| Plan Review Stops For Permit 21070967 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-15 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-15 |
Time |
08:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-30 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-30 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2021-07-30 15:07:50 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-15 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-15 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-30 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-30 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2021-07-30 15:11:34 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE LOCATION AND FLOORING TYPE ON THE | | | FLOOR PLAN. | | | | | | 2) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | | PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | 3). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | | TO PROJECTDOX ( [email protected] ) | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2021-08-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-02 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-02 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2021-08-02 13:43:30 | NO ELECTRICAL WORK SHOWN ON PLANS JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-08-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-08-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-08-26 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2021-08-26 11:44:06 | FIRE PROVISO: | | | | | | ENSURE FIRE RATED TENANT SEPARATION WALLS | | | ARE MAINTAINED & REPAIRED IF DAMAGED. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-07-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-07-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-07-23 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2021-07-23 10:01:04 | FIRE PROVISO: | | | | | | MAINTAIN/REPAIR, IF APPLICABLE, FIRE RATING OF | | | TENANT SEPARATION WALL BOARDS IF ALTERED/DAMAGED | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-09-29 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-09-29 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-09-28 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-15 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-25 |
Time |
09:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-08-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-02 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-21 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-09-10 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-10 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2021-09-10 10:59:53 | 09/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-08-06 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-27 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-27 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2021-07-27 11:58:02 | 08/06/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-09-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-09-29 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-29 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-09-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-09-22 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-22 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2021-09-22 17:06:45 | 3RD SIGNATURE REVIEW | | | PERMIT- 21070967 | | | 9/22/21 | | | | | | RESULTS- DENIED. | | | | | | 1) THE SUBMITTED PAPER PLANS- COV & A1 HAVE COPIED | | | ARCHITECT'S SEALS AND SIGNATURES. PLANS DESIGNED BY FL | | | LICENSED ARCHITECTS SUBMITTED IN PAPER FORM SHALL BEAR | | | THE RAISED OR INK SEAL AND WET SIGNATURE OF THE | | | ARCHTECT OF RECORD- FL. STATUTE-481.221 AND SECTION | | | 61G1-16.002 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-15 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-15 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2021-09-15 08:34:36 | SIGNATURE REVIEW | | | ALL DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN | | | ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX | | | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE | | | ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN | | | REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES NOT | | | HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP | | | OFF THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS | | | TO THE FRONT DESK IN THE BUILDING DIVISION AT THE CITY | | | HALL. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-30 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-30 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2021-07-30 15:13:14 | SIGNATURE REVIEW | | | DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE | | | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED | | | TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER | | | OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR | | | - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL. | | | |
|
|