Plan Review Details - Permit 21070675
Plan Review Stops For Permit 21070675
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-07-14 Cont ID  
Sent By cpuell Date 2021-07-14 Time 10:21 Rev Time 0.00
Received By cpuell Date 2021-07-14 Time 10:21 Sent To  
Notes
2021-07-14 10:21:557301 GEORGIA AVE GIVEN TO THIS BUILDING AS WELL AS
 BEING THE PRIMARY ADDRESS FOR THE PROJECT.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-07-19 Cont ID  
Sent By scwelter Date 2021-07-19 Time 11:26 Rev Time 0.00
Received By scwelter Date 2021-07-19 Time 11:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-11-03 Cont ID  
Sent By rmcphers Date 2021-11-03 Time 11:02 Rev Time 0.00
Received By rmcphers Date 2021-11-03 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-04 Cont ID  
Sent By rmcphers Date 2021-10-04 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2021-10-04 Time 13:23 Sent To  
Notes
2021-10-04 14:18:55NEW BUILDING - CLUBHOUSE AND PRO SHOP
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) IF YOU DON'T PROVIDE A MASTER ACCESSIBLE RESTROOM
 COMPONENT LOCATION DIMENSION DETAIL PLAN - YOU WILL
 NEED TO SHOW ALL COMPONENT LOCATION DIMENSIONS ON EACH
 RESTROOM FLOOR PLAN.
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR LOCATION DIMENSIONS FROM THE CENTER OF THE
 TOILET PER FBC 604.5.2
 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER LOCATION FROM THE FACE OF THE TIOLET TO COMPLY
 WITH FBC 604.7
 4) ACCESSIBLE RESTROOM - PLEASE NOTE THE MIRROR MAXIMUM
 HEIGHT FROM THE FLOOR TO THE "REFLECTIVE SURFACE" PER
 FBC 603.3 (PLEASE STATE TO THE REFLECTIVE SURFACE)
 5) ACCESSIBLE SHOWERS - PLEASE SHOW THE GRAB BAR
 LOCATION DIMENSIONS TO COMPLY WITH FBC 608.3.2 AND
 609.4
 6) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE BASEMENT -
 ROUTE, SLOPE, CROSS SLOPE ETC PER FBC 402.2 (PLEASE
 RESPOND TO THE EMAIL FROM ROBERT BROWN ON THIS SUBJECT)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By rmcphers Date 2021-08-19 Time 16:24 Rev Time 0.00
Received By rmcphers Date 2021-08-19 Time 07:46 Sent To  
Notes
2021-08-19 15:02:44NEW BUILDING - CLUBHOUSE AND PRO SHOP
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING S4.1.C SHOWS BUILDING WIND DESIGN RISK
 CATEGORY III WITH WIND SPEED OF 170MPH - WIND SPEED FOR
 A RISK CATEGORY III BUILDING SHOULD BE 180MPH PER FBC
 WPB SECTION 120.
 2) PLEASE PROVIDE A SOIL REPORT AS STATED IN THE NOTES
 ON DRAWING S4.1.C
 3) PLEASE SHOW THE TYPE OF WATER PROOFING FOR THE
 BASEMENT WALLS FBC 1805.2.2
 4) DRAWING A6.0.1 DETAIL 3 AND 1 - THE HAND RAIL
 EXTENSION AT THE BOTTOM SHALL CONTINUE TO SLOPE DOWN
 THE WIDTH OF THE STAIR TREAD FBC 1014.6
 5) DRAWING A6.0.2 DETAIL 1 HANDRAIL EXTENSIONS AT THE
 BOTTOM SHALL CONTINUE TO SLOPE DOWN FOR THE LENGTH OF
 THE STAIR TREAD. FBC 1014.6
 6) DRAWING A6.0.2 DETAIL 4 HANDRAIL EXTENSION SHALL
 EXTEND 12" PAST THE TOP RISER FBC 1014.6
 7) PLEASE SHOW THE ACCESSIBLE SEATING IN EACH OF THE
 DINING AREAS PER FBC 226.1
 8) PLEASE SHOW THE ACCESSIBLE INSIDE AND PATIO BAR
 SEATING COUNTER HEIGHT, CLEAR FLOOR SPACE, KNEE AND TOE
 CLEARANCE TO COMPLY WITH FBC 902
 9) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR LOCATION DIMENSIONS FROM THE CENTER OF THE
 TOILET PER FBC 604.5.2
 10) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER LOCATION FROM THE FACE OF THE TIOLET TO COMPLY
 WITH FBC 604.7
 11) ACCESSIBLE RESTROOM - PLEASE NOTE THE MIRROR
 MAXIMUM HEIGHT FROM THE FLOOR TO THE "REFLECTIVE
 SURFACE" PER FBC 603.3
 12) ACCESSIBLE SHOWERS - PLEASE SHOW THE GRAB BAR
 LOCATION DIMENSIONS TO COMPLY WITH FBC 608.3.2 AND
 609.4
 13) ACCESSIBLE SHOWERS - PLEASE SHOW THE DIMENSIONS FOR
 THE SEAT PER FBC 610.3
 14) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE BASEMENT -
 ROUTE, SLOPE, CROSS SLOPE ETC PER FBC 402.2
 15) PRODUCT APPROVAL PROVIDED FOR THE ROOF TILE -
 PLEASE CIRCLE THE TYPE OF TILE ATTACHMENT TO BE USED IN
 THE PRODUCT APPROVAL IF USING ADHESIVE PLEASE PROVIDE
 THE PRODUCT APPROVAL FOR THE ADHESIVE.
 16) CIVIL PLANS SHOW PROPERTY IN AN "X" AND "AE 14.8" -
 PLEASE CLEARLY SHOW THE FLOOD ZONE DELINEATION LINES -
 ARE ANY OF THE BUILDINGS IN THE "AE 14.8" FLOOD ZONE?
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2022-02-08 Cont ID  
Sent By jleahy Date 2022-02-08 Time 16:07 Rev Time 0.00
Received By jleahy Date 2022-02-08 Time 16:07 Sent To  
Notes
2022-02-08 16:07:56LIGHTNING PROTECTION SYSTEM.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-11-04 Cont ID  
Sent By jleahy Date 2021-11-04 Time 09:54 Rev Time 0.00
Received By jleahy Date 2021-11-04 Time 08:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-10-13 Cont ID  
Sent By jleahy Date 2021-10-13 Time 09:02 Rev Time 0.00
Received By jleahy Date 2021-10-13 Time 07:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-08-23 Cont ID  
Sent By jleahy Date 2021-08-23 Time 14:56 Rev Time 0.00
Received By jleahy Date 2021-08-23 Time 07:39 Sent To  
Notes
2021-08-23 15:04:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) THE FO;OWING SYSTEMS NEED SEPARATE PERMITS,
 GENERATOR, BDA, SITE LIGHTING, FIRE ALARM, LOW VOLTAGE
 WIRING.
  
 2) PAGE E4.02 GFCI PROTECTION FOR THE KITCHEN PREP
 AREAS.
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100
 AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL.
 (2) KITCHENS, (5) SINKS ? WHERE RECEPTACLES ARE
 INSTALLED WITHIN 1.8 M (6 FT) FROM THE TOP INSIDE EDGE
 OF THE BOWL OF THE SINK
 (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8
 M (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE
 SINK
 (6) INDOOR WET LOCATIONS.
  
 2) AIC RATING OF MAINS AND BRANCH BREAKERS REQUIRED PER
 110.9, 110.10
  
 3) TAMPER RESISTANT OUTLETS ARE REQUIRED PER 406.12
 125- AND 250-VOLT NONLOCKING-TYPE RECEPTACLES IN THE
 AREAS SPECIFIED IN 406.12(1) THROUGH (7) SHALL BE
 LISTED TAMPERRESISTANT
 RECEPTACLES.
 (1) DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND
 550.13
 (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS
 (3) CHILD CARE FACILITIES
 (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES
 (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE
 LIKE IN
 CLINICS, MEDICAL AND DENTAL OFFICES AND OUTPATIENT
 FACILITIES
 (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2
 TO
 INCLUDE PLACES OF WAITING TRANSPORTATION, GYMNASIUMS,
 SKATING RINKS, AND AUDITORIUMS
 (7) DORMITORIES

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-18 Cont ID  
Sent By jleahy Date 2021-08-18 Time 14:44 Rev Time 0.00
Received By jleahy Date 2021-08-18 Time 14:38 Sent To  
Notes
2021-08-18 14:47:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL PLANS INCLUDED TO REVIEW JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-10-05 Cont ID  
Sent By rrossano Date 2021-10-05 Time   Rev Time 0.00
Received By rrossano Date 2021-10-05 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By rrossano Date 2021-08-04 Time   Rev Time  
Received By rrossano Date 2021-08-04 Time   Sent To  
Notes
2021-08-04 13:48:15CURRENTLY UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-11-01 Cont ID  
Sent By   Date 2021-11-01 Time   Rev Time 0.00
Received By bdolan Date 2021-11-01 Time 12:24 Sent To  
Notes
2021-11-01 12:32:40REVISION 3 PASS FIRE.
  
 REFER TO PRIOR COMMENTS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-02 Cont ID  
Sent By   Date 2021-09-02 Time   Rev Time 0.00
Received By bdolan Date 2021-09-02 Time 11:39 Sent To  
Notes
2021-09-02 11:37:31THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR UNDER A SEPERATE PERMIT. A
 SEPARATE SHOP DRAWING COMPLIANT WITH NFPA 72 IS
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13 UNDER A SEPERATE PERMIT.
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY WORK ON THE SYSTEM.
  
 ALL WORK ON THE KITCHEN SUPPRESSION SYSTEM IS REQUIRED
 TO BE COMPLETED BY A CERTIFIED FCONTRACTOR AND SHALL
 COMPLY WITH NFPA 96 UNDER A SEPERATE PERMIT. SEPARATE
 SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED
 AND APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 WORK ON THE SYSTEM.
  
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-23 Cont ID  
Sent By   Date 2021-07-23 Time   Rev Time 0.00
Received By bdolan Date 2021-07-23 Time 15:51 Sent To  
Notes
2021-07-23 16:32:25THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 THERE ARE NO INDICATIONS OF A MONITORED FIRE SPRINKLER
 SYSTEM. THE LIFE SAFETY CODE REQUIRES THAT THE FIRE
 SPRINKLER SYSTEM BE MONITORED.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 ALL WORK ON THE FKITCHEN SUPPRESSION SYSTEM IS REQUIRED
 TO BE COMPLETED BY A CERTIFIED FCONTRACTOR AND SHALL
 COMPLY WITH NFPA 96. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
  
 PLEASE ADDRESS FIRE PROTECTION AND NOTIFICATION SYSTMS
 IN MASTER PERMIT ACCORDING TO FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-11-04 Cont ID  
Sent By ccole Date 2021-11-04 Time 16:43 Rev Time 0.00
Received By ccole Date 2021-11-04 Time 07:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-10-08 Cont ID  
Sent By ccole Date 2021-10-08 Time 13:18 Rev Time 0.00
Received By ccole Date 2021-10-06 Time 09:53 Sent To  
Notes
2021-10-08 13:20:142ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070675
 10/8/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES IN CAP
 LETTERS.
  
 1) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR THE WATER HEATERS AND DIRECT
 VENT SYSTEM, COOKING APPLIANCES, DRYERS, REGULATORS,
 SOLENOID VALVES- SECTION 305.1, 623.1, & 624.1 FBC FG,
 AND 107.2.1 WPB. BASED ON THE NARRATIVE RESPONSE PLEASE
 ADD THE ITEMS TO THE DEFERRED SUBMITALL LIST- SECTION
 107.3.4.1 WPB.
  
 4) FAILED. P4.01 & P7.05: THE GAS SUPPLY PIPE TO THE
 GENERATOR SHALL BE CONNECTED ON THE SUPPLY SIDE OF THE
 MAIN GAS SHUTOFF VALVE TO THE BUILDING AND BE MARKED AS
 SUPPLYING AN EMERGENCY GENERATOR- SECTION 7.9.7 NFPA
 110. THE DRAWINGS WERE NOT CORRECTED.
  
 6) FAILED. P4.01, P4.02 & P7.05: PLACE NOTES TO
 INDICATE ALL SHUTOFF VALVES INCLUDING THE SOLENOID
 VALVES WITH MANUAL RESETS ARE IN ACCESSIBLE LOCATIONS-
 SECTION 409.1.3 FBC FG. IT APPEARS THAT ONE AUTO VALVE
 WILL SERVE BOTH COOKING LINES WHICH APPEARS TO NOT MEET
 THE INTENT OF THE CODE. THERE ARE TWO HOOD EXHAUST
 SYSTEMS WHICH WILL TYPICALLY HAVE TWO SEPARATE FIRE
 SUPPRESSION SYSTEMS. CLARIFY IF THE INTENTION IS TO
 HAVE GAS SUPPLY SHUT DOWN TO BOTH COOKING LINES IF AN
 INCIDENT OCCURS AT ONLY ONE OF THE TWO COOKING LINES
 AND SUPPRESSION SYSTEMS. PLEASE ENSURE THAT THE FIRE
 SUPPRESSION SYSTEMS WILL CORRELATE TO THIS DESIGN-
 SECTION 107.2.1 WPB.
  
 7) FAILED. P4.01 & P7.05: PLACE A NOTE TO INDICATE THE
 SOLENOID VALVE SHOWN AT THE COOKING LINE MEETS
 COMPLIANCE WITH SECTION 10.4.1 NFPA 96: AN AUTOMATIC
 GAS SHUTOFF VALVE IS REQUIRED TO BE CONNECTED TO THE
 HOOD FIRE SUPPRESSION SYSTEM. PLEASE SEE COMMENT #6
 NOTES.
  
 8) FAILED. P4.01 & P7.05: SHOW THE LOCATION OF THE
 AUTOMATIC GAS VALVE FOR THE GAS LINE SERVICE COOKING
 APPLIANCES PK39, PK40 & PK41- SECTION 10.4.1 NFPA 96.
 PLEASE SEE COMMENT #6 NOTES.
  
 10) FAILED. P7.05: SHOW THE BRANCH LENGTHS AND CUT PIPE
 LENGTH MEASUREMENTS ON THE RISER INCLUDING BRANCH AND
 TOTAL LENGTHS FROM SECONDARY REGULATORS TO APPLIANCE
 AND EQUIPMENT OUTLETS- SECTIONS 402.4.1 & 402.4.2 FBC
 FG. A) THE MEASUREMENTS SHOWN ON THE RISER INDICATE THE
 5 PSI LINE FROM THE METER TO THE LOW PRESSURE REGULATOR
 FOR THE DRYERS HAS A TDL OF 103 FT. THE LENGTH TO THE
 LOW PRESSURE REGULATOR SERVING THE COOKING LINES IS 91
 FT. NOTE #1 ON THE PLAN INDICATES 202 FT. WHICH APPEARS
 INCORRECT.
  
 11) FAILED. P7.05: PROVIDE REGULATORS AT THE GAS DRYER
 AND GENERATOR LOCATIONS- SECTIONS 410.2 FBC FG.
 REGULATOR/NOTE NOT PROVIDED AT THE GENERATOR. PLEASE
 SEE PAGE 57- 60 OF THE ALLIANCE LAUNDRY SYSTEM
 INSTALLATION MANUAL AND PROVIDE THE INPUT PRESSURES
 RATING OF THE DRYERS AND VERIFY COMPLIANCE WITH THE
 PRESSURE DROP TABLES SHOWN.
  
 14) FAILED. P7.05 & P.1.1.1: BASED ON SHEET P1.1.1 IT
 APPEARS THE GAS PIPING TO THE GENERATOR MAY BE RUNNING
 UNDERGROUND. P1.1.1 SHOWS THE PIPING CROSSING IN FRONT
 OF THE ENTRY DOOR TO THE WATER ROOM. PLEASE PLACE NOTES
 ON THE RISER TO CLARIFY AND PROVIDE COMPLIANCE DETAILS
 FOR UNDERGROUND PIPING- SECTIONS 404.6 & 404.11 FBC FG.
 IF THE PIPING IS PE PLEASE PROVIDE INSTALLATION AND
 RISER DETAILS, AND THE PIPE SIZING TABLE TO BE USED-
 SECTION 402.4 FBC FG. THE METALLIC PIPING RUNNING
 UNDERGROUND SHALL BE PROTECTED AGAINST CORROSION-
 SECTIONS 404.11- 404.11.2 FBC FG. PLEASE INDICATE THE
 METHOD OF PROTECTION.
  
 15) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR
 WILL BE PROVIDED- SECTION 304.1 FBC FG. BASED ON THE
 NARRATIVE RESPONSE, REVIEW OF SHEET M6.0.1 INDICATES
 RTU 6 FOR THE KITCHEN HAS AN EXCESS SUPPLY OF 267 CFMS
 OF O/A AND THE CALCULATIONS INDICATE 435 CFMS IS
 REQUIRED. PLEASE NOTE THAT SECTION 304.9.3 REQUIRES THE
 SYSTEM SHALL PROVIDE THE SPECIFIED RATE IN ADDITION TO
 THE VENTILATION AIR RATE.
  
 16) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED DRYERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304.1 FBC FG. REFER TO SECTION
 304.6.2 FG FOR COMBUSTION AIR USING THE ONE
 PERMANENT-OPENING METHOD. THE OPENING IN THE DOOR DOES
 NOT MEET COMPLIANCE FOR SIZE AND LOCATION. THE OPENING
 SHALL BE WITHIN 12 INCHES TO THE TOP OF THE ENCLOSURE
 AND COMMUNICATING DIRECTLY WITH THE OUTDOORS. IN
 ADDTION, PLEASE REFER TO SECTION 404.3 FBC M WHICH
 REQUIRES ROOMS ADJACENT TO PARKING GARAGES TO BE
 MAINTAINED AT A POSITIVE PRESSURE. A) PLEASE SEE PAGE
 21 OF THE SUBMITTED ALLIANCE LAUNDRY SYSTEM SPECS AND
 INDICATE THE MODEL NUMBER OF THE DRYER. B) PLEASE SEE
 PAGE 52 OF THE ALLIANCE LAUNDRY SYSTEM SPECIFICATIONS
 AND SHOW COMPLIANCE FOR MAKEUP AIR OPENINGS.
  
 17) FAILED. PROVIDE A GAS DRYER EXHAUST DIAGRAM
 INDICATING THE TYPE AND SIZE OF EXHAUST DUCT, TOTAL RUN
 LENGTH AND TERMINATION LOCATION- SECTION 614.1 FBC FG.
 SHOW THE LOCATION OF REQUIRED CLEANOUTS- 614.3 AND
 PROVIDE TERMINATION CAP DETAILS- 614.4. PLEASE PROVIDE
 A SITE-SPECIFIC EXHAUST DUCT DIAGRAM BASED ON THE
 MANUFACTURER'S RECOMMENDATIONS SHOWN ON PAGES 52-56 OF
 THE SUBMITTED ALLIANCE LAUNDRY SYSTEMS SPECS. REFER TO
 PAGE 4- THE MAXIMUM ALLOWABLE LENGTH IS 14 FT AND WITH
 TWO 90 DEGREE ELBOWS OR EQUIVALENT FOR AN INDIVIDUAL
 VENT. SEE THE TABLE ON PAGE 54 FOR DUCT DIAMETERS AND
 ELBOW LENGTHS.
  
 18) FAILED. PLEASE NOTE THAT ALL REQUESTED
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR FIXTURES, APPLIANCES, AND EQUIPMENT MAY BE DEFERRED
 IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. ALL DEFERRED
 SUBMITTALS SHALL BE LISTED ON THE PLAN. PLEASE PROVIDE
 A LIST OF DEFERRED SUBMITTALS THAT INCLUDE THE WATER
 HEATERS, COOKING APPLIANCES, REGULATORS, SOLENOID VALVE
 ETC.
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By ccole Date 2021-08-20 Time 16:32 Rev Time 0.00
Received By ccole Date 2021-08-18 Time 12:57 Sent To  
Notes
2021-08-20 16:32:221ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070675
 8/20/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR THE WATER HEATERS AND DIRECT
 VENT SYSTEM, COOKING APPLIANCES, DRYERS, REGULATORS,
 SOLENOID VALVES- SECTION 305.1, 623.1, & 624.1 FBC FG,
 AND 107.2.1 WPB.
  
 2) PLACE A NOTE ON THE PLAN TO INDICATE THE GENERATOR
 WILL BE INSTALLED UNDER A SEPARATE PERMIT- SECTIONS
 105.1 & 107.2.1 WPB. THE CURRENT REVIEW UNDER THIS MAIN
 PERMIT IS LIMITED TO THE GAS PIPING RUN TO THE
 GENERATOR. SUBMITTAL OF A CUT SHEET SHOWING THE
 GENERATOR GAS LOADS AND INPUT PRESSURE WOULD BE HELPFUL
 FOR REVIEW OF GAS PIPE SIZING.
  
 3) SHEET P4.01: PROVIDE A KEYNOTE AT THE GAS LINE
 CONTINUATION TO THE GENERATOR AND INDICATE THE TYPE OF
 PIPING TO BE INSTALLED- SECTION 401.8 & 402.1 FBC FG
 AND SECTION 107.2.1 WPB. PROVIDE AN ENLARGED GAS PIPING
 LAYOUT DRAWING FOR THE AREA OF THE BUILDING SHOWING THE
 GAS PIPING RUN TO THE GENERATOR.
  
 4) P4.01 & P7.05: THE GAS SUPPLY PIPE TO THE GENERATOR
 SHALL BE CONNECTED ON THE SUPPLY SIDE OF THE MAIN GAS
 SHUTOFF VALVE TO THE BUILDING AND BE MARKED AS
 SUPPLYING AN EMERGENCY GENERATOR- SECTION 7.9.7 NFPA
 110.
  
 5) P4.01, P4.02 & P7.05: CLARIFY IF THE REGULATORS ARE
 EQUIPPED WITH LISTED AND LABELED VENT LIMITING DEVICES,
 OR PROVIDE VENTING DETAILS INCLUDING THE TYPES AND
 SIZES OF VENT PIPING, VENT PIPING RUNS AND DISCHARGE
 LOCATIONS- SECTIONS 410.3 & 410.3.1 FBC FG.
  
 6) P4.01, P4.02 & P7.05: PLACE NOTES TO INDICATE ALL
 SHUTOFF VALVES INCLUDING THE SOLENOID VALVES WITH
 MANUAL RESETS ARE IN ACCESSIBLE LOCATIONS- SECTION
 409.1.3 FBC FG.
  
 7) P4.01 & P7.05: PLACE A NOTE TO INDICATE THE SOLENOID
 VALVE SHOWN AT THE COOKING LINE MEETS COMPLIANCE WITH
 SECTION 10.4.1 NFPA 96: AN AUTOMATIC GAS SHUTOFF VALVE
 IS REQUIRED TO BE CONNECTED TO THE HOOD FIRE
 SUPPRESSION SYSTEM.
  
 8) P4.01 & P7.05: SHOW THE LOCATION OF THE AUTOMATIC
 GAS VALVE FOR THE GAS LINE SERVICE COOKING APPLIANCES
 PK39, PK40 & PK41- SECTION 10.4.1 NFPA 96.
  
 9) P4.01 & P7.05: PROVIDE A NOTE ON P4.01 TO SHOW THE
 LOCATION OF THE GAS PIPING DROP TO THE DRYERS IN THE
 BASEMENT AND PROVIDE A GAS PIPING FLOOR PLAN LAYOUT
 DRAWING- SECTIONS 107.2.1 & 107.3.5.1.5 WPB.
  
 10) P7.05: SHOW THE BRANCH LENGTHS AND CUT PIPE LENGTH
 MEASUREMENTS ON THE RISER INCLUDING BRANCH AND TOTAL
 LENGTHS FROM SECONDARY REGULATORS TO APPLIANCE AND
 EQUIPMENT OUTLETS- SECTIONS 402.4.1 & 402.4.2 FBC FG.
  
 11) P7.05: PROVIDE REGULATORS AT THE GAS DRYER AND
 GENERATOR LOCATIONS- SECTIONS 410.2 FBC FG.
  
 12) P7.05: SHOW THE LOCATIONS OF REQUIRED TEE FITTINGS
 AT REGULATOR LOCATIONS OR PROVIDE A NOTE TO ENSURE
 COMPLIANCE- SECTION 410.2(5,6) FBC FG.
  
 13) P7.05: SHOW THE LOCATIONS OF REQUIRED PIPE UNIONS
 AT REGULATOR LOCATIONS OR PROVIDE A NOTE TO ENSURE
 COMPLIANCE- SECTION 410.2(7) FBC FG.
  
 14) P7.05 & P.1.1.1: BASED ON SHEET P1.1.1 IT APPEARS
 THE GAS PIPING TO THE GENERATOR MAY BE RUNNING
 UNDERGROUND. P1.1.1 SHOWS THE PIPING CROSSING IN FRONT
 OF THE ENTRY DOOR TO THE WATER ROOM. PLEASE PLACE NOTES
 ON THE RISER TO CLARIFY AND PROVIDE COMPLIANCE DETAILS
 FOR UNDERGROUND PIPING- SECTIONS 404.6 & 404.11 FBC FG.
 IF THE PIPING IS PE PLEASE PROVIDE INSTALLATION AND
 RISER DETAILS, AND THE PIPE SIZING TABLE TO BE USED-
 SECTION 402.4 FBC FG.
  
 15) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR
 WILL BE PROVIDED- SECTION 304.1 FBC FG
  
 16) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED DRYERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304.1 FBC FG.
  
 17) PROVIDE A GAS DRYER EXHAUST DIAGRAM INDICATING THE
 TYPE AND SIZE OF EXHAUST DUCT, TOTAL RUN LENGTH AND
 TERMINATION LOCATION- SECTION 614.1 FBC FG. SHOW THE
 LOCATION OF REQUIRED CLEANOUTS- 614.3 AND PROVIDE
 TERMINATION CAP DETAILS- 614.4.
  
 18) PLEASE NOTE THAT ALL REQUESTED MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR FIXTURES,
 APPLIANCES, AND EQUIPMENT MAY BE DEFERRED IN ACCORDANCE
 WITH SECTION 107.3.4.1 WPB. ALL DEFERRED SUBMITTALS
 SHALL BE LISTED ON THE PLAN.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-11-29 Cont ID  
Sent By lmarchan Date 2021-11-29 Time 08:59 Rev Time 0.00
Received By lmarchan Date 2021-11-24 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-11-18 Time   Rev Time 0.00
Received By aoliver Date 2021-11-09 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-06 Cont ID  
Sent By lmarchan Date 2021-11-06 Time 17:39 Rev Time 0.00
Received By lmarchan Date 2021-10-26 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-13 Cont ID  
Sent By jleahy Date 2021-10-13 Time 09:02 Rev Time 0.00
Received By jleahy Date 2021-09-16 Time 12:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-03 Cont ID  
Sent By lmarchan Date 2021-09-03 Time 16:06 Rev Time 0.00
Received By lmarchan Date 2021-07-20 Time 15:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-02 Cont ID  
Sent By lmarchan Date 2021-12-02 Time 09:59 Rev Time 0.00
Received By lmarchan Date 2021-10-22 Time 09:34 Sent To  
Notes
2021-12-02 09:59:52RECEIPT MU-2021-051686 - $5255.67 PAID
2021-10-22 09:35:0810/22/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By rmcphers Date 2021-08-19 Time 16:24 Rev Time 0.00
Received By rmcphers Date 2021-08-19 Time 16:24 Sent To  
Notes
2021-08-19 16:25:46PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-11-01 Cont ID  
Sent By medwards Date 2021-11-01 Time 07:21 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 07:21 Sent To  
Notes
2021-11-01 07:24:01APPROVED WITH PRIVISO:
 VENTILATION REQUIREMENT SCHEDULE-AHU-2 SUPERMARKET,
 SALES SOULD BE THE BETTER FIT FOR THE USE OF THIS
 SPACE. THIS WOULD REQUIRE 253 CFM OF OUTDOOR AIR.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-09-28 Cont ID  
Sent By medwards Date 2021-09-28 Time 09:49 Rev Time 0.00
Received By medwards Date 2021-09-28 Time 09:49 Sent To  
Notes
2021-09-28 09:49:422ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21070675
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.0.1: IF THE OUTDOOR AIR CALCULATIONS ARE
 GOING TO BE BASED ON ASHRAE 62.1-2016 EDITION THE
 OCCUPANT COUNT FOR EACH USE OF SPACE MUST MATCH THE
 OCCUPANT COUNT BASED ON FBC 1004.5 SOME OF THE OUTDOOR
 AIR CALCULATIONS APPEAR TO BE LOW. PLEASE CHECK AGAIN
 AND MAKE SURE THAT YOU ARE MEETING THE MINIMUM REQUIRED
 OUTDOOR AIR CALCULATIONS. FBC M 403.3.1.1 AND TABLE
 403.3.1.1 EXAMPLE- PRIVATE DINING 2- 400 SQ FT; 400/15
 = 27 OCCUPANTS.
 27 X 7.5 = 202.5; 400 X .18 = 72; 202.5 + 72 = 275 CFM
 OF REQUIRED OUTDOOR AIR.
  
 2) PLEASE PROVIDE THE MODEL NUMBER OF THE GAS DRYERS AS
 THE LENGTH AND 90 DEGREE DUCTS ARE SPECIFIED IN THE
 INSTRUCTION MANUAL.
  
 3) PLEASE SHOW THE LOCATION OF THE REQUIRED LOUVERS FOR
 THE MAKEUP AIR FOR THE COMMERCIAL DRYERS ACCORDING TO
 THE MODELS OF THE DRYERS AND PAGE 52 OF THE INSTRUCTION
 MANUAL FOR THE DRYERS.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 06:05 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 06:05 Sent To  
Notes
2021-08-19 06:05:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070675
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1.0: PLEASE IDENTIFY WHICH IS DRYERS AND
 WHICH ARE WASHING MACHINES. PLEASE ALSO PROVIDE THE
 COMMERCIAL CLOTHES DRYER INSTALLATION INSTRUCTIONS FOR
 THE DRYER EXHAUST DUCT. FBC M 504.9
  
 2) PLEASE ADD STATEMENT TO DRAWINGS THAT THE
 REFRIGERATION WILL NOT BE REVIEWED ON THIS PERMIT. THE
 REFRIGERATION WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND DRAWINGS SUBMITTED.
  
 3) PLEASE ADD STATEMENT TO DRAWINGS THAT THE KITCHEN
 HOODS WILL NOT BE REVIEWED ON THIS PERMIT. THE KITCHEN
 HOODS WILL REQUIRE A SEPARATE PERMIT APPLICATION,
 REVIEW AND DRAWINGS SUBMITTED.
  
 4) SHEET M1.1.0: PLEASE PROVIDE THE EXHAUST
 CALCULATIONS FOR THE EXHAUST AIR FOR THE CART PARKING
 GARAGE. FBC M 404
  
 5) SHEET M1.1.1: PLEASE IDENTIFY THE RTU?S FOR EACH
 DUCT SYSTEM( EXAMPLE THE DUCT WORK CONDITIONING THE
 DINING AREA IS SERVED FROM WHICH RTU?) FBC 107.2.1
  
 6) SHEET M1.1.1: PLEASE SHOW THAT THE MEN?S BATHROOM
 EXHAUST INCLUDES THE URINALS. FBC M TABLE 403.3.1.1
 FOOTNOTE (E).
  
 7) SHEET M1.1.1: PLEASE LABEL EXHAUST FANS FOR EACH
 EXHAUST DUCT SERVED. FBC 107.2.1
  
 8) SHEET M1.1.2: PLEASE SHOW ROOF ACCESS TO WORK ON THE
 MECHANICAL UNITS. FBC 306.5
  
 9) PLEASE SHOW THE CONDENSATE DISPOSAL PIPING AND
 TERMINATION LOCATIONS. FBC M 307
  
 10) SHEET M1.1.1: PLEASE SHOW THAT THE MECHANICAL
 EQUIPMENT ON THE ROOF MEETS THE 10 FEET CLEARANCE OR
 HAS GUARDS. FBC M 304.11
  
 11) SHEET M6.0.1: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR ALL AREAS IN THIS NEW BUILDING BASED
 ON FBC 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-11-18 Cont ID  
Sent By ccole Date 2021-11-18 Time 08:54 Rev Time 0.00
Received By ccole Date 2021-11-18 Time 08:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-11-04 Cont ID  
Sent By ccole Date 2021-11-04 Time 16:43 Rev Time 0.00
Received By ccole Date 2021-11-04 Time 07:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-10-08 Cont ID  
Sent By ccole Date 2021-10-08 Time 10:07 Rev Time 0.00
Received By ccole Date 2021-10-06 Time 09:53 Sent To  
Notes
2021-10-08 10:07:282ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21070675
 10/8/2021
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES IN CAP
 LETTERS.
  
 3C) FAILED. ALS.1.0: DRINKING FOUNTAINS ARE REQUIRED
 FIXTURES FOR MERCANTILE, BUSINESS, AND STORAGE
 OCCUPANCIES. EXCEPTION 410.4 IS CALLED OUT IN THE TABLE
 HOWEVER SECTION 410.4 SUBSTITUTION OF DRINKING WATER IN
 A CONTAINER FREE OF CHARGE APPLIES ONLY TO THE
 RESTAURANT AREA. THE PLUMBING FIXTURE SCHEDULE
 INDICATES DRINKING FOUNTAIN EXCEPTION 410.4 ONLY FOR
 THE ASSEMBLY OCCUPANCIES. PLEASE PROVIDE THE REQUIRED
 FIXTURES PER THE COMMENT. BASED ON THE DRAWINGS
 SUBMITTED, IT APPEARS THAT THE PUBLIC CAN ACCESS THE
 SEPARATE MERCANTILE BUILDING (GOLF SHOP) WITHOUT HAVING
 TO ENTER THE RESTAURANT. HOW WOULD A PATRON OF THE GOLF
 SHOP THEN BE SUPPLIED WITH DRINKING WATER FROM THE
 RESTAURANT? THE SAME QUESTION APPLIES TO THE PUBLIC AND
 EMPLOYEES WHO ARE ACCESSING AND OCCUPYING THE LOWER
 LEVEL. THE CADDY LOUNGE AND THE BEVERAGE STATION ARE
 NOT CLASSIFIED AS RESTAURANTS.
  
 4) FAILED. A9.01: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. DEPTH DIMENSIONS NOT
 SHOWN
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 DIAMETER MEASUREMENT NOT PROVIDED.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 I) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 A FORWARD OR PARALLEL APPROACH TO THE SINK IN THE
 LOUNGE- 606.2. KNEE AND TOE CLEARANCES FOR FORWARD
 APPROACHES- SECTION 606.2. THE COMMENT WAS FOR THE
 CADDY LOUNG DETAIL SHOWN IN DETAIL 3. THE RESPONSE
 REFERS TO THE FOUNDER?S LOUNGE SINK.
 J) FAILED. LOUNGE SINK HEIGHT FROM THE FINISHED FLOOR
 TO THE RIM OF THE SINK- 606.3. NOTE- THE DRAWING SHOWS
 THE MEASUREMENT TO THE COUNTER. DETAIL 3 SHOWS
 MEASUREMENT TO THE COUNTER NOT THE SINK.
 K) FAILED. REACH RANGES AND OPERABLE PARTS FOR THE
 COFFEE MAKER- 308. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS TO VERY COMPLIANCE. A DEFERRED SUBMITTAL
 IS ACCEPTABLE. PLACE A NOTE THAT COMPLIANCE WITH
 SECTIONS 308 & 309 WILL BE MET.
  
 5) FAILED. A9.1.2: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE WATER CLOSET- SECTION 604.3. DIMENSIONS NOT
 PROVIDED.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE LAVATORY- SECTION 606.2. DIMENSIONS NOT PROVIDED.
 C) FAILED. TURNING SPACE DIAMETER- SECTION 304.3.
 DIAMETER MEASUREMENT NOT PROVIDED.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 F) FAILED. LOCATIONS OF THE WATER CLOSET FLUSH CONTROL-
 SECTION 604.6. NOT PROVIDED.
 G) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONT OF THE WATER CLOSET- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 H) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORY-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
  
 6) FAILED. A9.1.3: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE WATER CLOSET- SECTION 604.3. DIMENSIONS NOT
 PROVIDED. THE DOOR IS SWINGING INTO THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET. THE 30X48-INCH CLEAR FLOOR
 SPACE INSERTED IS NOT BEYOND THE ARC OF THE DOOR SWING-
 SECTION 603.2.3 (2).
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR
 THE LAVATORY- SECTION 606.2. DIMENSIONS NOT PROVIDED.
 C) FAILED. TURNING SPACE DIAMETER- SECTION 304.3.
 DIAMETER MEASUREMENT NOT PROVIDED.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 F) FAILED. LOCATIONS OF THE WATER CLOSET FLUSH CONTROL-
 SECTION 604.6. NOT PROVIDED.
 G) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONT OF THE WATER CLOSET- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 H) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORY-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
 I) FAILED. CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE
 SHOWER- SECTION 608.2.1. WIDTH MEASUREMENT NOT
 PROVIDED.
 J) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE ACCESSIBLE SHOWER- 608.2.1. DIMENSIONS NOT
 PROVIDED.
 K) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER 608.3 AND 608.3.1.
 REQUIRED OVERALL MINIMUM LENGTHS NOT INDICATED PER THE
 FIGURES.
 L) FAILED. SHOW THE LOCATION OF THE SHOWER CONTROL AND
 SPRAY IN ACCORDANCE WITH FIGURE 608.5.1. NOT PROVIDED-
 REFER TO THE FIGURE 608.5.1.
 N) FAILED PROVIDE THE ACCESSIBLE SHOWER SEAT HEIGHT AND
 MOUNTING DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
 NOT PROVIDED- REFER TO THE FIGURES ABOVE.
  
 7) FAILED. A9.1.5, A9.1.6 & A9.1.7: MISSING ACCESSIBLE
 PLUMBING FIXTURE DETAILS PER FBC ACC: SEE NOTES BELOW.
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. NOT
 PROVIDED.
 E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SECTION 604.4. NOT PROVIDED.
 H) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
 M) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- 608.3.2. GRAB BAR
 LOCATIONS AND POSITIONING DEPEND ON WHETHER A SEAT IS
 BEING INSTALLED. THE FLOOR PLAN DOES NOT SHOW A SEAT IN
 THE SHOWER, HOWEVER DETAIL 5 SHOWS A SEAT.
 N) FAILED. LOCATION OF THE SHOWER CONTROL AND SPRAY-
 608.5.2. SHOWER CONTROL LOCATIONS AND POSITIONING
 DEPEND ON WHETHER A SEAT IS BEING INSTALLED. THE FLOOR
 PLAN DOES NOT SHOW A SEAT IN THE SHOWER, HOWEVER DETAIL
 5 SHOWS A SEAT.
  
 9) FAILED. A9.1.8 & A9.1.9: MISSING ACCESSIBLE PLUMBING
 FIXTURE DETAILS PER FBC ACC: SEE NOTES BELOW.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. NOT PROVIDED.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE LAVATORIES- SECTION 606.2. NOT PROVIDED. IF USING A
 TYPICAL FIGURE PLEASE PROVIDE IT ON THE PLAN OR
 REFERENCE THE SHEET IT IS ON.
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. NOT
 PROVIDED.
 E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SECTION 604.4.NOT PROVIDED.
 F) FAILED. HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER
 SURFACE FROM THE FINISHED FLOOR- SECTION 606.3. NOT
 PROVIDED. IF USING A TYPICAL FIGURE PLEASE PROVIDE IT
 ON THE PLAN OR REFERENCE THE SHEET IT IS ON.
 G) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SECTION 603.3
 H) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. REQUIRED OVERALL MINIMUM
 LENGTHS NOT INDICATED PER THE FIGURES.
 I) FAILED. LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS
 - SECTION 604.6. NOT PROVIDED.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. NOT PROVIDED.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED. IF USING A TYPICAL FIGURE
 PLEASE PROVIDE IT ON THE PLAN OR REFERENCE THE SHEET IT
 IS ON.
 L) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE ACCESSIBLE SHOWER- 608.2.2.1. NOT PROVIDED.
 N) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- 608.3.2. GRAB BAR
 LOCATIONS AND POSITIONING DEPEND ON WHETHER A SEAT IS
 BEING INSTALLED. THE FLOOR PLAN DOES NOT SHOW A SEAT IN
 THE SHOWER, HOWEVER DETAIL 8 SHOWS A SEAT.
 O) FAILED. LOCATION OF THE SHOWER CONTROL AND SPRAY-
 608.5.2. SHOWER CONTROL LOCATIONS AND POSITIONING
 DEPEND ON WHETHER A SEAT IS BEING INSTALLED. THE FLOOR
 PLAN DOES NOT SHOW A SEAT IN THE SHOWER, HOWEVER DETAIL
 8 SHOWS A SEAT.
 P) FAILED. ACCESSIBLE URINAL- SHOW THE LOCATION(S),
 PROVIDE THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS,
 PROVIDE THE RIM HEIGHT FROM THE F.F., AND THE URINAL
 DEPTH- SECTIONS 213.3 & 605.2 FBC ACC. NOT PROVIDED.
  
 10) FAILED. A9.1.8: SHOW THE DEPTH MEASUREMENTS OF THE
 STANDARD WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC
 P. NOT PROVIDED.
  
 11) FAILED. A9.1.5 & A9.1.8: IN ACCORDANCE WITH SECTION
 213.3.1 FBC ACC, AMBULATORY TOILET COMPARTMENT STALLS
 ARE REQUIRED FOR THE MEN'S (138) AND WOMEN'S (148)
 BATHROOMS. PLEASE SEE SECTIONS 604.8.2- 604.8.2.3 AND
 REVISE THE PLANS AND DETAILS ACCORDINGLY. AMBULATORY
 COMPARTMENT FOR MEN NOT SHOWN ON A9.18. NO GRAB BAR
 DETAILS PROVIDED ON EITHER SHEET- SEE SECTIONS
 604.8.2.3 & 604.5.1 FBC ACC.
  
 12) FAILED P1.1.0 SAND/OIL INTERCEPTOR (SOI-1): A)
 FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS- SECTION 1003.4.2 FBC P.
 PLEASE ADD THE SOI-1 TO THE SEPARATE PERMIT LIST ON
 SHEET G1.0.1. FAILED. C) PROVIDE SIZING CALCULATIONS IN
 ACCORDANCE WITH SECTION 1003.4.2.1 OR PER
 MANUFACTURER'S SPECIFICATIONS. IT APPEARS THAT THE
 SO1-1 CALCULATIONS HAVE BEEN MISLABELED AS LINT
 INTERCEPTOR CALCULATION. IF THAT IS THE CASE, IT ALSO
 APPEARS THAT THE OS-75 AT 93 GALLONS CAPACITY IS
 UNDERSIZED PER THE 110 GALLONS REQUIRED BY THE
 CALCULATIONS.
  
 13) FAILED. P1.1.0 LINT TRAP (LI-1): A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1003.6 FBC P. SEE COMMENT #12
 REGARDING THE LINT INTERCEPTOR SIZING CALCULATIONS.
 PLEASE CLARIFY HOW THE LINT INTERCEPTOR WAS SIZED.
  
 14) FAILED. P1.1.0 STORM SUMP PUMP: A) FAILED. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1113.1 FBC P. PLEASE ADD THE SUMP
 PUMP COMPONENTS TO THE DEFERRED SUBMITTALS LIST ON
 G1.01. REVIEW COMMENT #16 NOTES BELOW.
  
 16) FAILED. P1.1.0, C2 & C2.1: SHOW THE DRAINAGE PIPING
 CONNECTIONS FOR THE TRENCH DRAINS (TD-1) LOCATED AT THE
 BAY DOORS. IF CONNECTING TO THE CITY STORM DRAINAGE
 SYSTEM, REFER TO SEC. 90-203 WPB CODE OF ORDINANCES AND
 VERIFY THAT THE DRAINS WILL CONVEY ONLY STORM WATER
 INTO THE SYSTEM. PLEASE NOTE THAT IT IS UNLAWFUL FOR
 ANY OTHER SUBSTANCES TO DISCHARGE INTO THE SYSTEM
 UNLESS MEETING ONE OF THE EXCEPTIONS UNDER SEC. 90- 205
 WPB. PLEASE REFER TO SEC. 90-203-205 WPB CODE OF
 ORDINANCES- THE PLAN SHOWS TRENCH DRAINS FROM THE
 GARAGE DRAINING DIRECTLY INTO THE SUMP PIT, BUT NEARBY
 FLOOR DRAINS DRAINING INTO THE OIL SEPARATOR. PLEASE
 CLARIFY WHY THE DRAINAGE FROM THE FLOOR DRAINS WOULD
 CONTAIN SUBSTANCES THAT REQUIRE SEPARATION AND THE
 TRENCH DRAINS WOULD NOT. THE EOR SHALL VERIFY THAT THE
 DISCHARGE FROM THE SUMP INTO THE STORM DRAIN SYSTEM
 WILL CONTAIN ONLY STORMWATER AND NO OTHER SUBSTANCES
 SUCH AS OIL, GREASE, OR CHEMICALS. PLEASE NOTE THAT AN
 OIL SEPARATOR MAY BE REQUIRED- SEC. 1003.4 FBC P.
  
 17) FAILED- SEE NOTES. P1.1.0 SANITARY BACKWATER VALVE:
 A) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATIONS INSTRUCTIONS- SECTIONS 715.2- 715.4. NOT
 PROVIDED. PLEASE ADD THE VALVE TO THE DEFERRED
 SUBMITTALS LIST ON G1.01.B) FAILED. PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7. NOT PROVIDED.
  
 19) FAILED. P1.1.1 GREASE INTERCEPTOR. C) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB. NOT PROVIDED. D) FAILED. PLEASE
 NOTE ONLY FIXTURES DISCHARGING GREASE LADEN WASTE WATER
 SHALL FLOW INTO THE GREASE INTERCEPTOR. CLEAR WATER
 WASTE FROM HAND SINKS, ICE MACHINES ETC. SHALL NOT
 DRAIN INTO THE SYSTEM- SECTION 1003.3.1 FBC P. THE
 CALCULATIONS ON P5.02 SHOW BAR SINKS. PLEASE CLARIFY
 THE LOCATIONS OF BAR SINKS ON THE PLANS AND WHAT THEIR
 USES ARE- THEY ARE NOT SPECIFIED IN THE SCHEDULE.
  
 20) FAILED. P1.1.1 SOLIDS INTERCEPTOR S1-1: A) FAILED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED. THE
 RESPONSE NARRATIVE INDICATES THE S1-1 SPECS LOCATED AT
 DETAIL 2 ON SHEET P5.02 HOWEVER DETAIL 2 IS THE STORM
 SUMP PUMP DETAIL. B) FAILED. PROVIDE SIZING
 CALCULATIONS- 1003.3.4. NOT PROVIDED. C) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB.
  
 21) FAILED. P1.1.1 SAMPLING PORT (SP-1): A) FAILED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED-
 PLEASE ADD TO THE DEFERRED SUBMITTALS LIST. B) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB. NOT PROVIDED- PLEASE ADD TO THE
 DEFERRED SUBMITTALS LIST.
  
 22) FAILED. P1.1.1: PROVIDE NOTES AT THE TERMINATION
 LOCATIONS OF THE GREASE WASTE AND SANITARY SEWER LINES
 OR SHOW THE POINTS OF CONNECTIONS TO THE SEWER LINE-
 SECTION 107.2.1 WPB. SHEET C3.1 SHOWS A SEWER
 CONNECTION AT THE LIFT STATION FOR THE STORM DRAINAGE-
 PLEASE CORRECT.
  
 23) FAILED. P1.1.1 STORM WATER BACKWATER VALVE: A)
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7. NOT PROVIDED. PLEASE ADD TO THE DEFERRED
 SUBMITTALS LIST.
  
 24) FAILED. P2.01: PROVIDE ROOF DRAINAGE PLANS AND A
 STORM DRAIN ISOMETRIC DRAWING- SECTION 107.3.5.1.3 FBC
 P. THE NARRATIVE INDICATES THE ISOMETRIC DRAWING IS ON
 P.7.06 HOWEVER THE DRAWING WAS NOT UPLOADED FOR REVIEW.
 PLEASE SHOW THE LOCATIONS OF THE OVERFLOW SCUPPERS ON
 SHEET P.2.01.
  
 26) FAILED. P4.01, P7.02: THE GW FIXTURE DRAIN FROM THE
 MOP SINK IS SHOWN TO BE CONNECTING TO THE SANITARY
 DRAIN- SECTION 1003.3.1 FBC P. THE GREASE WASTE
 ISOMETRIC IS MISSING FROM THE DRAWINGS.
  
 27) FAILED. P4.01, P4.02, P7.01, P7.02, K7, K8, & K9:
 CLEAR WATER WASTE DRAINAGE FROM HAND SINKS AND WASTE
 RECEPTORS AT ICE BIN AND ICE MAKER LOCATIONS ARE SHOWN
 DISCHARGING INTO THE GW LINE WHICH IS PROHIBITED-
 SECTION 1003.3.1 FBC P. THE GREASE WASTE ISOMETRIC IS
 MISSING FROM THE DRAWINGS.
  
 28) FAILED. P4.01 & K7: CONDENSATE FROM THE WALK-IN BOX
 EVAPORATORS SHALL NOT DRAIN INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. REFER TO
 SHEETS P.401 & P.702 AND CLARIFY HOW THE CONDENSATE
 WILL BE DISPOSED OF. SHOW THE CONDENSATE LINES FROM THE
 EVAPORATORS AND DISCHARGE LOCATIONS. IT APPEARS THAT
 HUB DRAINS CANNOT BE USED BECAUSE THEY MAY BE CONVEYING
 OTHER WASTE AND NOT JUST CONDENSATE. PLEASE NOTWE THAT
 P.4021 SHOWS THE HUB DRAINS CONNECTING TO THE STORM,
 AND P.702 SHOWS CONNECTION TO THE SANITARY.
  
 29) FAILED. P4.01 & P4.02: INDICATE TEMPERED WATER IS
 BEING SUPPLIED TO LAVATORIES L-1, L-2, & L-3- SECTION
 419.5 FBC P. ACCORDING TO SECTION 607.1.2 FBC P.
 TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070.
 PLEASE ADD THE COMPLIANCE NOTE IN THE SCHEDYULE AND ADD
 THE FAUCETS TO THE DEFERRED SUBMITTAL LIST.
  
 32) FAILED. P7.02: TD-2 AND SH-2 IN THE MEN'S BATHROOM
 DO NOT APPEAR TO BE VENTED PROPERLY. PLEASE CLARIFY HOW
 THE FIXTURES ARE BEING VENTED- SECTION 901.2.1 FBC P.
 A) RELOCATE THE 2-INCH VENT FOR BETWEEN THE TWO L2
 DRAIN CONNECTIONS- SECTION 912.2.1 FBC P. B) PROVIDE AN
 INDIVIDAUL VENT FOR SH-2- SECTION 910.1 FBC P. C)
 RELOCATE THE SH-1 SHOWER VENT TO A LOCATION BETWEEN THE
 TWO MOST UPSTREM FIXTURES CONNECTING TO THE HORIZONTAL
 BRANCH- SECTION 912.2.1 FBC P.
  
 33) FAILED. P7.01 & P7.02: INDICATE HOW TRAP SEAL
 PROTECTION WILL BE PROVIDED FOR FLOOR DRAINS AND OTHER
 TRAP SEALS SUBJECT TO EVAPORATION WILL BE PROTECTED-
 SECTION 1002.4.1 FBC P. THE CHIEF PLUMBING INSPECTOR
 FOR THE CITY OF WPB BUILDING DEPT. HAS PROHIBITED THE
 USE OF BARRIER-TYPE TRAP SEALS IN AREAS SUCH AS
 COMMERCAIL KITCHENS AND OTHER FLOOR AREAS WHERE
 EXCESSIVE GREASE OR OTHER SUBSTANCES AND DEBRIS WILL
 CAUSE THE TRAP TO FAIL. PLEASE PROVIDE AN ACCEPTABLE
 MEANS IN THE KITCHEN, BASEMENT AND LAUNDRY AREAS.
  
 35) FAILED. P7.03 & P7.04: PROVIDE A SHUTOFF VALVE AT
 THE TOP OF THE COLD WATER DOWN FEED PIPE FROM FIRST TO
 BASEMENT FLOOR- SECTION 606.1 (5) FBC P. P.704- SHUT
 OFF NOT SHOWN FOR 2-1/2-INCH CW LINE TO BASEMENT.
  
 38) FAILED. P.7.04: PROVIDE AN ENLARGED WATER
 FILTRATION PIPING DETAIL SHOWING SUPPLY CONNECTION TO
 THE FILTER, AND SUPPLY LINES TO FIXTURES AND EQUIPMENT
 REQUIRING FILTRATION. PLEASE NOTE THAT BACKFLOW
 PREVENTERS ARE REQUIRED FOR THE WATER SUPPLY LINES IN
 AND OUT OF THE FILTER- SECTION 608.3 FBC P. THE
 REQUESTED ENLARGED FILTER PIPING PLAN NOT PROVIDED. THE
 ISOMETRIC DRAWING APPEARS TO SHOW THE LOCATION FO THE
 FILTER BUT NO SUPPLY LINES TO EQUIPMENT.
  
 39) FAILED. PLEASE NOTE THAT ALL REQUESTED
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR FIXTURES, APPLIANCES, AND EQUIPMENT MAY BE DEFERRED
 IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. PLEASE NOTE
 THAT ALL DEFERRED SUBMITTALS SHALL BE LISTED ON THE
 PLAN. SEE PLAN REVIEW NOTES AND MODUIFY THE DEFERRED
 SUBMITTALS LIST.
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 NEW COMMENT: TO HELP EXPEDITE THE REVIEW PROCESS,
 PLEASE CORRELATE THE PLUMBING FIXTURES AND EQUIPMENT
 SHOWN ON THE DRAWING WITH THE KITCHEN AND PLUMBING
 EQUIPMENT SCHEDULES. THE DRAWINGS ARE USING THE LETTER
 (P) HOWEVER THE SCHEDULES USE (K) AND IT APPEARS SOME
 OF THE NUMBERS ARE NOT MARCHING BETWEEN THE PLANS AND
 SCHEDULE FOR EXAMPLE- (PS2).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By ccole Date 2021-08-20 Time 08:59 Rev Time 0.00
Received By ccole Date 2021-08-18 Time 10:26 Sent To  
Notes
2021-08-20 09:00:011ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21070675
 8/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE INSTALLATION OF THE , GREASE AND SOLIDS
 INTERCEPTORS, LIFT STATION, UNDERGROUND FIRE LINE,
 POTABLE WATER SERVICE BACKFLOW PREVENTER, IRRIGATION
 SERVICE BACKFLOW PREVENTER, FIRE LINE BACKFLOW
 PREVENTER, FIRE SPRINKLER, AND GAS-FIRED GENERATOR-
 SECTIONS 105.1 & 107.2.1 WPB.
  
 2) PROVIDE IRRIGATION PLANS OR INDICATE THE PLANS WILL
 BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION-
 SECTION 105.1 & 107.2.1 WPB.
  
 3) SHEET ALS.1.0 CODE DATA & PLUMBING FIXTURE REQ'S:
 THE LIFE SAFETY OCCUPANT LOAD AND FIXTURE CALCULATIONS
 ARE LACKING THE SQUARE FOOTAGES AND OCCUPANT LOADS OF
 EACH OF THE BUILDING AREAS (A2, M, B, & S). PLEASE NOTE
 THAT CODE SECTION 506.1.3 FBC B WHICH IS CALLED OUT IN
 THE DATA PERTAINS TO ALLOWABLE AREA FOR THE BUILDING
 AND DOES NOT EXCLUDE PLUMBING FIXTURE CALCULATIONS FOR
 THE BASEMENT AREAS. A COMPLETE REVIEW OF THE PLUMBING
 CANNOT BE COMPLETELY WITHOUT ACCURATE OCCUPANCY LOAD
 CALCULATIONS FOR EACH AREA OF THE BASEMENT AND GROUND
 FLOOR. THE RESTROOMS SHALL BE LABELED AS EITHER MALE OR
 FEMALE- TABLE 403.1 & SECTION 403.2 FBC P.THE PLANS
 SHOW FOUR RESTROOMS (TWO IN THE BASEMENT AND TWO ON THE
 FIRST FLOOR) THAT ARE NOT LABELED- SEE SECTION 403.1.2.
 A) ALS.1.0: REFER TO SECTION 403.1.4 FBC P AND INCLUDE
 THE OUTDOOR SEATING WITH THE CALCULATIONS.
  
 B) ALS.1.0: REFER TO SECTION 403.3 FBC P AND DESIGNATE
 THE REQUIRED EMPLOYEE TOILET FACILITIES AS EITHER
 SEPARATE OR COMBINED EMPLOYEE AND PUBLIC TOILET
 FACILITIES. PLEASE PROVIDE A BREAKDOWN CALCULATION FOR
 EMPLOYEES THAT INCLUDES THE GOLF CART GARAGE, CADDY
 LOUNGE, BEVERAGE AREA ETC.
  
 C) ALS.1.0: DRINKING FOUNTAINS ARE REQUIRED FIXTURES
 FOR MERCANTILE, BUSINESS, AND STORAGE OCCUPANCIES.
 EXCEPTION 410.4 IS CALLED OUT IN THE TABLE HOWEVER
 SECTION 410.4 SUBSTITUTION OF DRINKING WATER IN A
 CONTAINER FREE OF CHARGE APPLIES ONLY TO THE RESTAURANT
 AREA.
  
 4) A9.01: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 I) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR A
 FORWARD OR PARALLEL APPROACH TO THE SINK IN THE LOUNGE-
 606.2. KNEE AND TOE CLEARANCES FOR FORWARD APPROACHES-
 SECTION 606.2
 J) LOUNGE SINK HEIGHT FROM THE FINISHED FLOOR TO THE
 RIM OF THE SINK- 606.3. NOTE- THE DRAWING SHOWS THE
 MEASUREMENT TO THE COUNTER.
 K) REACH RANGES AND OPERABLE PARTS FOR THE COFFEE
 MAKER- 308. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS
 TO VERY COMPLIANCE.
  
 5) A9.1.2: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 G) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2
  
 6) A9.1.3: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOORS- SECTION 604.4.
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 G) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
 I) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE SHOWER-
 SECTION 608.2.1
 J) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWER- 608.2.1.
 K) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER 608.3 AND 608.3.1
 L) SHOW THE LOCATION OF THE SHOWER CONTROL AND SPRAY IN
 ACCORDANCE WITH FIGURE 608.5.1.
 M) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
 N) PROVIDE THE ACCESSIBLE SHOWER SEAT HEIGHT AND
 MOUNTING DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
  
 7) A9.1.5, A9.1.6 & A9.1.7: MISSING ACCESSIBLE PLUMBING
 FIXTURE DETAILS PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.LI) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE
 SHOWERS- SECTION 608.2.2.
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWER- 608.2.2.1.
 M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- 608.3.2.
 N) LOCATION OF THE SHOWER CONTROL AND SPRAY- 608.5.2
 O) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
  
 8) A9.1.5: SHOW THE DEPTH MEASUREMENTS OF THE STANDARD
 WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC P.
  
 9) A9.1.8 & A9.1.9: MISSING ACCESSIBLE PLUMBING FIXTURE
 DETAILS PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
 I) CLEAR INSIDE DIMENSIONS FOR THE ACCESSIBLE SHOWERS-
 SECTION 608.2.2.
 J) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWER- 608.2.2.1.
 K) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- 608.3.2.
 L) LOCATION OF THE SHOWER CONTROL AND SPRAY- 608.5.2
 M) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
 N) ACCESSIBLE URINAL- SHOW THE LOCATION(S), PROVIDE THE
 CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS, PROVIDE THE
 RIM HEIGHT FROM THE F.F., AND THE URINAL DEPTH-
 SECTIONS 213.3 & 605.2 FBC ACC.
  
 10) A9.1.8: SHOW THE DEPTH MEASUREMENTS OF THE STANDARD
 WATER CLOSET COMPARTMENTS- SECTION 405.3.1 FBC P.
  
 11) A9.1.5 & A9.1.8: IN ACCORDANCE WITH SECTION 213.3.1
 FBC ACC, AMBULATORY TOILET COMPARTMENT STALLS ARE
 REQUIRED FOR THE MEN'S (138) AND WOMEN'S (148)
 BATHROOMS. PLEASE SEE SECTIONS 604.8.2- 604.8.2.3 AND
 REVISE THE PLANS AND DETAILS ACCORDINGLY.
  
 12) P1.1.0 SAND/OIL INTERCEPTOR (SOI-1): A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1003.4.2 FBC P. B) LABEL THE
 ACCESS COVER AND RATED TRAFFIC LID- 1003.10, 1003.11 &
 305.7. C) PROVIDE SIZING CALCULATIONS IN ACCORDANCE
 WITH SECTION 1003.4.2.1 OR PER MANUFACTURER'S
 SPECIFICATIONS.
  
 13) P1.1.0 LINT TRAP (LI-1): A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SECTION
 1003.6 FBC P.
  
 14) P1.1.0 STORM SUMP PUMP: A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SECTION
 1113.1 FBC P. B) PROVIDE PUMP SIZING CALCS AND PUMP
 CURVE- 1113.1.1 C) PROVIDE AN ENLARGED INSTALLATION
 DETAIL SHOWING THE SUMP PIT DIMENSIONS, PIT MATERIALS,
 LOCATIONS OF VALVES, ACCESS TO VALVES, AND TRAFFIC
 RATED COVER- 1113.1.2. (DETAIL ON P5.02 IS INCOMPLETE)
 .D) SHOW THE LOCATION AND SIZE OF REQUIRED VENT-
 1113.1.4
  
 15) P.1.1.0: PROVIDE A NOTE AND GPM FLOW FOR THE STORM
 DRAIN PIPE BY THE SOUTH ENTRY DOOR- SECTION 1106.2 FBC
 P.
  
 16) P1.1.0, C2 & C2.1: SHOW THE DRAINAGE PIPING
 CONNECTIONS FOR THE TRENCH DRAINS (TD-1) LOCATED AT THE
 BAY DOORS. IF CONNECTING TO THE CITY STORM DRAINAGE
 SYSTEM, REFER TO SEC. 90-203 WPB CODE OF ORDINANCES AND
 VERIFY THAT THE DRAINS WILL CONVEY ONLY STORM WATER
 INTO THE SYSTEM. PLEASE NOTE THAT IT IS UNLAWFUL FOR
 ANY OTHER SUBSTANCES TO DISCHARGE INTO THE SYSTEM
 UNLESS MEETING ONE OF THE EXCEPTIONS UNDER SEC. 90- 205
 WPB.
  
 17) P1.1.0 SANITARY BACKWATER VALVE: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7.
  
 18) P1.1.0: PLACE A NOTE TO INDICATE NON-POTABLE WATER
 SIGNAGE WILL BE PROVIDED AT THE HB-1 LOCATION IN
 ACCORDANCE WITH SECTION 608.8.1 FBC P.
  
 19) P1.1.1 GREASE INTERCEPTOR G1-1: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.4 FBC P. B) PROVIDE SIZING
 CALCULATIONS- 1003.3.4. C) PROVIDE AN ENLARGED
 SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1 WPB. D)
 PLEASE NOTE ONLY FIXTURES DISCHARGING GREASE LADEN
 WASTE WATER SHALL FLOW INTO THE GREASE INTERCEPTOR.
 CLEAR WATER WASTE FROM HAND SINKS, ICE MACHINES ETC.
 SHALL NOT DRAIN INTO THE SYSTEM- SECTION 1003.3.1 FBC
 P.
  
 20) P1.1.1 SOLIDS INTERCEPTOR S1-1: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. B) PROVIDE SIZING
 CALCULATIONS- 1003.3.4. C) PROVIDE AN ENLARGED
 SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1 WPB.
  
 21) P1.1.1 SAMPLING PORT (SP-1): A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. B) PROVIDE AN
 ENLARGED SITE-SPECIFIC PIPING DRAWING- SECTION 107.2.1
 WPB.
  
 22) P1.1.1: PROVIDE NOTES AT THE TERMINATION LOCATIONS
 OF THE GREASE WASTE AND SANITARY SEWER LINES OR SHOW
 THE POINTS OF CONNECTIONS TO THE SEWER LINE- SECTION
 107.2.1 WPB.
  
 23) P1.1.1 STORM WATER BACKWATER VALVE: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7.
  
 24) P2.01: PROVIDE ROOF DRAINAGE PLANS AND A STORM
 DRAIN ISOMETRIC DRAWING- SECTION 107.3.5.1.3 FBC P.
 PLEASE NOTE THAT SEPARATE SYSTEMS ARE REQUIRED FOR
 PRIMARY AND SECONDARY (OVERFLOW) DRAINS- SECTION 1108.1
 FBC P. PLEASE SHOW THE PRIMARY AND SECONDARY SYSTEM
 DISCHARGE LOCATION(S). A) SHEET A2.01 SCHEDULE
 INCORRECTLY LISTS AREA 07 AS 02- SECTION 107.2.1 WPB.
 B) PROVIDE ROOF DRAIN AND OVERFLOW DRAIN INSTALLATION
 DETAILS- SECTIONS 1102.6 & 1105.1 C) PROVIDE GUTTER AND
 DOWNSPOUT INSTALLATION DETAILS INCLUDING DOWNSPOUT
 VERTICAL LEADERS TO UNDERGROUND STORM DRAIN
 CONNECTIONS- 1101.6, 1102.7.
  
 25) P4.01: PROVIDE CONDENSATE DISPOSAL DETAILS FOR THE
 TANKLESS WATER HEATERS- SECTION 314.1 FBC P. SEE GAS
 REVIEW COMMENTS FOR ADDITIONAL GAS WATER HEATER CODE
 REQUIREMENTS.
  
 26) P4.01, P7.02: THE GW FIXTURE DRAIN FROM THE MOP
 SINK IS SHOWN TO BE CONNECTING TO THE SANITARY DRAIN-
 SECTION 1003.3.1 FBC P.
  
 27) P4.01, P4.02, P7.01, P7.02, K7, K8, & K9: CLEAR
 WATER WASTE DRAINAGE FROM HAND SINKS AND WASTE
 RECEPTORS AT ICE BIN AND ICE MAKER LOCATIONS ARE SHOWN
 DISCHARGING INTO THE GW LINE WHICH IS PROHIBITED-
 SECTION 1003.3.1 FBC P.
  
 28) P4.01 & K7: CONDENSATE FROM THE WALK-IN BOX
 EVAPORATORS SHALL NOT DRAIN INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
  
 29) P4.01 & P4.02: INDICATE TEMPERED WATER IS BEING
 SUPPLIED TO LAVATORIES L-1, L-2, & L-3- SECTION 419.5
 FBC P.
  
 30) P7.01: THE RISER IS LABELED AS BASEMENT WASTE AND
 VENT RISER, HOWEVER THE 1ST FLOOR GREASE WASTE/VENT
 RISER IS ALSO SHOWN- SECTION 107.2.1 WPB.
  
 31) P7.01: THE 2-INCH WASTE STACKS FOR THE WASHING
 MACHINES ARE UNDERSIZED. MINIMUM 3-INCH STACKS ARE
 REQUIRED- SECTION 406.2 FBC P.
  
 32) P7.02: TD-2 AND SH-2 IN THE MEN'S BATHROOM DO NOT
 APPEAR TO BE VENTED PROPERLY. PLEASE CLARIFY HOW THE
 FIXTURES ARE BEING VENTED- SECTION 901.2.1 FBC P.
  
 33) P7.01 & P7.02: INDICATE HOW TRAP SEAL PROTECTION
 WILL BE PROVIDED FOR FLOOR DRAINS AND OTHER TRAP SEALS
 SUBJECT TO EVAPORATION WILL BE PROTECTED- SECTION
 1002.4.1 FBC P.
  
 34) P7.03, P7.04, K9: REQUIRED BACKFLOW PREVENTERS NOT
 SHOWN FOR SUPPLY LINES TO THE PIZZA OVEN, DISHWASHERS,
 COFFEE BREWER, ICED TEA BREWER, GLASS FILLER STATION,
 ICE AND SODA DISPENSER, SODA SYSTEM, HOT FOOD WELL, ICE
 MAKER, ICE BIN, WATER FILTRATION SYSTEM, BLENDER
 STATION, AND THE REF IMB-1- SECTION 608.3. FBC P.
  
 35) P7.03 & P7.04: PROVIDE A SHUTOFF VALVE AT THE TOP
 OF THE COLD WATER DOWN FEED PIPE FROM FIRST TO BASEMENT
 FLOOR- SECTION 606.1 (5) FBC P.
  
 36) P7.03 & P7.04: SHOW THE LOCATIONS OF WATER HAMMER
 ARRESTORS FOR SUPPLY LINES TO FLUSH VALVES, WASHING
 MACHINES, DISHWASHERS, AND OTHER FIXTURES AND EQUIPMENT
 WITH QUICK CLOSING VALVES- SECTION 604.9 FBC P.
  
 37) P7.04: PROVIDE AN ENLARGED PIPING DIAGRAM FOR
 INSTALLATION OF THE WATER HEATERS AND RECIRCULATION
 PUMPS SHOWING COMPLIANCE WITH 607.2.2 FBC P. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE PUMPS SHOWING
 COMPLIANCE WITH SECTION 607.2.1.2 ITEMS 1 & 2 FBC P-
 CONTROLS OPERATION.
  
 38) P.7.04: PROVIDE AN ENLARGED WATER FILTRATION PIPING
 DETAIL SHOWING SUPPLY CONNECTION TO THE FILTER, AND
 SUPPLY LINES TO FIXTURES AND EQUIPMENT REQUIRING
 FILTRATION. PLEASE NOTE THAT BACKFLOW PREVENTERS ARE
 REQUIRED FOR THE WATER SUPPLY LINES IN AND OUT OF THE
 FILTER- SECTION 608.3 FBC P.
  
 39) PLEASE NOTE THAT ALL REQUESTED MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR FIXTURES,
 APPLIANCES, AND EQUIPMENT MAY BE DEFERRED IN ACCORDANCE
 WITH SECTION 107.3.4.1 WPB. PLEASE NOTE THAT ALL
 DEFERRED SUBMITTALS SHALL BE LISTED ON THE PLAN.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-10-04 Cont ID  
Sent By rmcphers Date 2021-10-04 Time 14:26 Rev Time 0.00
Received By rmcphers Date 2021-10-04 Time 14:26 Sent To  
Notes
2021-10-04 14:26:43TPO LOW SLOPE ROOFING TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By rmcphers Date 2021-08-19 Time 16:25 Rev Time 0.00
Received By rmcphers Date 2021-08-19 Time 16:25 Sent To  
Notes
2021-08-19 16:26:18SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-11-24 Cont ID  
Sent By mpeterso Date 2021-11-24 Time 11:04 Rev Time 0.00
Received By mpeterso Date 2021-11-24 Time 11:05 Sent To  
Notes
2021-11-24 11:06:37PLANS SUBMITTED 11/24/2021 LABELED "M1.1.2, P0.0.1,
 P2.0.1, P4.0.2, P5.0.1, P5.0.2, P6.0.1, P6.0.2, P7.0.3,
 E2.1.0, E4.0.2, E4.0.3, E7.0.3" PASSED SIGNATURE REVIEW
 WITH SIGNATURE AND SEAL ON DIGITAL PLANS
2021-11-24 10:52:00REQUESTED DIGITALLY SIGNED FILES UNDER 'SIGNATURES'
 FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-11-18 Cont ID  
Sent By ccole Date 2021-11-18 Time 08:54 Rev Time 0.00
Received By ccole Date 2021-11-18 Time 08:10 Sent To  
Notes
2021-11-18 08:58:284TH SIGNATURE REVIEW- CCOLE
 11/18/21
  
 PLAN SHEETS LISTED BELOW IN THE 3RD REVIEW STILL NEED
 TO BE DIGITALLY SIGNED AND SEALED- FL. STATUTE 471.025
 AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 SIGNATURE REVIEW
  
 DRAWINGS BELOW IN PROJECTDOX DO NOT SHOW AS DIGITALLY
 SIGNED -
  
 M1.1.2, P0.0.1, P2.0.1, P4.0.2, P5.0.1, P5.0.2, P6.0.1,
 P6.0.2, P7.0.3, E2.1.0, E4.0.2, E4.0.3, E7.0.3
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-11-03 Cont ID  
Sent By rmcphers Date 2021-11-03 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2021-11-03 Time 10:32 Sent To  
Notes
2021-11-03 10:36:36SIGNATURE REVIEW
  
 DRAWINGS BELOW IN PROJECTDOX DO NOT SHOW AS DIGITALLY
 SIGNED -
  
 M1.1.2, P0.0.1, P2.0.1, P4.0.2, P5.0.1, P5.0.2, P5.0.4,
 P6.0.1, P6.0.2, P7.0.1, P7.0.3, E2.1.0, E4.0.2, E4.0.3,
 E7.0.3
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-10-04 Cont ID  
Sent By rmcphers Date 2021-10-04 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2021-10-04 Time 13:23 Sent To  
Notes
2021-10-04 13:55:44SIGNATURE REVIEW
  
 DRAWINGS BELOW AS LABLED IN PROJECTDOX DO NOT SHOW AS
 DIGITALLY SIGNED -
 122_E4.0.2 ENLARGED FOOD SERVICE PLANS-ELECTRICAL.PDF
 V2
 089_P4.0.1 ENLARGED KITCHEN, RRMS & WATER
 RM-PLUMBING.PDF V2
 098_P7.0.1 BASEMENT SANITRY WASTE & VENT
 RISR_WPBGCHPS.PDF V2
 090_P4.0.2 ENLRGD MENS & WMNS RRM WPBGCHPS.PDF V2
 085_P0.0.1 GENERAL NOTES, LEGEND -
 PLUMBING_WPBGCHPS.PDF V2
 070 M6.0.1 SCHEDULES - H.V.A.C_WPBGCHPS.PDF V2
 067 M1.1.2 ROOF PLAN - H.V.A.C_WPBGCHPS.PDF V2
 066 M1.1.1 FIRST FLOOR PLAN - H.V.A.C._WPBGCHPS.PDF V2
 065_M1.1.0 BASEMENT FLOOR PLAN - H.V.A.C_WPBGCHPS.PDF
 V2
 123_E4.0.3 ENLARGED FOOD SERVICE PLANS - ELECTRICAL.PDF
 V2
 131_E7.0.3 PANEL SCHEDULES - ELECTRICAL_WPBGCHPS.PDF V2
 117_E2.1.1 FIRST FLOOR PLAN - POWER_WPBGCHPS.PDF V2
 116_E2.1.0 BASEMENT FLOOR PLAN - POWER_WPBGCHPS.PDF V2
 102_P7.0.5 NATURAL GAS RISER_WPBGCHPS.PDF V2
 101_P7.0.4 FIRST FLOOR DOMESTIC WATER
 RISER_WPBGCHPS.PDF V2
 100_P7.0.3 BASEMENT DOMESTIC WATER RISER_WPBGCHPS.PDF
 V2
 096_P6.0.2 SCHEDULES - PLUMBING_WPBGCHPS.PDF V2
 095_P6.0.1 SCHEDULES - PLUMBING_WPBGCHPS.PDF V2
 094_P5.0.4 DETAILS - PLUMBING_WPBGCHPS.PDF V2
 092_P5.0.2 DETAILS - PLUMBING_WPBGCHPS.PDF V2
 091_P5.0.1 DETAILS - PLUMBING_WPBGCHPS.PDF V2
 088_P2.0.1 ROOF PLAN - PLUMBING_WPBGCHPS.PDF V2
 087_P1.1.1 FIRST FLOOR PLAN - PLUMBING_WPBGCHPS.PDF V2
 086_P1.1.0 BASEMENT FLOOR PLAN - PLUMBING_WPBGCHPS.PDF
 V2
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
2021-09-28 10:34:12SHEETS M1.1.0, M1.1.1,M1.1.2, M6.0.1 ARE MISSING THE
 DIGITAL SIGNATURES FROM THE DESIGNER. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By rmcphers Date 2021-08-19 Time 16:54 Rev Time 0.00
Received By rmcphers Date 2021-08-19 Time 16:54 Sent To  
Notes
2021-08-19 16:56:22SIGNATURE REVIEW
 CIVIL DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES NOT
 HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP
 OFF THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 TO THE FRONT DESK IN THE BUILDING DIVISION AT THE CITY
 HALL.
  
2021-08-19 06:06:12MECHANICAL SHEETS APPROVED ME

Review Stop Z ZONING
Rev No 4 Status P Date 2021-11-05 Cont ID  
Sent By jroach Date 2021-11-05 Time 10:35 Rev Time 0.00
Received By jroach Date 2021-11-05 Time 10:34 Sent To  
Notes
2021-11-05 10:35:18ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 11.05.2021
 PERMIT NO.: 21070675
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMITS REQUIRED FOR:
  
 1.1. LANDSCAPING
 1.2. FENCING/GATES
 1.3. SITE/PRIVACY WALLS
 1.4. SITE LIGHTING
 1.5. IRRIGATION
 1.6. GENERATOR
 1.7. SIGNAGE
 1.8. PARING LOT / STRIPING / HARDSCAPE
 1.9. SITE FIXTURES (I.E. BIKE RACKS, ETC.)
  
 2. THE WPB GOLF PARK DEVELOPMENT SHALL BE SUBJECT TO
 ALL DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN FORMAL
 SITE PLAN REVIEW (FSPR) CASE NO. 21-02, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY FSPR
 CASE NO. 21-02, AS AMENDED, SHALL BE ADDRESSED WITHIN
 THE APPROPRIATE SPECIFIED TIMEFRAMES.
  
 3. A REVISION TO THE BUILDING AND LANDSCAPE PERMITS
 SHALL BE SUBMITTED AND APPROVED TO REVISE THE PLANS AND
 ACCURATELY REFLECT THE FOLLOWING:
  
 3.1 LOCATION OF ALL MECHANICAL EQUIPMENT
 3.2 DETAIL ON THE MARKING FOR COMPACT PARKING SPACES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-10-01 Cont ID  
Sent By jroach Date 2021-10-01 Time 08:02 Rev Time 0.00
Received By jroach Date 2021-10-01 Time 08:02 Sent To  
Notes
2021-10-01 08:05:15ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10.01.2021
 PERMIT NO.: 21070675
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMITS REQUIRED FOR:
  
 1.1. LANDSCAPING
 1.2. FENCING/GATES
 1.3. SITE/PRIVACY WALLS
 1.4. SITE LIGHTING
 1.5. IRRIGATION
 1.6. GENERATOR
 1.7. SIGNAGE
 1.8. PARING LOT / STRIPING / HARDSCAPE
 1.9. SITE FIXTURES (I.E. BIKE RACKS, ETC.)
  
 2. THE WPB GOLF PARK DEVELOPMENT SHALL BE SUBJECT TO
 ALL DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN FORMAL
 SITE PLAN REVIEW (FSPR) CASE NO. 21-02, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY FSPR
 CASE NO. 21-02, AS AMENDED, SHALL BE ADDRESSED WITHIN
 THE APPROPRIATE SPECIFIED TIMEFRAMES.
  
 3. A REVISION TO THE BUILDING AND LANDSCAPE PERMITS
 SHALL BE SUBMITTED AND APPROVED TO REVISE THE PLANS AND
 ACCURATELY REFLECT THE FOLLOWING:
  
 3.1 LOCATION OF ALL MECHANICAL EQUIPMENT
 3.2 DETAIL ON THE MARKING FOR COMPACT PARKING SPACES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-09-25 Cont ID  
Sent By jroach Date 2021-09-25 Time 12:39 Rev Time 0.00
Received By jroach Date 2021-09-25 Time 12:32 Sent To  
Notes
2021-09-25 12:46:12ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 09.25.2021
 PERMIT NO.: 21070675
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - THE SITE PLAN SUBMITTED DOES NOT
 MATCH THE SITE PLAN THAT WAS APPROVED DURING THE FORMAL
 SITE PLAN REVIEW PROCESS; A SIGNIFICANT AMOUNT OF
 INFORMATION IS MISSING FROM THE SUBMITTED PLAN, ETC.
 PLEASE INCLUDE THE SITE PLAN, DETAILS, ETC. THAT WAS
 PREPARED BY URBAN DESIGN STUDIOS AND APPROVED AS PART
 OF FSPR CASE NO. 21-02. IF MODIFICATIONS TO THE
 APPROVED PLAN ARE NECESSARY, PLEASE INDICATE THE SCOPE
 OF THE MODIFICATIONS TO DETERMINE IF AN AMENDMENT IS
 REQUIRED.
  
 2. [ SATISFIED ] - LANDSCAPE PLANS SHALL BE REMOVED
 FROM THE BUILDING PERMIT SUBMITTAL AND SHALL BE
 SUBMITTED AS A SEPARATE LANDSCAPE PERMIT.
  
 3. [ SATISFIED ] - PLEASE PROVIDE SPECIFICATIONS FOR
 THE GENERATOR (PARTICULARLY THE HEIGHT) TO ENSURE THAT
 THE SCREEN WALL, AS DESIGNED, WILL FULLY SCREEN THE
 GENERATOR.
  
 4. [ NOT SATISFIED ] - MECHANICAL PLANS SHOW TWO (2)
 CONDENSING UNITS ON THE NORTH SIDE OF THE PRO SHOP THAT
 ARE NOT REFLECTED OR ACCOUNTED FOR ON THE LANDSCAPE
 PLANS. PLEASE ENSURE THAT ALL PLANS ARE CONSISTENT AND
 ACCURATE. ADDITIONALLY, THE LANDSCAPE PLANS WILL NEED
 TO ENSURE THAT THE UNITS ARE COMPLETELY SCREENED FROM
 VIEW.
  
 4.1 [ NEW COMMENT ] - WRITTEN RESPONSE TO COMMENT IS
 UNCLEAR. THE SITE PLAN SUBMITTED FOR PERMITTING SHOULD
 BE REVISED TO REFLECT THE SCOPE OF THE WORK PROPOSED,
 INCLUDING THE LOCATION OF ALL MECHANICAL EQUIPMENT.
  
 5. [ SATISFIED ] - THE PARKING STRIPING DETAIL ON SHEET
 C1.0 DOES NOT COMPLY WITH THE CITY?S STANDARD DETAIL.
 PLEASE CONTACT ME FOR THE APPROPRIATE DETAIL (IF
 NEEDED).
  
 6. [ NOT SATISFIED ] - A DETAIL SHALL BE PROVIDED
 INDICATING HOW THE COMPACT PARKING SPACES WILL BE
 MARKED.
  
 6.1 [ NEW COMMENT ] - THE WRITTEN RESPONSE INDICATES
 THAT A DETAIL IS NOT PROVIDED AS THERE ARE NO COMPACT
 SPACES BEING PROPOSED. HOWEVER, THE APPROVED SITE PLAN
 INDICATES THAT AT LEAST 16 COMPACT SPACES ARE PROPOSED.
 AS SUCH, A DETAIL SHOWING HOW THE COMPACT PARKING
 SPACES WILL BE MARKED SHALL BE INCLUDED.
  
 7. [ SATISFIED ] - SEPARATE PERMITS REQUIRED FOR:
  7.1. LANDSCAPING
  7.2. FENCING/GATES
  7.3. SITE/PRIVACY WALLS
  7.4. SITE LIGHTING
  7.5. IRRIGATION
  7.6. GENERATOR
  7.7. SIGNAGE
  7.8. PARING LOT / STRIPING / HARDSCAPE
  7.9. SITE FIXTURES (I.E. BIKE RACKS, ETC.)
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-03 Cont ID  
Sent By jroach Date 2021-09-03 Time 15:39 Rev Time 0.00
Received By jroach Date 2021-09-03 Time 15:39 Sent To  
Notes
2021-09-03 15:59:49ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 09.03.2021
 PERMIT NO.: 21070675
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE SITE PLAN SUBMITTED DOES NOT MATCH THE SITE PLAN
 THAT WAS APPROVED DURING THE FORMAL SITE PLAN REVIEW
 PROCESS; A SIGNIFICANT AMOUNT OF INFORMATION IS MISSING
 FROM THE SUBMITTED PLAN, ETC. PLEASE INCLUDE THE SITE
 PLAN, DETAILS, ETC. THAT WAS PREPARED BY URBAN DESIGN
 STUDIOS AND APPROVED AS PART OF FSPR CASE NO. 21-02. IF
 MODIFICATIONS TO THE APPROVED PLAN ARE NECESSARY,
 PLEASE INDICATE THE SCOPE OF THE MODIFICATIONS TO
 DETERMINE IF AN AMENDMENT IS REQUIRED.
  
 2. LANDSCAPE PLANS SHALL BE REMOVED FROM THE BUILDING
 PERMIT SUBMITTAL AND SHALL BE SUBMITTED AS A SEPARATE
 LANDSCAPE PERMIT.
  
 3. PLEASE PROVIDE SPECIFICATIONS FOR THE GENERATOR
 (PARTICULARLY THE HEIGHT) TO ENSURE THAT THE SCREEN
 WALL, AS DESIGNED, WILL FULLY SCREEN THE GENERATOR.
  
 4. MECHANICAL PLANS SHOW TWO (2) CONDENSING UNITS ON
 THE NORTH SIDE OF THE PRO SHOP THAT ARE NOT REFLECTED
 OR ACCOUNTED FOR ON THE LANDSCAPE PLANS. PLEASE ENSURE
 THAT ALL PLANS ARE CONSISTENT AND ACCURATE.
 ADDITIONALLY, THE LANDSCAPE PLANS WILL NEED TO ENSURE
 THAT THE UNITS ARE COMPLETELY SCREENED FROM VIEW.
  
 5. THE PARKING STRIPING DETAIL ON SHEET C1.0 DOES NOT
 COMPLY WITH THE CITY?S STANDARD DETAIL. PLEASE CONTACT
 ME FOR THE APPROPRIATE DETAIL (IF NEEDED).
  
 6. A DETAIL SHALL BE PROVIDED INDICATING HOW THE
 COMPACT PARKING SPACES WILL BE MARKED.
  
 7. SEPARATE PERMITS REQUIRED FOR:
  7.1. LANDSCAPING
  7.2. FENCING/GATES
  7.3. SITE/PRIVACY WALLS
  7.4. SITE LIGHTING
  7.5. IRRIGATION
  7.6. GENERATOR
  7.7. SIGNAGE
  7.8. PARING LOT / STRIPING / HARDSCAPE
  7.9. SITE FIXTURES (I.E. BIKE RACKS, ETC.)
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved