Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-03 Cont ID  
Sent By jleahy Date 2021-08-03 Time 15:34 Rev Time 0.00
Received By jleahy Date 2021-08-03 Time 15:32 Sent To  
Notes
2021-08-03 15:35:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW SIZE OF CIRCUITS FOR NEW AC
  
 NEED TO SUPLLY A LOAD CALCLUATION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-03 Cont ID  
Sent By jleahy Date 2021-08-03 Time 15:36 Rev Time 0.00
Received By jleahy Date 2021-07-22 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 08:51 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 08:51 Sent To  
Notes
2021-08-02 08:56:07PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS NEW MINISPLIT. THE CALCULATIONS
 MUST BE SIGNED BY THE CONTRACTOR HOLDING THE PERMIT TO
 INSTALL THE UNIT AT THIS ADDRESS OR A LICENSED ENGINEER
 WOULD NEED TO SIGN AND STAMP THE EQUIPMENT SIZING
 CALCULATIONS AND THE DESIGN. FBC EC R403.7
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 08:56 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 08:56 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved