| 2021-12-02 17:55:11 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-21071140 |
| | 12/2/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1. PROVIDE A CLEAR AND LEGIBLE PERMIT APPLICATION AND |
| | DRAWINGS FOR REVIEW.WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SECOND REQUEST. THE CITY OF WEST PALM BEACH HAS NO |
| | RECORD OF EXISTING GAS PERMITS WITH INSPECTIONS OF THE |
| | CURRENT SYSTEM. A COMPLETE EVALUATION OF ALL GAS |
| | SYSTEMS AND EQUIPMENT WILL BE DONE AT THE FIELD, AND IF |
| | NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE |
| | COMPLIANCE AT THE OWNER'S EXPENSE. PLEASE INCLUDE THE |
| | CURRENT AND NEW GAS SYSTEM AND EQUIPMENT IN THIS PERMIT |
| | FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 105.1. |
| | |
| | 3. SECOND REQUEST. THERE ARE TWO TANKLESS WATER HEATERS |
| | ARE SHOWN, BUT THE PERMIT IS FOR A GENERATOR, AND IT IS |
| | NOT ON ISOMETRIC. WOULD YOU PLEASE CLARIFY WHICH IS |
| | CORRECT AND CHANGE THE DESCRIPTION ON THE PERMIT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. SECOND REQUEST. A SEPARATE PERMIT IS REQUIRED FOR |
| | THE GENERATOR PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 5. SECOND REQUEST. PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 6. SECOND REQUEST. THE CLAIMED VALUE APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION. WOULD YOU PLEASE |
| | PROVIDE A BONA FIDE SIGNED CONTRACT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 109.3 BUILDING PERMIT |
| | VALUATIONS? |
| | |
| | 7. SECOND REQUEST. PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GENERATOR OR TANKLESS. THE |
| | GENERATOR SHALL BE LISTED AND APPROVED PER THE NFPA 58 |
| | SEC. 5.20.1. THE GENERATOR SHALL MEET THE REQUIREMENTS |
| | OF UL 2200. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |