Plan Review Details - Permit 21071145
Plan Review Stops For Permit 21071145
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-01-10 Cont ID  
Sent By jleahy Date 2022-01-10 Time 10:48 Rev Time 0.00
Received By jleahy Date 2022-01-10 Time 10:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-10-12 Cont ID  
Sent By jleahy Date 2021-10-12 Time 13:12 Rev Time 0.00
Received By jleahy Date 2021-10-12 Time 13:09 Sent To  
Notes
2021-10-12 13:09:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 MAIN ARE NOT GROUPED PER 230.72. THE INSTALLATION DOES
 NOT MEET THE CODE.
  
 230.72 GROUPING OF DISCONNECTS.
 (A) GENERAL. THE TWO TO SIX DISCONNECTS AS PERMITTED IN
 230.71 SHALL BE GROUPED. EACH DISCONNECT SHALL BE
 MARKED TO INDICATE THE LOAD SERVED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By jleahy Date 2021-08-13 Time 12:41 Rev Time 0.00
Received By jleahy Date 2021-08-13 Time 09:03 Sent To  
Notes
2021-08-13 12:43:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 MAINS 1,2 3 ARE NO LONGER GROUPED? 230.72
  
 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE TWO TO
 SIX DISCONNECTS AS PERMITTED IN
 230.71 SHALL BE GROUPED. EACH DISCONNECT SHALL BE
 MARKED TO INDICATE THE LOAD SERVED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-12 Cont ID  
Sent By jleahy Date 2021-10-12 Time 13:30 Rev Time 0.00
Received By jleahy Date 2021-09-08 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-13 Cont ID  
Sent By jleahy Date 2021-08-13 Time 12:44 Rev Time 0.00
Received By jleahy Date 2021-07-29 Time 17:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-12 Cont ID  
Sent By jleahy Date 2021-10-12 Time 13:30 Rev Time 0.00
Received By jleahy Date 2021-10-12 Time 13:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-13 Cont ID  
Sent By jleahy Date 2021-08-13 Time 12:44 Rev Time 0.00
Received By jleahy Date 2021-08-13 Time 09:03 Sent To  
Notes
***NONE***