAL PLUMBING #703. | | | | | | 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST | | | CONTROL COMPANY STATING THAT | | | DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED | | | FOR RODENTS. | | | | | | 6. COMPLETE THE DEMO DEBRIS FORM: | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR | | | THE FORM TO [email protected]. | | | | | | 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF | | | THE STRUCTURE(S) TO BE DEMOLISHED, | | | FBC 107. | | | | | | 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN. | | | | | | 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW | | | DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S | | | UTILITIES DEPT, 561-822-2244. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-11-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-11-01 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2021-10-14 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-10-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-10-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-10-14 10:28:38 | PLEASE ADDRESS BUILDING COMMENTS. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2021-08-04 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-08-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-08-04 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2021-08-04 11:44:25 | PLEASE ADDRESS BUILDING COMMENTS. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-08-06 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-08-06 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-08-06 |
Time |
13:38 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-11-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-11-20 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-08 |
Time |
07:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-11-01 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-10-26 |
Time |
07:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-10-14 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-10-14 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-09-20 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-08-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-23 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-27 |
Time |
16:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-07-30 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-07-30 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-09-30 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-09-30 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-09-30 |
Time |
17:36 |
Sent To |
|
|
| Notes |
| 2021-09-30 17:37:36 | PROVISO: DEMOLITION OF PARKING LOT IS ALLOWED BUT | | | EXISTING STRUCTURES ON SITE CANNOT BE DEMOLISHED UNTIL | | | THE BUILDING PERMTI FOR THE NEW BUILDING IS APPROVED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-08-20 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-08-20 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-08-20 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2021-08-20 15:34:40 | DEMOLITON OF RESDING ROOM OR ANY STRUCTURE ON SITE WILL | | | NOT BE APPROVED UNTIL A BUILDING PERMIT FOR NEW | | | BUILDING IS APPROVED. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|