Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 16:17 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 15:08 Sent To  
Notes
2021-08-10 15:09:14PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 15:09 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 14:47 Sent To  
Notes
2021-08-10 15:33:23REPAIRS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE A CONCRETE/REBAR REPAIR DETAIL ON THE
 DRAWINGS. FBC 107.2.1.2
 2) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE ROOFING SYSTEM - IN THE
 PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK - PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL - ROOFING SYSTEM TO BE USED ON THE PROVIDED
 PRODUCT APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND
 SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER
 FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER
 PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL
 - SEE GENERAL NOTES ON THE PRODUCT APPROVAL.
 3) DRAWING A-5 DETAIL NUMBER 4 - PLEASE SHOW ALL
 ATTACHMENT SIZES, TYPES AND ON CENTER SPACING FOR THE
 BLOCKING AND PARAPET CAP. FBC WPB 107.2.1.1

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-26 Cont ID  
Sent By pleduc Date 2021-08-26 Time   Rev Time 0.00
Received By pleduc Date 2021-08-26 Time 10:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By pleduc Date 2021-07-27 Time   Rev Time 0.00
Received By pleduc Date 2021-07-27 Time 10:24 Sent To  
Notes
2021-07-27 10:41:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PLEASE PROVIDE A DETAILED REVIEW OF THE CONCERN OF
 FALLING CONSTRUCTION DEBRIS AND WHAT LIFE SAFETY
 FEATURES WILL BE PROVIDED/INSTALLED TO PROTECT
 PEDESTRIANS AND THOSE ON THE AMENTITY DECK THROUGHOUT
 THE REPAIR PROCESS.
  
 PER NFPA 1:
  
 4.5.1.2 WHERE IT IS EVIDENT THAT A REASONABLE DEGREE OF
 SAFETY
 IS PROVIDED, ANY REQUIREMENT SHALL BE PERMITTED TO BE
 MODIFIED
 IF ITS APPLICATION WOULD BE HAZARDOUS UNDER NORMAL
 OCCUPANCY
 CONDITIONS IN THE JUDGMENT OF THE AHJ.
  
 4.5.6 CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS.
 4.5.6.1 BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE
 PERMITTED
 TO BE OCCUPIED DURING CONSTRUCTION, REPAIR,
 ALTERATIONS, OR ADDITIONS
 ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION FEATURES ARE IN PLACE AND CONTINUOUSLY
 MAINTAINED
 FOR THE PORTION OCCUPIED OR WHERE ALTERNATIVE LIFE
 SAFETY MEASURES
 AND BUILDING PROTECTION MEASURES ACCEPTABLE TO THE AHJ
 ARE IN PLACE.
  
 PER NFPA 241, INCLUDING BUT NOT LIMITED TO:
  
 CHAPTER 8 SAFEGUARDING CONSTRUCTION AND ALTERATION
 OPERATIONS
 8.1 GENERAL. IN ADDITION TO THE SPECIFIC REQUIREMENTS
 OF THIS
 CHAPTER, THE PROVISIONS OF CHAPTER 1 AND CHAPTERS 3
 THROUGH 7
 SHALL BE FOLLOWED, AS APPLICABLE, FOR ALL CONSTRUCTION.
  
 CHAPTER 9 SAFEGUARDING ROOFING OPERATIONS
 9.1 GENERAL. ALL ROOFING OPERATIONS INVOLVING HEAT
 SOURCES
 AND HOT PROCESSES SHALL BE CONDUCTED BY A QUALIFIED
 AGENCY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 16:47 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 15:44 Rev Time 0.00
Received By rmcphers Date 2021-07-26 Time 15:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 16:16 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 16:16 Sent To  
Notes
2021-09-14 16:17:34ROOFING PERMIT APPLICATION REQUIRED FROM A ROOFING
 CONTRACTOR

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-15 Cont ID  
Sent By pvalenti Date 2021-09-15 Time 15:40 Rev Time 0.00
Received By pvalenti Date 2021-09-15 Time 15:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 16:44 Sent To  
Notes
2021-09-14 16:47:35SIGNATURE REVIEW
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A-3 NEEDS TO BE SIGNED AND SEALED BY THE
 DESIGNER FBC WPB 107.1
  
 FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 15:42 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 15:42 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status N Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 16:18 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 16:18 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 15:44 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 15:33 Sent To  
Notes
2021-08-10 15:40:35THRESHOLD BUILDING
 CONCRETE RESTORATION
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 1) ANY REPAIRS TO THRESHOLD BUILDINGS ARE REQUIRED TO
 COMPLY WITH FS 553.79. THRESHOLD BLDG. REQUIRED
 STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 FLORIDA STATUTES.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved