Plan Review Details - Permit 21070982
Plan Review Stops For Permit 21070982
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-17 Cont ID  
Sent By jbrooks Date 2021-08-17 Time 10:21 Rev Time 0.00
Received By jbrooks Date 2021-08-17 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-05 Cont ID  
Sent By rmcphers Date 2021-08-05 Time 08:04 Rev Time 0.00
Received By rmcphers Date 2021-08-05 Time 07:45 Sent To  
Notes
2021-08-05 08:04:01ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) ROOFING SYSTEM CIRCLED TO BE USED ON THE PROVIDED
 PRODUCT APPROVAL DOES NOT MEET THE REQUIRED WIND
 PRESSURES PER FBC R TABLE R301.2(2) - - - WHEN CHOOSING
 A DIFFERENT ROOF SYSTEM PLEASE KEEP IN MIND TO REVIEW
 THE NOTES ON THE PRODUCT APPROVAL - NOTE NUMBER 9 ON
 THE PRODUCT APPROVAL - ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL.
  
 FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By jbrooks Date 2021-07-30 Time 09:53 Rev Time 0.00
Received By jbrooks Date 2021-07-30 Time 07:42 Sent To  
Notes
2021-07-30 09:53:56JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL12772-R6 HAS BEEN
 REVISED TO FL12772-R8. PROVIDE THE FOLLOWING: COVER
 PAGE, EVALUATION REPORTS PAGES 1-4 TO INCLUDE
 LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. SELECTED SYSTEM THAT MEETS OR EXCEEDS
 EXPOSURE CATEGORY C MINIMUM DESIGN PRESSURE
 REQUIREMENTS OF -108.17. SIGNED AND SEALED NAILING
 CALCULATIONS MAY BE REQUIRED.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), ROOF HEIGHT(S).
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-17 Cont ID  
Sent By jbrooks Date 2021-08-17 Time 10:21 Rev Time 0.00
Received By jbrooks Date 2021-08-16 Time 06:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-05 Cont ID  
Sent By rmcphers Date 2021-08-05 Time 08:04 Rev Time 0.00
Received By rmcphers Date 2021-08-03 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-30 Cont ID  
Sent By jbrooks Date 2021-07-30 Time 09:54 Rev Time 0.00
Received By jbrooks Date 2021-07-29 Time 09:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-16 Cont ID  
Sent By jleahy Date 2021-08-16 Time 16:35 Rev Time 0.00
Received By jleahy Date 2021-08-16 Time 16:35 Sent To  
Notes
2021-08-16 16:42:42SIGNATURE FILE SENT TO STORAGE JLEAHY