Plan Review Details - Permit 21070600
Plan Review Stops For Permit 21070600
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 08:56 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 08:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-12 Cont ID  
Sent By rmcphers Date 2021-08-12 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2021-08-12 Time 11:31 Sent To  
Notes
2021-08-12 11:35:14CONCRETE PAD FOR TEMPORARY TRAILER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A1.2 HAS NOT BEEN REVIESED. PLEASE SHOW THE
 ACCESSIBLE ROUTE TO COMPLY WITH FBC 402 - PLEASE SHOW
 THE ACCESSIBLE ROUTE FROM THE BUILDING EXIT DOOR TO THE
 TRAILER AREA.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 15:01 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 14:51 Sent To  
Notes
2021-07-27 15:07:08CONCRETE PAD FOR TEMPORARY TRAILER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE MORE INFORMATION ON THE TRAILER. WILL
 THE TRAILER REMAIN MOBILE (NOT STRUCTURALLY TIED
 DOWN?). CLEARLY SHOW THE THE TRAILER USE.
 2) PLEASE SHOW THE ACCESSIBLE ROUTE TO COMPLY WITH FBC
 402
 3) PLEASE PROVIDE THE ACCESSIBLE LIFT DETAILS TO COMPLY
 WITH FBC 410
 4) PLEASE SHOW THE TRAILER DISTANCE FROM THE EXISTING
 BUILDING. FBC WPB 107.2.5
 5) PLEASE PROVIDE CANOPY DETAILS TO COMPLY WITH FBC
 3105
 6) FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-28 Cont ID  
Sent By jleahy Date 2021-07-28 Time 10:57 Rev Time 0.00
Received By jleahy Date 2021-07-28 Time 07:26 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-11-16 Cont ID  
Sent By jleahy Date 2021-11-16 Time 11:05 Rev Time 0.00
Received By jleahy Date 2021-11-16 Time 11:05 Sent To  
Notes
2021-11-16 11:05:53NURSE CALL SYSTEM ONLY. JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By pleduc Date 2021-08-10 Time   Rev Time 0.00
Received By pleduc Date 2021-08-10 Time 08:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-15 Cont ID  
Sent By pleduc Date 2021-07-15 Time   Rev Time 0.00
Received By pleduc Date 2021-07-15 Time 11:09 Sent To  
Notes
2021-07-15 11:39:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF A PROPOSED TEMPORAY TRAILER
 THAT WILL BE LOCATED NEXT TO A BUILDING.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE PROVIDE DIMENSIONS TO THE PROPOSED LOCATED
 TRAILER AND ENSURE THAT THOSE DIMENSIONS COMPLY WITH
 THE REQUIREMENT.
  
 PLEASE ALSO NOTE THAT THERE IS A 75% REDUCTION FOR FIRE
 SPRINKLER INSTALLATION.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-02 Cont ID  
Sent By lmarchan Date 2021-09-02 Time 10:20 Rev Time 0.00
Received By lmarchan Date 2021-08-25 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-19 Cont ID  
Sent By lmarchan Date 2021-08-19 Time 16:10 Rev Time 0.00
Received By lmarchan Date 2021-08-09 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-07-28 Time   Rev Time 0.00
Received By cdecoeur Date 2021-07-14 Time 13:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-08-27 Cont ID  
Sent By ccole Date 2021-08-27 Time 13:17 Rev Time 0.00
Received By ccole Date 2021-08-27 Time 12:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-13 Cont ID  
Sent By ccole Date 2021-08-13 Time 09:00 Rev Time 0.00
Received By ccole Date 2021-08-12 Time 12:43 Sent To  
Notes
2021-08-13 09:01:312ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21070600
 8/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. IN RESAPONSE TO COMMENTS
 #2 & #3 PRINTED BELOW THE ARCHTECT OF RECORD STATES IN
 HIS NARRATIVE RESPONSE: "THE TEMPORARY TRAILER IS
 UTILIZED TO SUPPLEMENT CRITICAL MEDICAL MODALITIES (CT,
 MRI, X-RAY, ETC.) AND NOT AS AN OFFICE OR A PLACE OF
 DWELLING. SEE ATTACHED TRAILER PLAN SHOWING NO PLUMBING
 FIXTURES IN THIS TRAILER. PLUMBING SUPPLY IS BEING
 PROVIDED FOR ANY FUTURE TRAILER THAT MAY HAVE PLUMBING
 REQUIREMENTS". THE PLUMBING PLAN SHEET P1.1 HOWEVER IS
 INDICATING WATER LINE AND SANITARY DRAIN CONNECTIONS TO
 THE TRAILER. PLEASE CLARIFY THE NEED FOR WATER SUPPLY
 AND DRAIN CONNECTIONS TO THE TRAILER IF THERE ARE NO
 PLUMBING FIXTURES.
  
 2) A0.0 & P1.1 PLUMBING FIXTURE CALCULATIONS: PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES FOR THE TRAILER IN ACCORDANCE WITH
 TABLE 403.3 FBC P AND SHOW THEIR LOCATIONS. PLEASE NOTE
 THAT SECTION 102.2 WPB DOES NOT EXEMPT THE TRAILER FROM
 MEETING THE PLUMBING CODE. THE FIXTURES SHALL BE
 PROVIDED FOR BOTH PUBLIC AND STAFF USE- SECTION 403.3
 FBC P.
  
 3) P1.1: A COMPLETE PLUMBING REVIEW CANNOT BE COMPLETED
 AT THIS TIME BECAUSE THE TRAILER ARCHITECTURAL AND
 PLUMBING PLANS HAVE NOT BEEN PROVIDED. IN ACCORDANCE
 WITH SECTION 107.2.1 & 107.23.5.1.3 WPB THE TRAILER
 PLANS SHALL SHOW:
 A) LOCATIONS AND TYPES OF PLUMBING FIXTURES INSTALLED.
 B) SOURCE OF HOT WATER WHERE HOT WATER USE IS REQUIRED.
 C) WATER AND SANITARY RISER DRAWINGS.
 D) FBC ACC FIXTURE COMPLIANCE DETAILS AND DRAWINGS.
  
 NEW COMMENT.
 1) THE NEW TRAILER SUBMITTAL SHOWS AN AC SYSTEM WHICH
 WILL PRODUCE CONDENSATE. PLEASE PROVIDE A CONDENSATE
 DISPOSAL PLAN IN COMPLIANCE WITH SECTIONS 314.2 &
 314.2.1 FBC P. PLEASE NOTE THE SANITARY DRAIN AND THE
 PARKING LOT ARE NOT APPROVED PLACES OF DISPOSAL-
 SECTION 90-126 WPB CODE OR ORDINANCES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-28 Cont ID  
Sent By ccole Date 2021-07-28 Time 11:02 Rev Time 0.00
Received By ccole Date 2021-07-28 Time 08:36 Sent To  
Notes
2021-07-28 11:02:441ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21070600
 7/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0.0: PLEASE SEE SECTION 108.1 WPB AMENDMENTS
 TO THE FBC B AND INDICATE THE LENGTH OF TRAILER
 TEMPORARY USE TIME. PLEASE NOTE TEMPORARY USE PERMITS
 ARE VALID FOR 6 MONTHS AND EXTENDED USE BEYOND THAT
 TIME MUST BE GRANTED BY THE BUILDING OFFICIAL.
  
 2) A0.0 & P1.1 PLUMBING FIXTURE CALCULATIONS: PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES FOR THE TRAILER IN ACCORDANCE WITH
 TABLE 403.3 FBC P, AND SHOW THEIR LOCATIONS. PLEASE
 NOTE THAT SECTION 102.2 WPB DOES NOT EXEMPT THE TRAILER
 FROM MEETING THE PLUMBING CODE. THE FIXTURES SHALL BE
 PROVIDED FOR BOTH PUBLIC AND STAFF USE- SECTION 403.3
 FBC P.
  
 3) P1.1: A COMPLETE PLUMBING REVIEW CANNOT BE COMPLETED
 AT THIS TIME BECAUSE THE TRAILER ARCHITECTURAL AND
 PLUMBING PLANS HAVE NOT BEEN PROVIDED. IN ACCORDANCE
 WITH SECTION 107.2.1 & 107.23.5.1.3 WPB THE TRAILER
 PLANS SHALL SHOW:
 A) LOCATIONS AND TYPES OF PLUMBING FIXTURES INSTALLED.
 B) SOURCE OF HOT WATER WHERE HOT WATER USE IS REQUIRED.
 C) WATER AND SANITARY RISER DRAWINGS.
 D) FBC ACC FIXTURE COMPLIANCE DETAILS AND DRAWINGS.
  
 4) P1.1: REVISE NOTE 3 TO INDICATE A SEPARATE PERMIT
 WILL BE OBTAINED FOR INSTALLATION OF THE BACKFLOW-
 SECTION 105.1 WPB.
  
 5) PROVIDE IRRIGATIONS PLANS- SECTION 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 08:58 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 08:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-12 Cont ID  
Sent By rmcphers Date 2021-08-12 Time 11:36 Rev Time 0.00
Received By rmcphers Date 2021-08-12 Time 11:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 15:34 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 15:34 Sent To  
Notes
2021-07-27 15:36:49SIGNATURE REVIEW
 DRAWINGS LABLED "012 - L100 LANDSCAPE PLAN.PDF" AND
 "013 - L150 LANDSCAPE NOTES.PDF" IN PROJECTDOX DO NOT
 SHOW AS ELECTRONICALLY SIGNED IN ADOBE READER - SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-09-01 Cont ID  
Sent By llouie Date 2021-09-01 Time   Rev Time 0.00
Received By llouie Date 2021-09-01 Time   Sent To  
Notes
2021-09-01 16:16:04* SEPARATE PERMITS REQUIRED FOR LANDSCAPING/IRRIGATION
 AND BICYCLE RACK.
  
 (REFERENCE: PB CASE NO. 1068JJ)

Review Stop Z ZONING
Rev No 2 Status F Date 2021-08-19 Cont ID  
Sent By llouie Date 2021-08-19 Time   Rev Time 0.00
Received By llouie Date 2021-08-19 Time   Sent To  
Notes
2021-08-19 15:58:05** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) MINOR PLANNED DEVELOPMENT (PD) APPLICATION FOR THE
 PROPOSED SCOPE OF WORK IS CURRENTLY IN REVIEW
 (REFERENCE: PB CASE NO. 1068JJ). ZONING CANNOT PASS THE
 REVIEW UNTIL THE MINOR PD AMENDMENT IS APPROVED. ALL
 PLANS APPROVED AS PART OF THE MINOR PD AMENDMENT MUST
 MATCH THE PERMIT PLANS FOR CONSISTENCY.
  
  
 NOTES:
  
 * PB CASE NO. 1068JJ HEARD BY THE PPRC ON 6/10.
 RESUBMITTAL RECIEVED ON 8/17 AND IS CURRENT IN REVIEW.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CSPD (ST. MARY'S)

Review Stop Z ZONING
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By llouie Date 2021-07-22 Time   Rev Time  
Received By llouie Date 2021-07-22 Time   Sent To  
Notes
2021-07-22 15:07:16** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) MINOR PLANNED DEVELOPMENT (PD) APPLICATION FOR THE
 PROPOSED SCOPE OF WORK IS CURRENTLY IN REVIEW
 (REFERENCE: PB CASE NO. 1068JJ). ZONING CANNOT PASS THE
 REVIEW UNTIL THE MINOR PD AMENDMENT IS APPROVED. ALL
 PLANS APPROVED AS PART OF THE MINOR PD AMENDMENT MUST
 MATCH THE PERMIT PLANS FOR CONSISTENCY.
  
  
 NOTES:
  
 * PB CASE NO. 1068JJ HEARD BY THE PPRC ON 6/10.
 AWAITING RESUBMITTAL FROM THE APPLICANT.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CSPD (ST. MARY'S)
  