Plan Review Details - Permit 21071092
Plan Review Stops For Permit 21071092
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-08-12 Cont ID  
Sent By cpuell Date 2021-08-12 Time 08:13 Rev Time 0.00
Received By cpuell Date 2021-08-12 Time 08:13 Sent To  
Notes
2021-08-12 08:16:28TENANT TAKING OVER THE WHOLE OF THE 18TH FLOOR (AKA
 16TH FLOOR), NO SUITE NUMBER NEEDED HOWEVER 360 S
 FLAGLER DR FLOOR 18 IS THE DESIGNATORY ADDRESS

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By cpuell Date 2021-07-30 Time 16:09 Rev Time 0.00
Received By cpuell Date 2021-08-12 Time 08:12 Sent To  
Notes
2021-07-30 16:12:13PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE
 SUITE AS WELL AS A WHOLE FLOOR PLAN SHOWING ALL THE
 SUITES NUMBERS ON THE FLOOR. I WOULD ALSO SUGGEST
 GETTING WITH MIKE IZZO ([email protected]) AS A SUITE
 NUMBER MAY HAVE BEEN ASSIGNED FOR THIS UNIT. PLEASE
 EMAIL [email protected] OR CALL 561-805-6659 WITH
 RESPONSES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2021-08-17 Cont ID  
Sent By rmcphers Date 2021-08-17 Time 12:31 Rev Time 0.00
Received By rmcphers Date 2021-08-17 Time 08:10 Sent To  
Notes
2021-08-17 12:31:29NEW SPACE - NO DEMO

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-09-27 Cont ID  
Sent By rmcphers Date 2021-09-27 Time 07:53 Rev Time 0.00
Received By rmcphers Date 2021-09-27 Time 07:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-15 Cont ID  
Sent By rmcphers Date 2021-09-15 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2021-09-15 Time 15:03 Sent To  
Notes
2021-09-15 15:15:49OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ACCESSIBLE RESTROOMS - THE GRAB BAR MAXIMUM HEIGHT
 SHOULD BE SHOWN TO THE TOP OF THE GRIPPING SURFACE (NOT
 THE CENTER OF THE GRAB BAR) FBC A 609.4 POSITION OF
 GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 2) THE TOILET PAPER HOLDER LOCATION DIMENSIONS FROM THE
 FRONT OF THE TOILET SEAT IS SHOWN INCORRECTLY FOR AN
 ACCESSIBLE RESTROOM FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
 3) THE MIRROR DIMENSIONS FROM THE FLOOR SHOULD BE TO
 THE "REFLECTIVE SURFACE" FOR AN ACCESSIBLE RESTROOM PER
 FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) PLEASE SHOW ALL WOOD AND PLYWOOD BACKING TO BE FIRE
 RETARDANT PER FBC 603.1 AND FBC 803.13.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By rmcphers Date 2021-08-17 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2021-08-17 Time 08:10 Sent To  
Notes
2021-08-17 11:56:58OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE A FINISH SCHEDULE.
 2) FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
 3) FBC 1210.2.1 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM).
 4) FBC 1210.2.3 SHOWERS.
 SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH
 INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH,
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72
 INCHES (1829 MM) ABOVE THE DRAIN INLET.
 5) PLEASE SHOW THE ACCESSIBLE SEATING IN THE CAFE FBC
 A226.1 GENERAL.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
 6) PLEASE SHOW THE GRAB BAR SIZES AND LOCATION
 DIMENSIONS AT THE SHOWER TO COMPLY WITH FBC 608.3.2
 7) PLEASE SHOW THE SHOWER SEAT SIZE AND LOCATION
 DIMENSIONS TO COMPLY WITH FBC A610.3
 8) RAMPS ARE SHOWN IN DIFFERENT AREAS ON DRAWING A1.116
 - PLEASE SHOW THE LANDINGS AT DOORS TO COMPLY WITH FBC
 A404.2.4.4 FLOOR OR GROUND SURFACE.
 FLOOR OR GROUND SURFACE WITHIN REQUIRED MANEUVERING
 CLEARANCES SHALL COMPLY WITH 302. CHANGES IN LEVEL ARE
 NOT PERMITTED.
 9) PLEASE SHOW RAMP LENGTHS AND RISE TO DETERMINE IF A
 HANDRAIL IS REQUIRED PER FBC A405.8 HANDRAILS.
 RAMP RUNS WITH A RISE GREATER THAN 6 INCHES (150 MM)
 SHALL HAVE HANDRAILS COMPLYING WITH 505.
 10) THE TOILET PAPER HOLDER LOCATION DIMENSIONS FROM
 THE FRONT OF THE TOILET SEAT IS SHOWN INCORRECTLY FOR
 AN ACCESSIBLE RESTROOM FBC A604.7
 11) THE MIRROR DIMENSIONS FROM THE FLOOR SHOULD BE TO
 THE "REFLECTIVE SURFACE" FOR AN ACCESSIBLE RESTROOM PER
 FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-07 Cont ID  
Sent By jleahy Date 2021-09-07 Time 15:40 Rev Time 0.00
Received By jleahy Date 2021-09-07 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By jleahy Date 2021-08-17 Time 12:01 Rev Time 0.00
Received By jleahy Date 2021-08-17 Time 10:43 Sent To  
Notes
2021-08-17 11:25:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) IN THE CAFE ANY OUTLET WITHIN 6' OF THE SINK TO BE
 GFCI PROTECTED 210.8(B)
  
 2) ANY CONFERENC ROOM LESS THAN 100 SQ. FT. SHALL HAVE
 WALL OUTLETS INSTALLED PER 210.71(B)(1)
  
 3) ANY CONFERENCE ROOM MORE THAN 214 SQ. FT. SHALL HAVE
 FLOOR OUTLET(S) INSTALLED PER 210.71(B)(2)
  
 4) ANY OUTLET WITHIN 6' OF ANY SINK SHALL BE GFCI
 PROTECTED PER 210.8(B)(5)
  
 5) PANEL NL16A NOT SHOWN ON RISER DIAGRAM 215.5
  
 6) PANEL NL 16A DOES NOT HAVE A PANEL SHCEDULE FOR
 REVIEW.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-10-14 Cont ID  
Sent By jleahy Date 2021-10-14 Time 13:32 Rev Time 0.00
Received By jleahy Date 2021-10-14 Time 13:32 Sent To  
Notes
2021-10-14 13:32:41VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-13 Cont ID  
Sent By pleduc Date 2021-08-13 Time   Rev Time 0.00
Received By pleduc Date 2021-08-09 Time 11:41 Sent To  
Notes
2021-08-13 14:51:35FIRE PROVISO:
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-27 Cont ID  
Sent By rmcphers Date 2021-09-27 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-15 Cont ID  
Sent By rmcphers Date 2021-09-15 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2021-08-26 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-18 Cont ID  
Sent By medwards Date 2021-08-18 Time 08:12 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 14:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-08-13 Cont ID  
Sent By shill Date 2021-08-13 Time 07:25 Rev Time 0.00
Received By shill Date 2021-08-13 Time 07:25 Sent To  
Notes
2021-08-13 07:25:51PAID UNDER PRIMARY BUILDING PERMIT
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-09-24 Cont ID  
Sent By medwards Date 2021-09-24 Time 07:10 Rev Time 0.00
Received By medwards Date 2021-09-24 Time 07:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 08:13 Rev Time 0.00
Received By medwards Date 2021-08-28 Time 08:13 Sent To  
Notes
2021-08-28 08:13:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071092
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE, EACH SPACE WILL REQUIRE A CERTAIN AMOUNT
 OF OUTDOOR AIR PLEASE SHOW THAT CFM NUMBER FOR EACH
 SPACE. I.E. LARGE CONFERENCE ROOM (18A19) 168 SQ
 FT/1000 = .168; .168 X 50 = 8.4; 8.4 X 5 = 42; 168 X
 .06 = 10.08; 42 + 10.08 = 52.08 CFM OF OUTDOOR AIR
 REQUIRED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-18 Cont ID  
Sent By medwards Date 2021-08-18 Time 07:54 Rev Time 0.00
Received By medwards Date 2021-08-17 Time 16:43 Sent To  
Notes
2021-08-18 07:55:051ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071092
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-601: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR EACH SPACE IN THIS TENANT SPACE. FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
 2) SHEET MH-216: PLEASE PROVIDE INFORMATION FOR THE
 PREP KITCHEN, WHAT IS THE PURPOSE OF THIS PREP KITCHEN?
 WHAT IS GOING TO BE PREPARED IN THIS PREP KITCHEN?
 WHERE IS THE EXHAUST FOR THIS PREP KITCHEN? FBC 107.2.1
  
 3) SHEET MH-216: PLEASE EXPLAIN NOTE 10 FOR THE SMALL
 DUCT COMING FROM THE MECHANICAL ROOM TO THE VAV IN THE
 ELECTRICAL ROOM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-09-24 Cont ID  
Sent By ccole Date 2021-09-24 Time 14:30 Rev Time 0.00
Received By ccole Date 2021-09-24 Time 13:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-09-13 Cont ID  
Sent By ccole Date 2021-09-13 Time 10:32 Rev Time 0.00
Received By ccole Date 2021-09-13 Time 08:33 Sent To  
Notes
2021-09-13 10:33:172ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21071092
 9/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES IN CAP
 LETTERS FOR FURTHER CLARIFICATION.
  
 1) FAILED A, B, C, G, I, J, K. SHEETS A3.01 & A3.02-
 MISSING OR INCORRECT ACCESSIBLE PLUMBING FIXTURE
 DETAILS FOR THE BATHROOMS PER FBC ACC:
  
 A) FAILED CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. WATER CLOSET CLEAR
 FOOR SPACE SHALL BE 56 INCES MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. THE DOOR SHALL NTO
 SWING INTO THE CLEAR FLOOR SPACE- SECTION 603.2.3.
  
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE LAVATORIES- 606.2. THE DOOR SHALL NTO SWING INTO
 THE CLEAR FLOOR SPACE- SECTION 603.2.3.
  
 C) FAILED. TURNING SPACE DIAGRAMS AND DIMENSIONS-
 304.3. DIMENSION NOT PROVIDED.
  
 G) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- 604.5 & 609.4, FIGURES
 604. PLEASE SHOW THE MINIMUM AND MAXIMUM DIMENSIONS AS
 SHOWN IN THE FIGURES. THE DETAIL INCORRECTLY SHOWS THE
 HEIGHTS OF THE GRAB BARS MEASURED TO THE CENTERLINES OF
 THE GRAB BAR AND NOT THE TOPS OF THE GRIPPING SURFACES.
  
 I) FAILED LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS
 - 604.6. NOT PROVIDED.
  
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. THE DRAWING DOES NOT SHOW THE
 MEASUREMENT TO THE CENTER OF THE DISPENSER. DETAIL WAS
 NOT CORRECTED.
  
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED. DETAIL 10 ON A5.32 DOES
 NOT SHOW TOE CLEARANCES.
  
 2) FAILED C & F. SHEETS A3.01 & A3.02- MISSING OR
 INCORRECT ACCESSIBLE SHOWER DETAILS PER FBC ACC:
  
 C) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- 608.3 AND 608.3.1. REAR GRAB BAR LENGTH NOT
 SHOWN. HEIGHT OF 3'2" EXCEEDS MAX 36".
  
 F) FAILED. LOCATION OF ACCESSIBLE SHOWER SEAT AND
 MOUNTING DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
 SEAT HEIGHT PROVIDED BUT NOT PROPER MOUNTING LOCATIONS
 AND CLEARANCES PER FIGURE 610.3.2.
  
 5) FAILED. A1.116: SHOW THE INTERIOR DIMENSIONS OF THE
 NEW WATER CLOSET COMPARTMENT IN THE MEN'S BATHROOM-
 SECTION 405.3.1 FBC P. MINIUM 60 INCH DEPTH FOR FLOOR
 MOUNTED WATER CLOSETS, AND 56 INCHES FOR WALL MOUNTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-09-13 10:33:012ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21071092
 9/13/2021
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES IN CAP
 LETTERS FOR FURTHER CLARIFICATION.
 1) FAILED A, B, C, G, I, J, K. SHEETS A3.01 & A3.02-
 MISSING OR INCORRECT ACCESSIBLE PLUMBING FIXTURE
 DETAILS FOR THE BATHROOMS PER FBC ACC:
 A) FAILED CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. WATER CLOSET CLEAR
 FOOR SPACE SHALL BE 56 INCES MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. THE DOOR SHALL NTO
 SWING INTO THE CLEAR FLOOR SPACE- SECTION 603.2.3.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE LAVATORIES- 606.2. THE DOOR SHALL NTO SWING INTO
 THE CLEAR FLOOR SPACE- SECTION 603.2.3.
 C) FAILED. TURNING SPACE DIAGRAMS AND DIMENSIONS-
 304.3. DIMENSION NOT PROVIDED.
 G) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- 604.5 & 609.4, FIGURES
 604. PLEASE SHOW THE MINIMUM AND MAXIMUM DIMENSIONS AS
 SHOWN IN THE FIGURES. THE DETAIL INCORRECTLY SHOWS THE
 HEIGHTS OF THE GRAB BARS MEASURED TO THE CENTERLINES OF
 THE GRAB BAR AND NOT THE TOPS OF THE GRIPPING SURFACES.
 I) FAILED LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS
 - 604.6. NOT PROVIDED.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. THE DRAWING DOES NOT SHOW THE
 MEASUREMENT TO THE CENTER OF THE DISPENSER. DETAIL WAS
 NOT CORRECTED.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED. DETAIL 10 ON A5.32 DOES
 NOT SHOW TOE CLEARANCES.
 2) FAILED C & F. SHEETS A3.01 & A3.02- MISSING OR
 INCORRECT ACCESSIBLE SHOWER DETAILS PER FBC ACC:
 C) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- 608.3 AND 608.3.1. REAR GRAB BAR LENGTH NOT
 SHOWN. HEIGHT OF 3?2? EXCEEDS MAX 36?.
 F) FAILED. LOCATION OF ACCESSIBLE SHOWER SEAT AND
 MOUNTING DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
 SEAT HEIGHT PROVIDED BUT NOT PROPER MOUNTING LOCATIONS
 AND CLEARANCES PER FIGURE 610.3.2.
 5) FAILED. A1.116: SHOW THE INTERIOR DIMENSIONS OF THE
 NEW WATER CLOSET COMPARTMENT IN THE MEN'S BATHROOM-
 SECTION 405.3.1 FBC P. MINIUM 60 INCH DEPTH FOR FLOOR
 MOUNTED WATER CLOSETS, AND 56 INCHES FOR WALL MOUNTED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By ccole Date 2021-08-17 Time 14:57 Rev Time 0.00
Received By ccole Date 2021-08-17 Time 11:23 Sent To  
Notes
2021-08-17 14:57:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21071092
 8/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A3.01 & A3.02- MISSING OR INCORRECT
 ACCESSIBLE PLUMBING FIXTURE DETAILS FOR THE BATHROOMS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- 606.2.
 C) TURNING SPACE DIAGRAMS AND DIMENSIONS- 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- 604.2.
 E) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOOR- 606.3.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- 604.5 & 609.4, FIGURES 604.
 PLEASE SHOW THE MINIMUM AND MAXIMUM DIMENSIONS AS SHOWN
 IN THE FIGURES.
 H) REMOVE THE VERTICAL GRAB BAR SHOWN IN THE DETAIL.
 GRAB BARS SHALL BE INSTALLED IN HORIZONTAL POSITIONS-
 609.4
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. THE DRAWING DOES NOT SHOW THE MEASUREMENT
 TO THE CENTER OF THE DISPENSER.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
  
 2) SHEETS A3.01 & A3.02- MISSING OR INCORRECT
 ACCESSIBLE SHOWER DETAILS PER FBC ACC:
 A) CLEAR INSIDE DIMENSIONS- SECTION 608.2.1
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS- 608.2.1.
 C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- 608.3 AND 608.3.1
 D) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- 608.5.1 & FIGURE 608.5.1. THE DRAWING SHOWS THE
 LOCATION OF THE CONTROL, FAUCET, AND SPRAY IN THE WRONG
 LOCATION.
 E) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
 F) LOCATION OF ACCESSIBLE SHOWER SEAT AND MOUNTING
 DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
 G) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE SINK
 AND SINK MOUNTING HEIGHT- 606.2 & 606.3.
  
 3) A3.03: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSION FOR THE SINK- 606.2.
  
 4) A3.03 & A3.04: A) CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSION FOR THE SINK AND SINK MOUNTING HEIGHT- 606.2
 & 606.3. B) REACH RANGES AND OPERABLE PARTS FOR THE
 COFFEE MAKER AND DISPENSER- 308. SUBMIT MANUFACTURER'S
 SPECIFICATIONS TO VERIFY COMPLIANCE.
  
 5) A1.116: SHOW THE INTERIOR DIMENSIONS OF THE NEW
 WATER CLOSET COMPARTMENT IN THE MEN'S BATHROOM- SECTION
 405.3.1 FBC P.
  
 6) REFER TO SECTION 310.3 FBC P AND SECTION 1210.2.2
 AND INDICATE THE TYPE OF WALL FINISH SURROUND MATERIAL
 TO BE INSTALLED AT THE MOP SINK
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-24 Cont ID  
Sent By ccole Date 2021-09-24 Time 13:34 Rev Time 0.00
Received By ccole Date 2021-09-24 Time 13:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-15 Cont ID  
Sent By rmcphers Date 2021-09-15 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2021-09-15 Time 15:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-17 Cont ID  
Sent By rmcphers Date 2021-08-17 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2021-08-17 Time 13:07 Sent To  
Notes
***NONE***