| Plan Review Stops For Permit 21071047 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-01 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-01 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-10-25 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-25 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2021-10-25 15:39:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SHOW BRANCH CIRCUIT SIZE FOR CONDUCTOR, AND | | | WIRE SIZE. | | | | | | GFCI PROTECTION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2021-09-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-30 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-30 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2021-09-30 09:51:49 | SEE COMMENTS FROM FIRST REVIEW JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-28 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-28 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2021-07-28 11:42:50 | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PLEASE SUBMIT A PLAN SHOWING THE BRANCH CIRCUIT AND | | | SIZE FOR THE TUB, 215.5 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-07-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-07-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-07-23 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2021-07-23 10:53:00 | FIRE PROVISO: | | | | | | MAINTAIN/REPAIR, IF APPLICABLE, THE FIRE | | | RATED TENANT SEPARATION WALL BOARD | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-01 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-28 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-10-25 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-10-05 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-30 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-08 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-28 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-21 |
Time |
15:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-22 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-22 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2021-07-22 10:22:53 | 07/22/21 REVIEWED FOR CODE COMPLIANCE | | | (PLUMBING/BACKFLOW) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
N |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-01 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-01 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-10-25 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-25 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2021-10-25 15:37:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ALL PLANS SUBMITTED NEED TO BE SIGNED BY QUALIFIER. | | | JLEAHY | | | | | | SAME AS LAST REVIEW. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-09-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-30 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-30 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2021-09-30 09:52:51 | SEE COMMENT FROM FIRST REVIEW JLEAHY |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-28 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-28 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2021-07-28 12:16:10 | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | | | | |
|
|