Plan Review Details - Permit 21070960
Plan Review Stops For Permit 21070960
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-07-28 Cont ID  
Sent By cpuell Date 2021-07-28 Time 08:11 Rev Time 0.00
Received By cpuell Date 2021-07-28 Time 08:11 Sent To  
Notes
2021-07-28 08:14:30CONSULTED WITH M.ORIO AS THIS BRIDGE ENCOMPASSES TWO
 PARCELS. HE SUGGESTED THAT WE CHOOSE THE PARCEL
 FRONTING A MAIN STREET AND NOT A SIDE/FEEDER STREET. SO
 THE PARCEL FOR THIS PROJECT WILL BE 74434333000001030
 WITH THE ADDRESS OF 2751 S DIXIE HWY

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status P Date 2022-09-15 Cont ID  
Sent By swelter Date 2022-09-15 Time 10:57 Rev Time 0.00
Received By swelter Date   Time   Sent To  
Notes
2022-09-15 10:57:46DEVELOPER SATISFIED PUBLIC ART REQUIREMENT - OPTION 2
 CONTRIBUTION 9.13.2022

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-08-17 Cont ID  
Sent By scwelter Date 2021-08-17 Time 13:59 Rev Time 0.00
Received By scwelter Date 2021-08-17 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-11-02 Cont ID  
Sent By rmcphers Date 2021-11-02 Time 16:15 Rev Time 0.00
Received By rmcphers Date 2021-11-02 Time 16:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 16:43 Rev Time 0.00
Received By rmcphers Date 2021-08-26 Time 16:57 Sent To  
Notes
2021-08-30 16:40:14BRIDGE OVER RAILROAD TRACKS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE ROOFING MATERIAL DETAILS (TYPE OF
 MATERIAL, ATTACHMENTS TO STRUCTURE ETC.).
 2) PLEASE PROVIDE A SURVEY FOR EACH PROPERTY THAT THE
 BRIDGE IS ON.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-27 Cont ID  
Sent By jleahy Date 2021-10-27 Time 10:22 Rev Time 0.00
Received By jleahy Date 2021-10-27 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-24 Cont ID  
Sent By jleahy Date 2021-08-24 Time 13:41 Rev Time 0.00
Received By jleahy Date 2021-08-24 Time 13:23 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-10-21 Cont ID  
Sent By rrossano Date 2021-10-21 Time   Rev Time 0.00
Received By rrossano Date 2021-10-21 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By rrossano Date 2021-08-04 Time   Rev Time  
Received By rrossano Date 2021-08-04 Time   Sent To  
Notes
2021-08-04 13:33:48PLEASE ADDRESS FIRE COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By pleduc Date 2021-10-15 Time   Rev Time 0.00
Received By pleduc Date 2021-10-15 Time 11:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By pleduc Date 2021-07-27 Time   Rev Time 0.00
Received By pleduc Date 2021-07-23 Time 15:50 Sent To  
Notes
2021-07-27 15:15:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE STAIR DETAIL DID NOT INDICATE CLEARLY TEH DESIGN
 TO MINIMIZE WATER ACCUMULATION.
  
 PER NFPA 101 , CH 7 MEANS OF EGRESS
  
 7.2.2.6.5* WATER ACCUMULATION. OUTSIDE STAIRS AND
 LANDINGS, OTHER
 THAN EXISTING OUTSIDE STAIRS AND LANDINGS, SHALL BE
 DESIGNED TO MINIMIZE
 WATER ACCUMULATION ON THEIR SURFACES.
  
 7.2.2.3.4* TREAD AND LANDING SLOPE. THE TREAD AND
 LANDING SLOPE
 SHALL NOT EXCEED 1?4 IN./FT (21 MM/M) (A SLOPE OF 1 IN
 48).
  
 A.7.2.2.3.4 A SMALL DRAINAGE SLOPE FOR STAIR TREADS
 SUBJECT TO WETTING
 CAN IMPROVE TREAD SLIP RESISTANCE (SEE ALSO
 A.7.2.2.3.3.2). A CONSISTENT
 SLOPE TO A SIDE OF THE STAIR, WHERE DRAINAGE IS
 POSSIBLE, MIGHT BE PREFERABLE
 TO A FRONT-TO-BACK SLOPE OF THE TREADS. PROVIDING A
 PITCH OF 1?8 IN./FT
 TO 1?4 IN./FT (10 MM/M TO 21 MM/M) AIDS THE SHEDDING OF
 WATER FROM A
 NOMINALLY HORIZONTAL SURFACE.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 2) THERE IS AN INDICATION OF A STEEL WIRE MESH
 SURROUNDING THE STAIRWAY/WALKWAY
  
 7.2.2.6.6 OPENNESS. OUTSIDE STAIRS, OTHER THAN EXISTING
 OUTSIDE STAIRS,
 SHALL BE NOT LESS THAN 50 PERCENT OPEN ON ONE SIDE.
 OUTSIDE STAIRS SHALL
 BE ARRANGED TO RESTRICT THE ACCUMULATION OF SMOKE.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE
  
  
  
 3) THERE WAS LIMITED INFORMATION REGARDING LIGHTING.
  
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE
 WITH SECTION 7.8 FOR EVERY BUILDING AND STRUCTURE WHERE
 REQUIRED IN
 CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS
 SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS,
 AND PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT,
 EXIT DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS,
 RAMPS, ESCALATORS, WALKWAYS, AND PASSAGEWAYS LEADING TO
 A PUBLIC WAY
  
 7.8.1.3 THE FLOORS AND OTHER WALKING SURFACES WITHIN AN
 EXIT AND WITHIN
 THE PORTIONS OF THE EXIT ACCESS AND EXIT DISCHARGE
 DESIGNATED IN 7.8.1.1
 SHALL BE ILLUMINATED AS FOLLOWS:
 (1) DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW
 STAIRS SHALL BE AT LEAST 10 FT-CANDLE (108 LUX),
 MEASURED AT THE
 WALKING SURFACES.
 (2) THE MINIMUM ILLUMINATION FOR FLOORS AND OTHER
 WALKING SURFACES,
 OTHER THAN NEW STAIRS DURING CONDITIONS OF STAIR USE,
 SHALL BE TO
 VALUES OF AT LEAST 1 FT-CANDLE (10.8 LUX), MEASURED AT
 THE FLOOR.
 (3) IN ASSEMBLY OCCUPANCIES, THE ILLUMINATION OF THE
 WALKING SURFACES
 OF EXIT ACCESS SHALL BE AT LEAST 0.2 FT-CANDLE (2.2
 LUX) DURING PERIODS
 OF PERFORMANCES OR PROJECTIONS INVOLVING DIRECTED
 LIGHT.
 (4)* THE MINIMUM ILLUMINATION REQUIREMENTS SHALL NOT
 APPLY WHERE
 OPERATIONS OR PROCESSES REQUIRE LOW LIGHTING LEVELS
  
 7.8.2 SOURCES OF ILLUMINATION.
 7.8.2.1 ILLUMINATION OF MEANS OF EGRESS SHALL BE FROM A
 SOURCE CONSIDERED
 RELIABLE BY THE AUTHORITY HAVING JURISDICTION.
 7.8.2.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER
 TYPES OF PORTABLE LAMPS
 OR LANTERNS SHALL NOT BE USED FOR PRIMARY ILLUMINATION
 OF MEANS OF EGRESS.
 BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO
 BE USED AS AN EMERGENCY
 SOURCE TO THE EXTENT PERMITTED UNDER SECTION 7.9.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE
  
  
 4) THERE ARE NO INDICATIONS OF EXIT SIGNS
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-02 Cont ID  
Sent By rmcphers Date 2021-11-02 Time 16:19 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-13 Cont ID  
Sent By lmarchan Date 2021-10-13 Time 10:16 Rev Time 0.00
Received By lmarchan Date 2021-07-20 Time 14:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 16:43 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 16:43 Sent To  
Notes
2021-08-30 16:44:00NOT A BUILDING - NO AC SPACE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 11:23 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By lcrespo Date 2021-10-15 Time 11:20 Rev Time 0.00
Received By lcrespo Date 2021-10-15 Time 10:34 Sent To  
Notes
2021-10-15 11:21:1810/15/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By lcrespo Date 2021-08-13 Time 17:46 Rev Time 0.00
Received By lcrespo Date 2021-08-13 Time 17:46 Sent To  
Notes
2021-08-13 17:46:4508/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-PB 03;
 A. THE FLOOR DRAIN THAT RECEIVES THE SUMP PUMP LOOKS TO
 BE OUTSIDE AND THAT LINE IS LABEL SANITARY SEWER LINE.
 STORM WATER SHALL NOT BE DRAINED INTO SEWERS INTENDED
 FOR SEWAGE ONLY PER THE 2020 FBC SEC. 1101.3 PROHIBITED
 DRAINAGE.
  
 B. IF THE FLOOR DRAIN IS GOING TO BE MOVED INSIDE IT
 WILL REQUIRE A TRAP PRIMER PER THE 2020 FBC SEC.
 1002.4.1 TRAP SEAL PROTECTION.
  
 C. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 2. G-PB-103, UNDER APPLICABLE CODE IT STATES THE 6 TH
 EDITION PLEASE CORRECT TO THE 7 TH EDITION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-11-02 Cont ID  
Sent By rmcphers Date 2021-11-02 Time 16:15 Rev Time 0.00
Received By rmcphers Date 2021-11-02 Time 16:15 Sent To  
Notes
2021-11-02 16:16:17FABRIC AWNING

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 16:44 Sent To  
Notes
2021-08-30 16:44:50SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-02 Cont ID  
Sent By rmcphers Date 2021-11-02 Time 16:16 Rev Time 0.00
Received By rmcphers Date 2021-11-02 Time 16:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 11:23 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 11:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-10-13 Cont ID  
Sent By jroach Date 2021-10-13 Time 09:55 Rev Time 0.00
Received By jroach Date 2021-10-13 Time 09:55 Sent To  
Notes
2021-10-13 09:58:15THIS REVIEW IS LIMITED TO THE PEDESTRIAN BRIDGE ONLY!
  
 THE PROJECT IS SUBJECT TO ALL DEVELOPEMNT ORDER
 CONDITIONS, AS OULTINED IN RESOLUTION NO. 81-20, AS
 APPROVED BY THE CITY COMMISSION AND AS MAY BE
 AMENDED.1.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved