Plan Review Details - Permit 21070789
Plan Review Stops For Permit 21070789
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-27 Cont ID  
Sent By shill Date 2021-08-27 Time 18:05 Rev Time 0.00
Received By shill Date 2021-08-27 Time 18:05 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 11:07 Rev Time 0.00
Received By shill Date 2021-07-21 Time 11:07 Sent To  
Notes
2021-07-21 11:07:52PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-27 Cont ID  
Sent By shill Date 2021-08-27 Time 18:07 Rev Time 0.00
Received By shill Date 2021-08-27 Time 18:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By shill Date 2021-07-22 Time 11:44 Rev Time 0.00
Received By shill Date 2021-07-21 Time 11:09 Sent To  
Notes
2021-07-21 11:15:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FLOORING IS PROPOSED. REVISE PLAN TO INDICATE TYPE
 OF FLOORING AND PROVIDE TEST REPORTS FOR THE
 UNDERLAYMENT:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 2. IT APPEARS THAT WINDOW OR DOOR IS TO BE REPLACED,
 BUT THAT IS NOT CLEAR ON THE PLAN. WIND DESIGN
 PRESSURES WERE PROVIDED. DEMO PLAN SHOWS WINDOW/SLIDERS
 BEING REMOVED AND REPLACED. NO PRODUCT APPROVALS WERE
 SUBMITTED. FBC 107, CLARIFY SCOPE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-20 Cont ID  
Sent By jleahy Date 2021-07-20 Time 17:37 Rev Time 0.00
Received By jleahy Date 2021-07-20 Time 17:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By cwalker Date 2021-08-24 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-21 Cont ID  
Sent By cwalker Date 2021-07-21 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-27 Cont ID  
Sent By shill Date 2021-08-27 Time 18:08 Rev Time 0.00
Received By shill Date 2021-08-23 Time 09:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-22 Cont ID  
Sent By shill Date 2021-07-22 Time 11:45 Rev Time 0.00
Received By shill Date 2021-07-19 Time 09:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2021-08-24 Cont ID  
Sent By medwards Date 2021-08-24 Time 14:06 Rev Time 0.00
Received By medwards Date 2021-08-24 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By medwards Date 2021-07-22 Time 06:10 Rev Time 0.00
Received By medwards Date 2021-07-22 Time 06:05 Sent To  
Notes
2021-07-22 06:13:43THE NEW FLOOR LAYOUT SHOWS A HOOD ABOVE THE STOVE, THE
 DEMO LAYOUT SHOWS A MICROWAVE ABOVE THE STOVE. IS THE
 NEW HOOD VENTED TO THE EXTERIOR? WHAT IS THE CFM'S OF
 THIS HOOD? FBC M 505.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 16:42 Rev Time 0.00
Received By lcrespo Date 2021-08-26 Time 16:40 Sent To  
Notes
2021-08-26 16:42:3908/26/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By lcrespo Date 2021-07-21 Time 15:59 Rev Time 0.00
Received By lcrespo Date 2021-07-21 Time 15:49 Sent To  
Notes
2021-07-21 16:10:2607/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SHOWER CAN NOT DRIAN INTO AN EXSITING TRAP. IT
 MUST DRAIN AND BE VENTED SEPARATELY; EACH TRAP AND
 TRAPPED FIXTURE IS PERMITTED TO BE PROVIDED WITH AN
 INDIVIDUAL VENT. THE INDIVIDUAL VENT SHALL CONNECT TO
 THE FIXTURE DRAIN OF THE TRAP OR TRAPPED FIXTURE BEING
 VENTED PEE THE 2020 FBC P 910.1 INDIVIDUAL VENT
 PERMITTED.
  
 2. TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER PER THE 2020 FBC P 901.2.1.
  
 3. THE DISTANCE FROM TRAP TO VENT SHALL COMPLY WITH
 DEVELOPED LENGTH IN THE FIXTURE DRAIN FROM THE TRAP
 WEIR TO THE VENT FITTING ARE WITHIN THE REQUIREMENTS
 SET FORTH IN TABLE 909.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-23 Cont ID  
Sent By rmcdouga Date 2021-08-23 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2021-08-23 Time 10:01 Sent To  
Notes
2021-08-23 09:55:23ORIGINAL SIGNED AND SEALED DRAWINGS SENT TO STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-20 Cont ID  
Sent By medwards Date 2021-07-20 Time 16:26 Rev Time 0.00
Received By medwards Date 2021-07-20 Time 16:25 Sent To  
Notes
2021-07-20 16:27:31ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME