Plan Review Details - Permit 21071140
Plan Review Stops For Permit 21071140
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-01-10 Cont ID  
Sent By lcrespo Date 2022-01-10 Time 07:44 Rev Time 0.00
Received By lcrespo Date 2022-01-10 Time 07:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-12-02 Cont ID  
Sent By abelisle Date 2021-12-02 Time 18:30 Rev Time 0.00
Received By abelisle Date 2021-12-02 Time 16:42 Sent To  
Notes
2021-12-02 17:55:112ND REVIEW FBC-2020 PLUMBING
 PERMIT-21071140
 12/2/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. PROVIDE A CLEAR AND LEGIBLE PERMIT APPLICATION AND
 DRAWINGS FOR REVIEW.WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SECOND REQUEST. THE CITY OF WEST PALM BEACH HAS NO
 RECORD OF EXISTING GAS PERMITS WITH INSPECTIONS OF THE
 CURRENT SYSTEM. A COMPLETE EVALUATION OF ALL GAS
 SYSTEMS AND EQUIPMENT WILL BE DONE AT THE FIELD, AND IF
 NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE
 COMPLIANCE AT THE OWNER'S EXPENSE. PLEASE INCLUDE THE
 CURRENT AND NEW GAS SYSTEM AND EQUIPMENT IN THIS PERMIT
 FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE
 FBC SEC. 105.1.
  
 3. SECOND REQUEST. THERE ARE TWO TANKLESS WATER HEATERS
 ARE SHOWN, BUT THE PERMIT IS FOR A GENERATOR, AND IT IS
 NOT ON ISOMETRIC. WOULD YOU PLEASE CLARIFY WHICH IS
 CORRECT AND CHANGE THE DESCRIPTION ON THE PERMIT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 4. SECOND REQUEST. A SEPARATE PERMIT IS REQUIRED FOR
 THE GENERATOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 5. SECOND REQUEST. PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 6. SECOND REQUEST. THE CLAIMED VALUE APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION. WOULD YOU PLEASE
 PROVIDE A BONA FIDE SIGNED CONTRACT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 109.3 BUILDING PERMIT
 VALUATIONS?
  
 7. SECOND REQUEST. PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GENERATOR OR TANKLESS. THE
 GENERATOR SHALL BE LISTED AND APPROVED PER THE NFPA 58
 SEC. 5.20.1. THE GENERATOR SHALL MEET THE REQUIREMENTS
 OF UL 2200.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 09:10 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 09:10 Sent To  
Notes
2021-08-10 09:28:5308/10/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT
 SYSTEM. A COMPLETE EVALUATION OF ALL GAS SYSTEMS AND
 EQUIPMENT WILL BE DONE AT THE FIELD, AND IF NOT TO
 CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT
 THE OWNER'S EXPENSE. PLEASE INCLUDE THE CURRENT AND NEW
 GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE
 OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. THERE ARE TWO TANKLESS WATER HEATERS ARE SHOWN, BUT
 THE PERMIT IS FOR A GENERATOR, AND IT IS NOT ON
 ISOMETRIC. WOULD YOU PLEASE CLARIFY WHICH IS CORRECT
 AND CHANGE THE DESCRIPTION ON THE PERMIT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR PER
 THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 4. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 5. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION. WOULD YOU PLEASE PROVIDE A BONA FIDE
 SIGNED CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC.
 109.3 BUILDING PERMIT VALUATIONS?
  
 6. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE GENERATOR OR TANKLESS. THE GENERATOR SHALL BE
 LISTED AND APPROVED PER THE NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-10 Cont ID  
Sent By lcrespo Date 2022-01-10 Time 07:58 Rev Time 0.00
Received By lcrespo Date 2022-01-07 Time 12:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-03 Cont ID  
Sent By lmarchan Date 2021-12-03 Time 07:55 Rev Time 0.00
Received By lmarchan Date 2021-11-23 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 09:10 Rev Time 0.00
Received By lcrespo Date 2021-08-04 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2022-01-10 Cont ID  
Sent By lcrespo Date 2022-01-10 Time 07:44 Rev Time 0.00
Received By lcrespo Date 2022-01-10 Time 07:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-12-02 Cont ID  
Sent By abelisle Date 2021-12-02 Time 16:42 Rev Time 0.00
Received By abelisle Date 2021-12-02 Time 16:42 Sent To  
Notes
2021-12-02 18:31:242ND REVIEW FBC-2020 PLUMBING
 PERMIT-21071140
 12/2/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. PROVIDE A CLEAR AND LEGIBLE PERMIT APPLICATION AND
 DRAWINGS FOR REVIEW.WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 09:10 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 09:10 Sent To  
Notes
***NONE***