Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 09:08 Rev Time 0.00
Received By shill Date 2021-07-21 Time 09:08 Sent To  
Notes
2021-07-21 09:12:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DESIGN CRITERIA IS SHOWN ON DEMO, CONSTRUCTION PLAN,
 POSSIBLY OTHER PAGES, AS FBC 2017 AND FBC 2010.
 GOVERNING CODE IS FBC 2020, REVISE.
  
 FOR ITEMS #2 AND #3 - ALTHOUGH I KNOW THAT TEST REPORTS
 ARE AVAILABLE FOR THE PROPOSED INSTALLATION, THE TEST
 REPORTS SHOULD BE SUBMITTED. PLEASE PROVIDE.
  
 2. PROVIDE TEST REPORTS FOR THE FLOORING UNDERLAYMENT.
 THE UNDERLAYMENT MUST BE TESTED WITH WOOD GLUE DOWN
 FLOORING OR AN EQUIVALENCY ANALYSIS IS REQUIRED.
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 3. REVISE PLAN TO SHOW FLOORIG PROPOSED IN BATHROOM. IF
 THIS IS NOT WOOD GLUE DOWN FLOORING, THE TEST REPORTS
 REFERENCED IN ITEM 2 ARE REQUIRED FOR TILE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-29 Cont ID  
Sent By jleahy Date 2021-07-29 Time 07:41 Rev Time 0.00
Received By jleahy Date 2021-07-29 Time 07:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By pleduc Date 2021-08-24 Time   Rev Time 0.00
Received By pleduc Date 2021-08-24 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By pleduc Date 2021-07-20 Time   Rev Time 0.00
Received By pleduc Date 2021-07-20 Time 10:11 Sent To  
Notes
2021-07-20 10:24:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF COMPOSITE WOOD FLOORING AND
 NEW CARPET AND PAD. THE FLOOR UNDERLAYMENT
 SPECS/PRODUCT WAS PROVIDED BUT NO
 SPECIFICATIONS/PRODUCT SHEETS FOR THE WOOD, CARPET, PAD
 IS PROVIDED THAT INDICATE MEETING THE REQUIREMENTS PER
 NFPA.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
  
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 2) THERE ARE INDICATIONS OF REMOVED WALLS, NEW WALLS
 AND DOORS, CEILING WORK AND PAINTING.
  
 A REVIEW BY A CERTIFIED FIRE SPRINKLER CONTRACTOR IS
 REQUIRED TO ENSURE CODE COMPLIANT SPRINKLER HEAD
 COVERAGE.
  
 ANY WORK INVOLVING FIRE SPRINKLER SYSTEMT SHALL BE DONE
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 FIRE SPRINKLERS SHALL BE PROTECTED FROM PAINTING OR
 DAMAGE.
  
 THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3) THERE ARE INDICATIONS OF REMOVED WALLS, NEW WALLS
 AND DOORS, CEILING WORK AND PAINTING
  
 A REVIEW BY A CERTIFIED FIRE ALARM CONTRACTOR MAY BE
 REQUIRED TO ENSURE CODE COMPLIANCE.
  
 ANY WORK INVOLVING FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 FIRE ALARM EQUIPMENT SHALL BE PROTECTED FROM PAINTING
 OR DAMAGE.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT
 DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3A) WITH THE NOTED MODIFICATIONS THE LOCATION OF SMOKE
 ALARMS MAY REQUIRED REALIGNMENT/ADDITIONAL SA.
  
 SA ARE REQUIRED WITHIN EACH SLEEPING ROOM AND DIRECTLY
 OUTSIDE EACH SLEEPING.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-24 Cont ID  
Sent By lmarchan Date 2021-08-24 Time 10:42 Rev Time 0.00
Received By lmarchan Date 2021-08-20 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-29 Cont ID  
Sent By jleahy Date 2021-07-29 Time 07:41 Rev Time 0.00
Received By jleahy Date 2021-07-19 Time 11:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-07-21 Cont ID  
Sent By abelisle Date 2021-07-21 Time 08:18 Rev Time 0.00
Received By abelisle Date 2021-07-20 Time 08:34 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-09-09 09:56:15PRIVATE PROVIDER INSPECTIONS ONLY
 TEW & TAYLOR
  
 RICHARD GATRIGHT
 ASSISTANT BUILDING OFFICIAL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-22 Cont ID  
Sent By medwards Date 2021-07-22 Time 14:52 Rev Time 0.00
Received By medwards Date 2021-07-22 Time 14:51 Sent To  
Notes
2021-07-22 14:53:10ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME