Plan Review Details - Permit 21071198
Plan Review Stops For Permit 21071198
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-02-10 Cont ID  
Sent By jleahy Date 2022-02-10 Time 16:29 Rev Time 0.00
Received By jleahy Date 2022-02-10 Time 16:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-01-25 Cont ID  
Sent By jleahy Date 2022-01-25 Time 15:58 Rev Time 0.00
Received By jleahy Date 2022-01-25 Time 15:54 Sent To  
Notes
2022-01-25 16:00:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PERMIT IS NOT FOR ACCESS CONTROL IT IS FOR LV/ TV IN
 UNITS $25,000 IS LOW PER SIZE OF BUILDING. PLANS CALLED
 FOR A SEPARATE PERMIT AND REVIEW FOR ALL LOW VOLTAGE
 SYSTEMS.
  
 VALUE IS LOW FOR SIZE OF BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By mpeterso Date 2021-12-27 Time 16:25 Rev Time 0.00
Received By mpeterso Date 2021-12-27 Time 16:25 Sent To  
Notes
2021-12-27 16:31:481) VALUE APPEARS TO BE VERY LOW. PLEASE PROVIDE A COST
 BREAKDOWN OF MATERIALS AND LABOR OR AT YOUR DISCRETION,
 A CONTRACT PROVIDING DETAILS AS TO THE TOTAL COST OF
 THE PROJECT. W.P.B. AMENDMENTS FBC 109.3
  
 2 )IT APPEARS PLANS LABELED "636-640 AND 643 " ARE
 COPIES OF A DIGIGITALLY SIGNED AND SEALED PLANS FROM
 THE ENGINEER OF RECORD THAT CANNOT BE CERTIFIED USING
 DIGITAL SOFTWARE
  
 PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-30 Cont ID  
Sent By cpuell Date 2022-01-30 Time 08:34 Rev Time 0.00
Received By cpuell Date 2022-01-05 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-03 Cont ID  
Sent By cpuell Date 2022-01-03 Time 16:29 Rev Time 0.00
Received By cpuell Date 2021-12-03 Time 09:30 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-01-31 Cont ID  
Sent By shill Date 2022-01-31 Time 09:09 Rev Time 0.00
Received By shill Date 2022-01-31 Time 09:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-10 Cont ID  
Sent By jleahy Date 2022-02-10 Time 16:29 Rev Time 0.00
Received By jleahy Date 2022-02-10 Time 16:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-25 Cont ID  
Sent By jleahy Date 2022-01-25 Time 16:01 Rev Time 0.00
Received By jleahy Date 2022-01-25 Time 15:54 Sent To  
Notes
2022-01-25 16:02:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS STILL APEAR TO BE COPIES. IT HAS OUR STAMPS ON
 THEM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-03 Cont ID  
Sent By rmcdouga Date 2022-01-03 Time 11:22 Rev Time 0.00
Received By rmcdouga Date 2022-01-03 Time 11:22 Sent To  
Notes
2022-01-03 11:23:47COULD NOT VERIFY ENGINEER'S SIGNATURE ON THE PLANS.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15