Plan Review Details - Permit 21071007
Plan Review Stops For Permit 21071007
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 06:52 Rev Time 0.00
Received By shill Date 2021-08-21 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By jbrooks Date 2021-08-03 Time 13:47 Rev Time 0.00
Received By jbrooks Date 2021-08-03 Time 11:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 14:08 Rev Time 0.00
Received By shill Date 2021-07-21 Time 14:08 Sent To  
Notes
2021-07-21 14:15:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC R 301:
  
 1. ON THE INSTALLATION SCHEDULE IT STATES THAT THE
 SUBSTRATE IS CONCRETE/BLOCK. DOES THAT MEAN CONCRETE ON
 THE TOP, BLOCK ON THE BOTTOM, OR CONCRETE BLOCK?
  
 PAGE 6, THE TRAPPED MOUNT IS CIRCLED. AT THE TOP POURED
 CONCRETE IS REQUIRED, SPACING CAN BE 24" PER THE
 DETAIL. THEREFORE IT APPEARS THAT THE ANCHOR SPACING
 PROPOSED IS FOR THE SIDES.
  
 PAGE 8 BUILDOUT MOUNT IS CIRCLED, IT REFERS TO ANCHOR
 CHARTS ON SHEETS 17 AND 15, THIS ALLOWS FOR FILLED
 CONCRETE BLOCK SUBSTRATE, NOTHING ON PAGES 17 AND 18
 ARE CIRCLED.
  
 PAGE 16 ANCHOR SPACING FOR TRAPPED MOUNT IS CIRCLED.
 SUBSTRATE IS REQUIRED TO BE POURED CONCRETE (NOT BLOCK,
 NOT FILLED CELL BLOCK).
  
 PLEASE CORRELATE THE ANCHOR SCHEDULE, THE MARKUPS ON
 THE PRODUCT APPROVAL, AND THE PROPOSED INSTALLATION.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-08-19 Cont ID  
Sent By jleahy Date 2021-08-19 Time 16:25 Rev Time 0.00
Received By jleahy Date 2021-08-19 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-07-27 Cont ID  
Sent By jleahy Date 2021-07-27 Time 11:46 Rev Time 0.00
Received By jleahy Date 2021-07-27 Time 11:43 Sent To  
Notes
2021-07-27 11:47:22 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A PLAN SHOWING THE SIZE OF THE WIRE AND
 OVERCURRENT PROTECTION FOR THE ROLL UP SHUTTER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By jleahy Date 2021-07-22 Time 19:52 Rev Time 0.00
Received By jleahy Date 2021-07-22 Time 19:51 Sent To  
Notes
2021-07-22 19:53:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT AN ELECTRICAL PLAN FOR SHUTTER.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 06:52 Rev Time 0.00
Received By shill Date 2021-08-12 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-03 Cont ID  
Sent By jbrooks Date 2021-08-03 Time 13:47 Rev Time 0.00
Received By jbrooks Date 2021-07-23 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-22 Cont ID  
Sent By jleahy Date 2021-07-22 Time 19:53 Rev Time 0.00
Received By jleahy Date 2021-07-20 Time 12:29 Sent To  
Notes
***NONE***