Plan Review Details - Permit 21070634
Plan Review Stops For Permit 21070634
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 13:34 Rev Time 0.00
Received By rmcphers Date 2021-07-21 Time 13:26 Sent To  
Notes
2021-07-21 13:29:39CANOPY DRAWINGS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING NEEDS TO SHOW THE WIND DESIGN DATA AND CODE
 VERSION USED PER FBC 1603.1.4
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-30 Cont ID  
Sent By rmcdouga Date 2021-08-30 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2021-08-27 Time 12:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2021-07-23 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 13:34 Rev Time 0.00
Received By rmcphers Date 2021-07-14 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-30 Cont ID  
Sent By rmcdouga Date 2021-08-30 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2021-08-30 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 13:30 Sent To  
Notes
2021-07-27 13:33:51SIGNATURE REVIEW
 DRAWING LABELED "RAC PE 7 6 21 75084-PRODUCTION.PDF"
 DOES NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE READER
 - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2021-07-21 Time 13:33 Sent To  
Notes
2021-07-21 13:34:16SIGNATURE REVIEW
 DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR
 - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  