Plan Review Stops For Permit 21070905
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 11:38 Rev Time 0.00
Received By lcrespo Date 2021-09-28 Time 11:29 Sent To  
Notes
2021-09-28 11:39:1009/28/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 10:57 Rev Time 0.00
Received By lcrespo Date 2021-08-26 Time 10:57 Sent To  
Notes
2021-08-26 10:57:2008/26/2 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A
 PERMITTED GAS SYSTEM. IS THIS A NEW INSTALLATION?
  
 2. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2020 FBC FG SEC. 402.4.1, 402.4.2.
  
 3. WOULD YOU PLEASE CLARIFY THE TYPE OF PIPE IN BLUE
 BEING USED FROM THE METER TO THE FIRST PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF
 THE DELIVERY GAS METER TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER THE 2020 FBC FG SEC.
 402.4.1.
  
 5. WOULD YOU PLEASE PROVIDE THE SIZING TABLE OR NOTE
 THE PLANS FOR THE BLUE PIPE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. WOULD YOU PLEASE SUBMIT THE MANUFACTURERES
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC.
 305.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC FG SECS. 402.2 AND 301.3.
  
 8. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC FG
 SEC 410.2?
  
 9. WOULD YOU PLEASE SHOW AND LABEL THE SHUT-OFF, AND
 THEY SHALL BE ACCESSIBLE WITHOUT MOVING THE EQUIPMENT
 PER THE 2020 FBC SEC. G2403 (202) GD, ACCESS.
  
 10. WOULD YOU PLEASE SHOW AND LABEL ALL DRIP LEGS ON
 EQUIPMENT EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD
 GRILLS PER THE 2020 FBC FG 408.2.
  
 11. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 12. ALL THE BTU LOADS OF EACH APPLIANCE ARE SHOWN.
 WOULD YOU PLEASE TOTAL BTU LOAD ON THE SYSTEM AND
 DISPLAY IT ON PLANS PER THE 2020 FBC RES. SEC. G2413.
  
 13. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER AND ALL APPLIANCES? THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 11:29 Rev Time 0.00
Received By lcrespo Date 2021-09-24 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 10:58 Rev Time 0.00
Received By lcrespo Date 2021-08-18 Time 11:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 11:29 Rev Time 0.00
Received By lcrespo Date 2021-09-28 Time 11:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 10:58 Rev Time 0.00
Received By lcrespo Date 2021-08-26 Time 10:58 Sent To  
Notes
***NONE***