| 2021-07-23 07:34:58 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | REF. PRODUCT APPROVAL FOR THE FOLLOWING COMMENTS: |
| | |
| | 1. ANCHOR SCHEDULE SPECIFIES ANCHOR TYPES A, A1 AND C. |
| | ANCHOR SPACING TABLE SPECIFIES ANCHOR TYPES A, A1 AND |
| | B. PLEASE CLARIFY? |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | REF. SHUTTER SCHEDULE FOR THE FOLLOWING COMMENTS: |
| | |
| | 2. SHUTTER INSTALLATION SPECIFIES HORIZONTAL, ACCORDION |
| | SHUTTERS ARE INSTALLED VERTICAL. (BLADE ORIENTATION) |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | 3. ANCHOR TYPE. SEE NOTE 1, ANCHOR TYPES SHALL BE |
| | SPECIFIC. INCLUDE ALL ANCHOR TYPES USED. A, A1 AND C. |
| | |
| | 4. SEE SPECIFIC ANCHOR TYPE COLUMN. OPENING #1 SHOULD |
| | SPECIFY ANCHOR TYPE C FOR TOP CONNECTION (WOOD) AND |
| | ANCHOR TYPE A OR A1 FOR BOTTOM (CONCRETE) CONNECTION. |
| | ANCHOR TYPE MUST BE SPECIFIC. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |