Plan Review Details - Permit 21070798
Plan Review Stops For Permit 21070798
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-01-13 Cont ID  
Sent By lcrespo Date 2022-01-13 Time 12:48 Rev Time 0.00
Received By lcrespo Date 2022-01-13 Time 12:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-11-05 Cont ID  
Sent By lcrespo Date 2021-11-05 Time 08:19 Rev Time 0.00
Received By lcrespo Date 2021-11-05 Time 06:58 Sent To  
Notes
2021-11-05 08:17:4411/05/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE TIE-DOWN DRAWING BELONG TO A PERSON THAT DOES
 NOT HAVE A ENGINEER STAMP ON IT AND IS NOT ACCEPTABLE.
 THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005. VISIT
 HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO
 PROVIDE THIS DOCUMENT THAT IS ENGINEERED FOR THIS
 APPLICATION.
  
 2. ON THE ISOMETRIC THE PHYSICAL ADDRESS OF THE
 RESIDENCE MUST BE ON PLANS IN FULL, NUMBER, STREET,
 CITY, STATE, AND ZIP CODE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2.
  
 4. IF THE LP-GAS CONTAINERS OR SYSTEMS THAT ARE
 INSTALLED IS WITHIN 10 FT OF PUBLIC VEHICULAR
 THOROUGHFARES IT SHALL BE PROVIDED WITH A MEANS OF
 VEHICULAR BARRIER PROTECTION PER THE 2020 NFPA 58-17
 SEC. 6.8.1.2. DISTANCE IS NEEDED TO DETERMINE THIS.
  
 5. A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS
 TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD PER
 THE 2020 FBC FG SEC.G2408.1.
  
 6. WOULD YOU PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (BBQ
 GRILL, POOL HEATER AND FUTURE FIRE PIT) TO VERIFY
 COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC FG SECS. 402.2 AND 301.3 OR 2020 FBC RES. SEC.
 G2413.2 AND G2404.3.
  
 8. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 9. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
 10. WOULD YOU PLEASE LABEL DRIP LEG PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 11. WOULD YOU PLEASE LABEL HARD CAP FOR FUTURE FIRE PIT
 ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2401.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By abelisle Date 2021-10-25 Time 07:31 Rev Time 0.00
Received By abelisle Date 2021-10-25 Time 06:56 Sent To  
Notes
2021-10-25 07:05:461ST REVIEW FBC-2020 PLUMBING
 PERMIT-21070798
 10/25/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED
  
 1) CLEARLY, INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF
 REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE
 ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND,
 THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170
 MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2) THE SUBMITTED GAS PERMIT APPLICATION STATES INSTALL
 500 GALLON LP TANK AND GAS LINES TO POOL HEATER, FIRE
 PIT, AND FIRE BOWLS. PLEASE SHOW THE GAS LINES
 EXTENDING TO THE FIRE BOWLS.WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & A
 NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 4) THE SUBMITTED SHEET FOR THE LOCATION OF UNDERGROUND
 LP TANK INSTALLATION IS FOR ILLUSTRATIVE PURPOSES ONLY.
 THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY
 WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF
 THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE.
  
 5) SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY
 WITH NFPA 58 SEC. 6.6.6.1.
  
 6) THE GAS HAS BEEN SUBMITTED THAT IS DRAWN IN PENCIL
 ON THE SURVEY ARE ILLEGIBLE, AND DO NOT SHOW ALL OF THE
 GAS LINES TO BE INSTALLED. PLANS DONE IN PENCIL ARE
 UNACCEPTABLE AS THE DRAWING CAN BE MODIFIED/CHANGED.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1.4 QUALITY OF
 BUILDING PLANS.
  
 7) THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8) A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS
 TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD,
 2017 FBC FG SEC.G2408.1.
  
 9) SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRIL AND
 ALL GAS FIXTURES/ APPLIANCES TO BE INSTALLED. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
 10) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-08 Cont ID  
Sent By cthroop Date 2022-02-08 Time 15:12 Rev Time 0.00
Received By cthroop Date 2022-01-12 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-24 Cont ID  
Sent By lmarchan Date 2021-11-24 Time 08:24 Rev Time 0.00
Received By lmarchan Date 2021-11-03 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-26 Cont ID  
Sent By mpeterso Date 2021-10-26 Time 14:19 Rev Time 0.00
Received By mpeterso Date 2021-10-26 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2022-01-13 Cont ID  
Sent By lcrespo Date 2022-01-13 Time 12:49 Rev Time 0.00
Received By lcrespo Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-11-05 Cont ID  
Sent By lcrespo Date 2021-11-05 Time 08:18 Rev Time 0.00
Received By lcrespo Date 2021-11-05 Time 06:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-10-25 Cont ID  
Sent By abelisle Date 2021-10-25 Time 06:56 Rev Time 0.00
Received By abelisle Date 2021-10-25 Time 06:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-08 Cont ID  
Sent By cthroop Date 2022-02-08 Time 15:12 Rev Time 0.00
Received By cthroop Date 2022-02-08 Time 14:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-05 Cont ID  
Sent By lcrespo Date 2021-11-05 Time 07:09 Rev Time 0.00
Received By lcrespo Date 2021-11-05 Time 07:09 Sent To  
Notes
2021-11-05 07:19:52THE TIE-DOWN DRAWING BELONG TO A PERSON THAT DOES NOT
 HAVE A ENGINEER STAMP ON IT AND IS NOT ACCEPTABLE. THE
 ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS SHALL
 PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE DOCUMENT-
 FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.005. VISIT HTTPS://WWW.ENGINEERINGEXPRESS.COM/
 THEY MAY BE ABLE TO PROVIDE THIS DOCUMENT THAT IS
 ENGINEERED FOR THIS APPLICATION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-26 Cont ID  
Sent By mpeterso Date 2021-10-26 Time 14:19 Rev Time 0.00
Received By mpeterso Date 2021-10-26 Time 14:19 Sent To  
Notes
2021-10-26 14:19:34CONTRACTOR DRAWN PLANS

Review Stop Z ZONING
Rev No 3 Status P Date 2022-03-08 Cont ID  
Sent By asangele Date 2022-03-08 Time   Rev Time 0.00
Received By asangele Date 2022-03-08 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-02-07 Cont ID  
Sent By asangele Date 2022-02-07 Time 11:23 Rev Time 0.00
Received By asangele Date 2022-02-07 Time 11:23 Sent To  
Notes
2022-02-07 11:25:02FAILED: PLEASE REVIEW AND ADDRESS PREVIOUS ZONING
 COMMENTS.
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By awooten Date 2021-11-23 Time   Rev Time 0.00
Received By awooten Date 2021-11-23 Time   Sent To  
Notes
2021-11-23 15:19:11********************ZONING REVIEW FAILED************
  
 PROVIDE A SURVEY SHOWING THE FIRE PIT, TANK AND
 ASSOCIATED SETBACKS.
  
 FIRE PIT IS AN ACCESSORY STRUCTURE AND REQUIRES A
 MINIMUM 5 FOOT SETBACK.
  
 THE TANK IS MECHANICAL EQUIPMENT AND CANNOT GO FURTHER
 THAN FOUR FEET INTO THE SETBACK.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449