Plan Review Details - Permit 21071231
Plan Review Stops For Permit 21071231
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-08-20 Cont ID  
Sent By cpuell Date 2021-08-20 Time 15:39 Rev Time 0.00
Received By cpuell Date 2021-08-20 Time 15:39 Sent To  
Notes
2021-08-20 15:40:40PER GREENCARD REAR BUILDING IS A DUPLEX. GAVE DOWNSTAIR
 UNIT THE NEW ADDRESS OF 927 SELKIRK AND THE UPSTAIRS
 UNIT THE ADDRESS OF 929 SELKIRK.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By cpuell Date 2021-08-19 Time 14:30 Rev Time 0.00
Received By cpuell Date 2021-08-19 Time 14:30 Sent To  
Notes
2021-08-19 14:30:43PLANS INDICATE THAT THE WORK IS FOR THE REAR BUILDING,
 HOWEVER IT APPEARS THAT THERE IS TO BE TWO UNITS, AND
 ADDITIONAL ADDRESS WILL BE REQUIRED FOR THE SECOND
 UNIT. PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO DISCUSS ADDRESSING OPTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-11-24 Cont ID  
Sent By jgomez Date 2021-11-24 Time 09:28 Rev Time 0.00
Received By jgomez Date 2021-11-24 Time 09:16 Sent To  
Notes
2021-11-24 09:39:33BUILDING REVIEW APPROVED WITH PROVISO:
 NOTE: PROVIDE REQUIRED INFORMATION FOR REVIEW PRIOR TO
 INSPECTIONS.
 1- SHEET 4-4: REVISE BOTTOM CHORD LIVE/DEAD LOADS.
 TABLE R301.5 FBC-RESIDENTIAL.
 NOTE: AHU IS LOCATED IN THE ATTIC.
 2- DEFERRED SUBMITTAL: SUBMIT HANDRAIL AND GUARDRAIL
 SHOP DRAWINGS APPROVED BY ENGINEER OF RECORD.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-15 Cont ID  
Sent By jgomez Date 2021-11-15 Time 18:25 Rev Time 0.00
Received By jgomez Date 2021-11-15 Time 16:46 Sent To  
Notes
2021-11-15 18:26:37REBUILD DUPLEX (R3) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071231
  
  
 NOTE:
 SECOND FLOOR FRAMING PLAN ON SHEET 4-4 IS MISSING THE
 SIZE OF THE FLOOR TRUSSES AND LIVE/DEAD LOADS DESIGN
 INFORMATION.. ENGINEER NEEDS TO SPECIFY THIS
 INFORMATION.
  
  
 1- PERMIT APPLICATION STATES: "REMODEL TWO STORY
 BUILDING AS PER PLANS". PLANS SUBMITTED ARE FOR
 COMPLETE CONSTRUCTION OF A TWO STORY DUPLEX. NEED TO
 REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION TO
 SAY REBUILD TWO STORY DUPLEX.
 THE PERMIT TYPE WILL BE CHANGED FROM RESIDENTIAL
 REMODEL TO NEW RESIDENTIAL BUILDING PERMIT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 SCOPE OF WORK ON PERMIT APPLICATION WAS NOT CHANGED.
 ALSO, SCOPE OF WORK ON SHEET 1-4 WAS REVISED TO SAY
 "REMODELING A 2-STORY CBS MULTIFAMILY RESIDENCE". THIS
 IS INCORRECT. THIS IS NOT A "REMODELING" PROJECT. THIS
 IS A REBUILD OR NEW CONSTRUCTION. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- OK
 3- OK
 4- OK
 5- OK
 6- OK
 7- OK
 8- OK
  
 9- STAIRWAY CONSTRUCTION:
 A)
  
 ORIGINAL COMMENT:
 B)PROVIDE NOSING DETAIL/SPECIFICATIONS AS REQUIRED BY
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 STAIR DETAIL ON SHEET 3-4 DOESN'T SHOW NOSING
 PROJECTION. IT SPECIFIES 3/4" NOSING BUT THE DETAIL
 DOESN'T SHOW THE 3/4" PROJECTION. REVISE AS REQUIRED.
 SHOW THE NOSING PROJECTION.
  
 C) OK.
 D) OK.
  
 E) DEFERRED SUBMITTAL: AFTER THE PERMIT IS ISSUED NEED
 TO SUBMIT HANDRAIL AND GUARDRAIL SHOP DRAWINGS APPROVED
 BY ENGINEER OF RECORD AS DEFERRED SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 10- OK
 11- OK.
 12-OK.
 13-OK
 14-OK
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
 **************************************

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-23 Cont ID  
Sent By jgomez Date 2021-09-23 Time 11:11 Rev Time 0.00
Received By jgomez Date 2021-09-23 Time 09:17 Sent To  
Notes
2021-09-23 11:13:01REBUILD DUPLEX (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071231
  
 ORIGINAL COMMENT:
 1- PERMIT APPLICATION STATES: "REMODEL TWO STORY
 BUILDING AS PER PLANS". PLANS SUBMITTED ARE FOR
 COMPLETE CONSTRUCTION OF A TWO STORY DUPLEX. NEED TO
 REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION TO
 SAY CONSTRUCTION OF A NEW TWO STORY DUPLEX.
 THE PERMIT TYPE WILL BE CHANGED FROM RESIDENTIAL
 REMODEL TO NEW RESIDENTIAL BUILDING PERMIT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 BASED ON REVISED PLANS SUBMITTED, THE SCOPE OF WORK IS
 TO REBUILT THE TWO STORY DUPLEX. PERMIT TYPE WAS
 CHANGED TO BUILDING-RESIDENTIAL PERMIT. SEC. 107.2.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- BASED ON ITEM #1 ABOVE. VALUATION DECLARED IN THE
 PERMIT APPLICATION IS TOO LOW. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 VALUATION WAS UPDATED TO $182843.00. OWES $2250.65.
  
 RESPONSE:
 FEES NEED TO BE PAID WHEN PERMIT IS APPROVED.
  
 ORIGINAL COMMENT:
 3- NEED TO APPLY FOR A SEPARATE BUILDING DEMOLITION
 PERMIT IN ORDER TO DEMOLISH OLD BUILDING. SEC. 105.1
 CITY AMENDMENTS.
  
 RESPONSE:
 WILL NEED DEMOLITION PERMIT.
  
 ORIGINAL COMMENT:
 4- NEED TO SPECIFY A LISTED FIRE RATED CEILING /FLOOR
 ASSEMBLY TESTED IN ACCORDANCE WITH ASTM E119 OR UL263
 AS REQUIRED BY SEC. R302.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 1 HOUR FIRE RATED FLOOR/CEILING ASSEMBLY DETAIL SHOWN
 ON SHEET 2-4 IS INCORRECT. UL DESIGN U465 IS FOR WALL
 ASSEMBLIES NOT FOR FLOOR/CEILING ASSEMBLIES. REVISE AS
 REQUIRED. NEED TO SPECIFY AN APPROVED FLOOR /CEILING
 ASSEMBLY.
 ALSO, INFORMATION SHOWN ON THE 1 HOUR FIRE RATED
 FLOOR/CEILING ASSEMBLY DETAIL DOESN'T MATCH INFORMATION
 SHOWN ON THE TYPICAL WALL SECTION ON SAME SHEET 2-4.
 REVISE AS REQUIRED AND COORDINATE ACCORDINGLY WITH
 CORRECT FLOOR/CEILING ASSEMBLY DETAIL.
  
 ORIGINAL COMMENT:
 5- NEED TO PROVIDE FIRE RATED PENETRATIONS DETAILS AND
 SPECIFICATIONS FOR THE FIRE RATED FLOOR CEILING
 ASSEMBLY AS REQUIRED BY SEC. R302.4 FBC-RESIDENTIAL.
  
 RESPONSE:
 ENGINEER'S RESPONSE LETTER STATES "INFORMATION HAS BENN
 UPDATED ON SHEET 2-4". INFORMATION WAS NOT PROVIDED.
  
 6- OK.
  
 ORIGINAL COMMENT:
 7- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 ENGINEER'S RESPONSE LETTER STATES "THIS IS A REMODEL
 PROJECT". THIS IS INCORRECT. BASED ON PLANS SUBMITTED
 SOIL IS ALTERED FOR PROPOSED CONSTRUCTION. PROVIDE
 REQUIRED DRAINAGE PLAN.
 NOTE: NORTH SIDE OF RECONSTRUCTED BUILDING IS TOO CLOSE
 TO THE THE ADJACENT PROPERTY. TAKE THIS INTO
 CONSIDERATION WHEN DOING THE DRAINAGE PLAN. WATER CAN
 NOT BE DIVERTED TO ADJACENT PROPERTIES.
  
 8- ACCORDING TO SURVEY SUBMITTED THE NORTH WALL OF
 BUILDING IS LOCATED LESS THAN 3 FEET FROM THE PROPERTY
 LINE. THE FOLLOWING FIRE RESISTANT CONSTRUCTION IS
 REQUIRED:
  
 ORIGINAL COMMENT:
 A) PROJECTIONS: NEED TO SPECIFY 1 HOUR FIRE RATED
 ASSEMBLY ON THE UNDERSIDE OF THE ROOF PROJECTION. TABLE
 R302.1 FBC-RESIDENTIAL.
 NOTE: TAKE INTO CONSIDERATION OPENINGS FOR ATTIC
 VENTILATION.
  
 RESPONSE:
 THERE IS NO DETAIL FOR 1 HOUR FIRE RATED ASSEMBLY ON
 THE UNDERSIDE OF THE ROOF PROJECTION.
 ALSO, THERE IS NO INFORMATION ABOUT THE ATTIC VENTS ON
 THE NORTH SIDE OF THE BUILDING.
 TYPICAL WALL SECTION ON SHEET 2-4 SPECIFIES VENTS @
 8'-0" O.C. VENTS ARE NOT ALLOWED ON THE NORTH SIDE OF
 THE BUILDING. ENGINEER OF RECORD TO SHOW ON THE ROOF
 PLAN HOW PROVIDING THE CROSS VENTILATION AT THE 1/150
 RATIO AS REQUIRED BY SEC. R806.1 AND SEC. R806.2
 FBC-RESIDENTIAL. PROVIDE CALCULATIONS FOR THE REQUIRED
 NUMBER OF VENTS.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C)PROVIDE FIRE RATED DETAIL/SPECIFICATIONS FOR ANY WALL
 PENETRATIONS. TABLE R302.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. SEE ELECTRICAL PLAN FOR
 WALL PENETRATIONS.
  
 9- STAIRWAY CONSTRUCTION:
 A)
  
 ORIGINAL COMMENT:
 B)PROVIDE NOSING DETAIL/SPECIFICATIONS AS REQUIRED BY
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 STAIR DETAIL ON SHEET 3-4 SHOWS 1/2" NOSING PROJECTION.
 NEED A NOSING PROJECTION NOT LESS THAN 3/4". REVISE AS
 REQUIRED.
 NOTE: STAIR DETAIL SHOWS MARBLE TREADS AND RISERS.
 THESE ARE EXTERIOR STAIRS. THERE IS A CONCERN ABOUT
 THESE STAIRS BEING TOO SLIPPERY WHEN WET. PROVIDE
 DETAIL/SPECIFICATIONS SHOWING HOW TO AVOID SLIPPERY
 TREADS. SEC. 101.3 CITY AMENDMENTS.
  
 C) OK.
 D) OK.
  
 E) AFTER THE PERMIT IS ISSUED NEED TO SUBMIT HANDRAIL
 AND GUARDRAIL SHOP DRAWINGS APPROVED BY ENGINEER OF
 RECORD AS DEFERRED SUBMITTAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 10- OK
 11- OK.
 12-OK.
 13-OK
  
 14- ENERGY CALCULATIONS SUBMITTED:
 A) OK
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. CORRECT ADDRESS IS 929 SELKIRK ST. NOT 923.
 PROVIDE OWNER AND BUILDER INFORMATION. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 DOWNSTAIR & UPSTAIR UNITS ASSIGNED ADDRESS ARE OK ON
 EACH ENERGY CALCULATIONS SUBMITTED. REQUESTED OWNER AND
 BUILDER INFORMATION WAS NOT PROVIDED. NEED TO PROVIDE
 THIS INFORMATION.
  
 C)OK.
 D) OK
 E) OK
 F) OK
 G) OK
 H) OK
 I) OK
 J)OK
 K)OK
  
 ORIGINAL COMMENT:
 L)PROVIDE CORRECT INFORMATION FOR "WINDOWS" INFORMATION
 ON PAGE 3. THERE ARE TWO UNITS. WINDOW OVERHEAD
 SEPARATION VARIES FROM FIRST FLOOR UNIT TO SECOND FLOOR
 UNIT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 WINDOW OVERHEAD SEPARATION FOR DOWNSTAIR UNIT (927
 SELKIRK ST) IS INCORRECT. SEE BUILDING ELEVATIONS AND
 REVISE AS REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 11:20 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 08:45 Sent To  
Notes
2021-08-20 11:23:03DUPLEX (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071231
  
 1- PERMIT APPLICATION STATES: "REMODEL TWO STORY
 BUILDING AS PER PLANS". PLANS SUBMITTED ARE FOR
 COMPLETE CONSTRUCTION OF A TWO STORY DUPLEX. NEED TO
 REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION TO
 SAY CONSTRUCTION OF A NEW TWO STORY DUPLEX.
 THE PERMIT TYPE WILL BE CHANGED FROM RESIDENTIAL
 REMODEL TO NEW RESIDENTIAL BUILDING PERMIT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- BASED ON ITEM #1 ABOVE. VALUATION DECLARED IN THE
 PERMIT APPLICATION IS TOO LOW. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 VALUATION WAS UPDATED TO $182843.00. OWES $2250.65.
  
 3- NEED TO APPLY FOR A SEPARATE BUILDING DEMOLITION
 PERMIT IN ORDER TO DEMOLISH OLD BUILDING. SEC. 105.1
 CITY AMENDMENTS.
  
 4- NEED TO SPECIFY A LISTED FIRE RATED CEILING /FLOOR
 ASSEMBLY TESTED IN ACCORDANCE WITH ASTM E119 OR UL263
 AS REQUIRED BY SEC. R302.3 FBC-RESIDENTIAL.
  
 5- NEED TO PROVIDE FIRE RATED PENETRATIONS DETAILS AND
 SPECIFICATIONS FOR THE FIRE RATED FLOOR CEILING
 ASSEMBLY AS REQUIRED BY SEC. R302.4 FBC-RESIDENTIAL.
  
 6- NEED TO PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE A/C DUCTWORK FOR THE FIRST FLOOR
 DWELLING UNIT. IS THERE A DROPPED CEILING?
 SEC. R302.4 FBC-RESIDENTIAL.
  
 7- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 8- ACCORDING TO SURVEY SUBMITTED THE NORTH WALL OF
 BUILDING IS LOCATED LESS THAN 3 FEET FROM THE PROPERTY
 LINE. THE FOLLOWING FIRE RESISTANT CONSTRUCTION IS
 REQUIRED:
 A) PROJECTIONS: NEED TO SPECIFY 1 HOUR FIRE RATED
 ASSEMBLY ON THE UNDERSIDE OF THE ROOF PROJECTION. TABLE
 R302.1 FBC-RESIDENTIAL.
 NOTE: TAKE INTO CONSIDERATION OPENINGS FOR ATTIC
 VENTILATION.
  
 B)WINDOWS ARE NOT ALLOWED. TABLE R302.1
 FBC-RESIDENTIAL.
  
 C)PROVIDE FIRE RATED DETAIL/SPECIFICATIONS FOR ANY WALL
 PENETRATIONS. TABLE R302.1 FBC-RESIDENTIAL.
  
 9- STAIRWAY CONSTRUCTION:
 A)CONCRETE STAIR SECTION ON SHEET 3-4: NUMBER OF TREADS
 AND RISERS SPECIFIED DON'T MATCH NUMBER OF TREADS AND
 RISER SHOWN ON THE DETAIL. REVISE AS REQUIRED TO MATCH.
 NOTE: SAME COMMENT APPLIES TO STAIRS SHOWN ON FIRST
 FLOOR PLAN VIEW ON SHEET 1-4.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)PROVIDE NOSING DETAIL/SPECIFICATIONS AS REQUIRED BY
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 C)TYPICAL STAIR & GUARDRAIL NOTES SPECIFIED ON SHEET
 3-4. THE BALUSTERS REQUIRED RESISTANCE IS NOT 25LB PER
 SQUARE FOOT. SEE TABLE R301.5 FBC-RESIDENTIAL AND
 REVISE AS REQUIRED.
 ALSO, ALL THE NOTES NEED TO REFERENCE THE CORRECT CODE
 SECTION FROM THE FBC-RESIDENTIAL CODE NOT THE
 FBC-BUILDING. REVISE AS REQUIRED.
  
 D) CONCRETE STAIR SECTION ON SHEET 3-4: REVISE HANDRAIL
 NOTE STATING "34-38" HANDRAIL BY OTHERS". THIS HANDRAIL
 IS A GUARDRAIL AND THE MINIMUM HEIGHT IS 36". SEE SEC.
 R312.1.2 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 E) NEED TO SUBMIT HANDRAIL AND GUARDRAIL SHOP DRAWINGS
 APPROVED BY ENGINEER OF RECORD AS DEFERRED SUBMITTAL.
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- PROPOSED FLOOR PLANS AND SURVEY SUBMITTED DON'T
 MATCH.
 REVISE AS REQUIRED TO MATCH. SEE DIMENSIONS AND
 STAIRWAY.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR CANOPY
 ABOVE FIRST FLOOR ENTRY DOOR. CLEARLY SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IT LOOKS LIKE THIS DETAIL IS ON SHEET 2-4 BUT IT
 IS NOT LABELED AND NEED TO BE REVISED. SIMPSON MP24
 MENDING PLATE IS NOT AN STRUCTURAL CONNECTOR (SEE
 SIMPSON CATALOG). SIZE OF STEEL ANGLE CONNECTING THE
 CANOPY TO THE WALL IS NOT SPECIFIED. PROVIDE COMPLETE
 INFORMATION FOR THE SHEATHING, ROOFING , UNDERLAYMENT,
 ETC. MOST LIKELY THERE ARE NOT TRUSSES FOR THIS LITTLE
 CANOPY (REVISE AS REQUIRED OR PROVIDE TRUSS PACKAGE
 SHOWING THIS LITTLE ROOF AREA).
  
 12- SHEET 4-4:
 A)PLYWOOD ROOD SHEATHING NOTE ON THE GENERAL ROOF NOTES
 AND NOTE BELOW THE COMPONENT AND CLADDING PRESSURES
 ZONES TABLE DON'T MATCH THOSE SHOWN ON THE COMPONENT
 AND CLADDING PRESSURES ZONES TABLE. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 13- FIRST FLOOR BATHROOM NEEDS A DOOR THAT PROVIDE 29"
 MIN. CLEAR OPENING. SPECIFIED 30" DOOR DOESN'T COMPLY.
 SEC. R320.1 FBC-RESIDENTIAL.
  
 14- ENERGY CALCULATIONS SUBMITTED:
 NOTE: ENERGY CALCULATIONS SUBMITTED ARE SEPARATE FOR
 EACH DWELLING UNIT. COMMENTS BELOW APPLY TO BOTH
 CALCULATIONS SUBMITTED. COORDINATE AND REVISE
 ACCORDINGLY.
  
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. CORRECT ADDRESS IS 929 SELKIRK ST. NOT 923.
 PROVIDE OWNER AND BUILDER INFORMATION. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION
 ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?.
 "DETACHED IS NOT THE ANSWER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)PROVIDE CORRECT INFORMATION FOR ITEM #3. THERE ARE
 TWO UNITS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)PROVIDE CORRECT INFORMATION FOR ITEM #6. NEED TO
 PROVIDE THE A/C AREA FOR EACH UNIT, NOT ENTIRE
 BUILDING. SEE PLANS A/C AREA OF EACH UNIT. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)PROVIDE CORRECT INFORMATION FOR ITEM #9. THERE ARE
 TWO UNITS. ONE IS ON SLAB ON GRADE AND THE OTHER ONE IS
 NOT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)PROVIDE CORRECT INFORMATION FOR ITEM #11. NOTE: THERE
 ARE TWO UNITS. THIS INFORMATION VARIES FOR EACH UNIT.
 ALSO, SEE PLANS FOR CORRECT INSULATION R-VALUE AND
 VENTILATION. TOP UNIT IS VENTED.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 H)PROVIDE CORRECT INFORMATION FOR "BLOCKS" INFORMATION
 ON PAGE 2. THERE ARE TWO UNITS, NOT ENTIRE HOUSE.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 I)PROVIDE CORRECT INFORMATION FOR "SPACES" INFORMATION
 ON PAGE 2. THERE ARE TWO UNITS, NOT ENTIRE HOUSE.
 REVISE NUMBER OF OCCUPANTS AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: TYPICALLY, THE NUMBER OF OCCUPANTS IS BASED ON
 THE NUMBER OF BEDROOMS. NUMBER OF PEOPLE IS NOT ADDED
 FOR THE LIVING ROOM AND BEDROOM.
  
 J)PROVIDE CORRECT INFORMATION FOR "FLOORS" INFORMATION
 ON PAGE 2. THERE ARE TWO UNITS. ONE IS ON SLAB ON GRADE
 AND THE OTHER ONE IS NOT. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 K)PROVIDE CORRECT INFORMATION FOR "DOORS" INFORMATION
 ON PAGE 3. THERE ARE TWO UNITS. DOOR ORIENTATION IS
 DIFFERENT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 L)PROVIDE CORRECT INFORMATION FOR "WINDOWS" INFORMATION
 ON PAGE 3. THERE ARE TWO UNITS. WINDOW OVERHEAD
 SEPARATION VARIES FROM FIRST FLOOR UNIT TO SECOND FLOOR
 UNIT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-11-16 Cont ID  
Sent By fgiaquin Date 2021-11-16 Time 23:19 Rev Time 0.00
Received By fgiaquin Date 2021-11-16 Time 21:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-09-30 Cont ID  
Sent By fgiaquin Date 2021-09-30 Time 23:47 Rev Time 0.00
Received By fgiaquin Date 2021-09-30 Time 21:12 Sent To  
Notes
2021-09-30 23:47:44ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO MAINS SHOWN AT SERVICE. SERVICE MAINS MUST BE
 GROUPED. NEC 230.72
  
 2. SERVICE ENTRANCE CONDUCTORS SIZE ARE INSUFFICIENT
 FOR SERVICE SIZE. CALCULATED LOAD SHOWN TO BE 256AMPS.
 4/0 WIRE SHOWN IS ONLY PERMISSIBLE FOR 230AMPS AT
 75DEGREES CELCIUS. MINIMUM 250MCM REQUIRED. NEC 230.23A
  
 3. EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM METER CANS
 TO 1ST MEANS OF DISCONNECTS. THIS IS NOT PERMITTED AND
 PROVIDED A PARALLEL PATH BACK TO THE GROUNDED
 CONDUCTOR. EQUIPMENT GROUND ORIGINATES AFTER 1ST MEANS
 OF DISCONNECT. PROVIDE CORRECTION. NEC 250.24C
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-29 Cont ID  
Sent By fgiaquin Date 2021-07-29 Time 22:26 Rev Time 0.00
Received By fgiaquin Date 2021-07-29 Time 21:31 Sent To  
Notes
2021-07-29 22:26:47ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SERVICE ALLOWED FOR A BUILLDING. PLANS
 SHOWS 2 SEPARATE METER CANS AND ONE-LINE DIAGRAM STATES
 IT IS A "TYPICAL" SERVICE FOR EACH. NEC 230.2
  
 2. PROVIDE ACCURATE ONE-LINE DIAGRAM FOR NEW SERVICE
 SUPPLYING BOTH METERS. FBC 107.2.1
  
 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AFTER
 IT HAS BEEN REDESIGNED TO SHOW BOTH METERS BEING FED BY
 ONE MAST OF OVERHEAD SERVICE CONDUCTORS. FBC 107.2.1
 NEC 220
  
 4. TV RECEPTACLES IN BEDROOMS DO NOT MEET THE
 REQUIREMENTS FOR WALL SPACING WHEN ENTERING THROUGH
 BEDROOM DOOR. ADDITIONAL WALL SPACING RECEPTACLES
 REQUIRED WITHIN 6FT OF DOOR. NEC 210.52#4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-05 Cont ID  
Sent By vbroglia Date 2022-01-05 Time 10:06 Rev Time 0.00
Received By vbroglia Date 2021-11-23 Time 17:14 Sent To  
Notes
2021-11-23 17:14:54ENGINEER EMAILED REVISED PLANS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-17 Cont ID  
Sent By ajones Date 2021-11-17 Time 10:33 Rev Time 0.00
Received By ajones Date 2021-10-21 Time 12:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-30 Cont ID  
Sent By fgiaquin Date 2021-09-30 Time 23:47 Rev Time 0.00
Received By fgiaquin Date 2021-09-08 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 12:55 Rev Time 0.00
Received By jgomez Date 2021-07-27 Time 15:47 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-01-14 Cont ID  
Sent By lmarchan Date 2022-01-14 Time 10:05 Rev Time 0.00
Received By lmarchan Date 2022-01-10 Time 15:35 Sent To  
Notes
2022-01-14 10:05:46NO IMPACT FEES DUE. LEM
2022-01-10 15:35:201/10/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 12:43 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 11:26 Sent To  
Notes
2021-08-20 12:44:41IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-09-16 Cont ID  
Sent By hmoser Date 2021-09-16 Time 11:27 Rev Time 0.00
Received By hmoser Date 2021-09-13 Time 07:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-08-04 Cont ID  
Sent By medwards Date 2021-08-04 Time 07:30 Rev Time 0.00
Received By medwards Date 2021-08-04 Time 07:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-17 Cont ID  
Sent By ccole Date 2021-09-17 Time 15:34 Rev Time 0.00
Received By ccole Date 2021-09-17 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-28 Cont ID  
Sent By ccole Date 2021-07-28 Time 17:31 Rev Time 0.00
Received By ccole Date 2021-07-28 Time 17:02 Sent To  
Notes
2021-07-28 17:32:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21071231
 7/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 1-4 & P-1: PLEASE CLARIFY THE OCCUPANCY
 CLASSIFICATION OF THE BUILDING AND WHICH CODES ARE
 APPLICABLE. SHEET 1-4 INDICATES AN R-3 HOWEVER BOTH THE
 FBC-RES. AND FBC P CODES ARE LISTED AS APPLICABLE
 CODES. PLEASE NOTE THAT THE FBC RES. IS THE APPLICABLE
 PLUMBING CODE FOR SINGLE AND TWO-FAMILY RESIDENCES. FBC
 P IS THE PLUMBING CODE FOR THREE OR MORE. ARE THERE
 OTHER RESIDENCES ON THE LOT?
  
 2) P-1: SHOW THE LOCATIONS OF THE WATER HEATERS AND
 PROVIDE EQUIPMENT SCHEDULES, PAN AND PAN DRAIN DETAILS,
 DRAIN DISCHARGE LOCATION- SECTION P2801.1 FBC RES. AND
 C404.1 FBC EC.
  
 3) P-1: SHOW THE LOCATIONS OF THE SHUT OFF VALVES FOR
 THE WASHING MACHINES TO VERIFY THEY CAN BE ACCESSED-
 SECTION P2903.9.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 12:42 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 12:40 Sent To  
Notes
2021-08-20 12:42:45SHINGLES NOA 18-0123.06

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-11-24 Cont ID  
Sent By jgomez Date 2021-11-24 Time 09:28 Rev Time 0.00
Received By jgomez Date 2021-11-24 Time 09:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-16 Cont ID  
Sent By fgiaquin Date 2021-11-16 Time 23:19 Rev Time 0.00
Received By fgiaquin Date 2021-11-16 Time 23:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-23 Cont ID  
Sent By jgomez Date 2021-09-23 Time 11:19 Rev Time 0.00
Received By jgomez Date 2021-09-23 Time 11:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 12:55 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 12:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-01-05 Cont ID  
Sent By vbroglia Date 2022-01-05 Time 10:05 Rev Time 0.00
Received By vbroglia Date 2022-01-05 Time 10:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2021-11-17 Cont ID  
Sent By ajones Date 2021-11-17 Time 10:32 Rev Time 0.00
Received By ajones Date 2021-11-17 Time 10:32 Sent To  
Notes
2021-11-17 10:33:2311/17/21- FAILED. PLEASE PROVIDE THE FINAL FIRE REPORT
 INDICATING THE CAUSE OF THE FIRE.
  
 ANGELLA VANN
 [email protected]
 561-822-1441

Review Stop Z ZONING
Rev No 2 Status F Date 2021-09-15 Cont ID  
Sent By ajones Date 2021-09-15 Time 15:56 Rev Time 0.00
Received By ajones Date 2021-09-15 Time 15:56 Sent To  
Notes
2021-09-15 15:58:229/15/21- FAILED. AN EXISTING NONCONFORMING STRUCTURE
 AND USE CANNOT BE REBUILT. SEE ORIGINAL COMMENTS FOR
 MORE DETAILS
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By kalexand Date 2021-08-06 Time 17:42 Rev Time 0.00
Received By kalexand Date 2021-08-19 Time 10:59 Sent To  
Notes
2021-08-06 17:43:05ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE ATTACHED PLANS ARE FOR THE CONSTRUCTION OF A NEW
 DUPLEX BUILDING. AS THIS PROPOERTY IS WITHIN A SINGLE
 FAMILY LOW-DENSITY (SF7) ZONING DISTRICT, THE PROPOSED
 IS NOT PERMITTED.
  
 THE EXISTING DUPLEX STRUCTURE IS CONSIDERED A LEGALLY
 NON-CONFOMRING STRUCTURE (REGULATED BY SEC 94-515) AND
 CANNOT BE DEMOLISHED AND REBUILT OR EXPANDED. ALSO NOTE
 THAT ANY REPAIRS MUST NOT EXEED MORE THAN 50% OF THE
 IMPROVEMENT VALUE OF THE STRUCTURE.
  
 THE 2 UNITS WITHIN THE DUPLEX STRUCURE ARE ALSO
 CONSIDERED TO BE NONCONFORRMING USES (REGULATED BY SEC.
 94- 514) WHICH CANNOT BE EXPANDED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved