Plan Review Details - Permit 21070853
Plan Review Stops For Permit 21070853
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-05 Cont ID  
Sent By pleduc Date 2021-08-05 Time   Rev Time 0.00
Received By pleduc Date 2021-08-05 Time 10:31 Sent To  
Notes
2021-08-05 10:35:56FIRE PROVISO:
  
 INSTALL TEST AND INSPECT PER NFPA 24
  
 DO NOT COVER OVER ANY JOINTS PRIOR TO FIRE INSPECTION
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By pleduc Date 2021-07-20 Time   Rev Time 0.00
Received By pleduc Date 2021-07-20 Time 12:51 Sent To  
Notes
2021-07-20 12:56:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PAGE 10 PF THE PRODUCT SUBMITTAL INDICATES DOWNTOWN
 DAVIE APARTMENT PRODUCT SUBMITTAL.
  
 PLEASE REVIEW AND ENSURE THAT THIS IS APPLICABLE TO THE
 401 DATURA SENIOR APT. WPB AS INDICATED ON PAGE 1.
  
 PROVIDE DETAILS OR CHANGES AS APPLICABLE.
  
  
 1A) THE ARE TWO FIRE HYDRANTS INDICATED; HOWEVER, THERE
 ARE NO SPEC SHEETS FOR THEM.
  
 PLEASE PROVIDE IF WITHIN THE SCOPE OF THIS INSTALL.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-15 Cont ID  
Sent By lcrespo Date 2021-09-15 Time 09:33 Rev Time 0.00
Received By lcrespo Date 2021-09-15 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-20 Cont ID  
Sent By lmarchan Date 2021-08-20 Time 11:10 Rev Time 0.00
Received By lmarchan Date 2021-08-04 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-30 Cont ID  
Sent By hmoser Date 2021-07-30 Time 10:33 Rev Time 0.00
Received By hmoser Date 2021-07-19 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2021-09-15 Cont ID  
Sent By hmoser Date 2021-09-15 Time 09:19 Rev Time 0.00
Received By hmoser Date 2021-09-15 Time 09:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-18 Cont ID  
Sent By hmoser Date 2021-08-18 Time 13:56 Rev Time 0.00
Received By hmoser Date 2021-08-18 Time 11:04 Sent To  
Notes
2021-08-18 13:49:58PLAN DENIED
 SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED
 FOR BACK FLOW ASSEMBLY
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By hmoser Date 2021-07-30 Time 10:33 Rev Time 0.00
Received By hmoser Date 2021-07-30 Time 09:36 Sent To  
Notes
2021-07-30 10:32:37PLAN DENIED
 SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED FOR
 BACK FLOW ASSEMBLY.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-09-15 Cont ID  
Sent By lcrespo Date 2021-09-15 Time 09:33 Rev Time 0.00
Received By lcrespo Date 2021-09-15 Time 09:33 Sent To  
Notes
2021-09-15 09:33:3809/15/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-20 Cont ID  
Sent By tklarge Date 2021-08-20 Time 10:57 Rev Time 0.00
Received By tklarge Date 2021-08-20 Time 10:42 Sent To  
Notes
2021-08-20 10:56:361) SUBMIT A SEPARATE PERMIT APPLICATION FOR THE FIRE
 BACKFLOW DEVICE OR REMOVE THE BACKFLOW SPECIFICATIONS
 FROM THIS SUBMITTAL AND SUBMIT A SEPARATE PERMIT
 APPLICATION AND THE SPECIFICATIONS FOR A STAND ALONE
 PERMIT. WPB AMEND. TO FBC SEC. 105.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By tklarge Date 2021-07-27 Time 06:25 Rev Time 0.00
Received By tklarge Date 2021-07-27 Time 06:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-30 Cont ID  
Sent By hmoser Date 2021-07-30 Time 10:33 Rev Time 0.00
Received By hmoser Date 2021-07-30 Time 10:33 Sent To  
Notes
***NONE***