| Plan Review Stops For Permit 21070558 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-07-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-07-20 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-07-20 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2021-07-20 09:46:10 | ADDRESS CHANGED FROM 5415 MANNING AVE TO 700 54TH ST TH | | | NEW BUILDINGS ENTRANCE IS ON 54TH ST. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-07-13 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-07-13 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2021-07-13 13:07:30 | CORNER LOT, IT APPEARS THAT THE MAIN ENTRANCE WILL NOW | | | BE ON 54TH ST. PLEASE HAVE OWNER CONTACT [email protected] | | | OR 561-805-6659 TO DISCUSS ADDRESSING OPTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-04-26 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-04-26 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-24 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-24 |
Time |
12:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-08 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-08 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2021-12-08 11:23:03 | NEW BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB | | | CHAPTER 1 AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW ATTIC PROTECTION TO COMPLY WITH FBC | | | 903.2.8.3 GROUP R-4 CONDITION 2. | | | AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE | | | WITH SECTION 903.3.1.2 SHALL BE PERMITTED IN GROUP R-4 | | | CONDITION 2 OCCUPANCIES. ATTICS SHALL BE PROTECTED IN | | | ACCORDANCE WITH SECTION 903.2.8.3.1 OR 903.2.8.3.2. | | | | | | FBC 903.2.8.3.2 ATTICS NOT USED FOR LIVING PURPOSES, | | | STORAGE OR FUEL-FIRED EQUIPMENT. | | | ATTICS NOT USED FOR LIVING PURPOSES, STORAGE OR | | | FUEL-FIRED EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE | | | WITH ONE OF THE FOLLOWING: | | | | | | A).ATTICS PROTECTED THROUGHOUT BY A HEAT DETECTOR | | | SYSTEM ARRANGED TO ACTIVATE THE BUILDING FIRE ALARM | | | SYSTEM IN ACCORDANCE WITH SECTION 907.2.10. | | | | | | B).ATTICS CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS. | | | | | | C).ATTICS CONSTRUCTED OF FIRE-RETARDANT-TREATED WOOD | | | FRAMING COMPLYING WITH SECTION 2303.2. | | | | | | D).THE AUTOMATIC SPRINKLER SYSTEM SHALL BE EXTENDED TO | | | PROVIDE PROTECTION THROUGHOUT THE ATTIC SPACE. | | | | | | 2) PLEASE SHOW FIRE SPRINKLER COVERAGE FOR THE PATIOS | | | PER FBC 903.3.1.2.1 BALCONIES AND DECKS. | | | SPRINKLER PROTECTION SHALL BE PROVIDED FOR EXTERIOR | | | BALCONIES, DECKS AND GROUND FLOOR PATIOS OF DWELLING | | | UNITS AND SLEEPING UNITS WHERE THE BUILDING IS OF TYPE | | | V CONSTRUCTION, PROVIDED THERE IS A ROOF OR DECK ABOVE. | | | SIDEWALL SPRINKLERS THAT ARE USED TO PROTECT SUCH AREAS | | | SHALL BE PERMITTED TO BE LOCATED SUCH THAT THEIR | | | DEFLECTORS ARE WITHIN 1 INCH (25 MM) TO 6 INCHES (152 | | | MM) BELOW THE STRUCTURAL MEMBERS AND A MAXIMUM DISTANCE | | | OF 14 INCHES (356 MM) BELOW THE DECK OF THE EXTERIOR | | | BALCONIES AND DECKS THAT ARE CONSTRUCTED OF OPEN WOOD | | | JOIST CONSTRUCTION. | | | | | | 3) FENCE AND GENERATOR - EACH REQUIRE A SEPARATE PERMIT | | | - WHICH CAN BE SUBMITTED LATER - BEFORE INSTALLATION. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-09-01 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-01 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2021-09-01 10:56:56 | NEW BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB | | | CHAPTER 1 AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWING A-1.10 SHOWS R3 "CONGREGATE" LIVING FACILITY | | | WITH 5 OCCUPANTS MAXIMUM - DRAWING STATES COMPLIANCE IS | | | PER FBC RESIDENTIAL CODE - FBC R310.5.1 ALLOWS "CARE" | | | FACILITIES (NOT "CONGREGATE" FACILITIES) WITHIN A | | | DWELLING. CARE FACILITIES FOR FIVE OR FEWER PERSONS | | | RECEIVING CARE THAT ARE WITHIN A SINGLE-FAMILY DWELLING | | | ARE PERMITTED TO COMPLY WITH THE FLORIDA BUILDING CODE, | | | // R3 CONGREGATE WILL NEED TO USE THE FBC BUILDING. | | | 2) PLEASE SHOW DESCRIPTION AS (CONGREGATE (TRANSIENT) | | | OR (NON TRANSIENT) ) PER FBC 310.5 | | | 3) PLEASE PROVIDE COMPLETE PRODUCT APPROVALS FOR THE | | | EXTERIOR WINDOWS, DOORS, ROOFING SYSTEMS ETC.. ALL | | | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE | | | LISTED BY PRODUCT APPROVAL NUMBER ON THE DRAWINGS. FBC | | | WPB 107.2.1 | | | 4) HARDI PLANK SIDING IS SUBJECT TO WIND LOADS - PLEASE | | | PROVIDE ATTACHMENT DETAILS OR PRODUCT APPROVALS TO | | | COMPLY WITH FBC R703.1.2 | | | 5) PLEASE SHOW THE WOOD EXTERIOR WALLS -WATER RESISTIVE | | | BARRIER TO COMPLY WITH FBC R703.2 | | | | | | DRAWINGS WERE REVIEWED BASED ON THE FBC RESIDENTIAL - | | | IF CORRECTIONS SUGGEST DESIGN TO BE PER FBC BUILDING | | | ADDITIONAL CORRECTIONS MAY BE REQUIRED. | | | | | | | | 2021-08-16 17:34:59 | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-08-02 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-08-02 |
Time |
21:25 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-07-30 |
Time |
21:48 |
Sent To |
|
|
| Notes |
| 2021-08-02 21:24:59 | SEPARATE PERMIT REQUIRED FOR GENERATOR. | | | | | | SEPARATE PERMIT AND PLANS SUBMITTAL REQUIRED FOR FIRE | | | ALARM. | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2023-01-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2023-01-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-30 11:30:53 | A FORMAL ENGINEERING SUBMITTAL IS REQUIRED. PLEASE | | | EMAIL FOR AN ENGINEERING SUBMITTAL PACKAGE. | | | | | | THANKS, | | | RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES | | | DEPT., 561-494-1098, FAX: 561-494-1116 [email protected] | | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-02-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-02-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-02-11 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2021-11-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-11-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-11-29 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2021-11-29 12:10:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) PREVIOUS COMMENT # 2 WAS NOT ADDRESSED AND REMAINS. | | | | | | THE PRIMARY MEANS OF ESCAPE WITH THE STAIR OPENING INTO | | | THE LVIVING ROOMS DOES NOT MEET THE REQUIREMENTS OF | | | NFPA 101 CH 32 | | | | | | | | | 32.2.2.4.6 IN BUILDINGS THREE OR FEWER STORIES IN | | | HEIGHT AND PROTECTED | | | BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 32.2.3.5, | | | STAIR ENCLOSURES SHALL NOT BE REQUIRED, PROVIDED THAT | | | THERE STILL REMAINS | | | A PRIMARY MEANS OF ESCAPE FROM EACH SLEEPING AREA THAT | | | DOES NOT REQUIRE | | | OCCUPANTS TO PASS THROUGH A PORTION OF A LOWER FLOOR, | | | UNLESS THAT ROUTE | | | IS SEPARATED FROM ALL SPACES ON THAT FLOOR BY | | | CONSTRUCTION HAVING A MINIMUM | | | 1?2-HOUR FIRE RESISTANCE RATING. | | | | | | THE PROVISIONS OF 32/33.2.2.4.7 PERMIT A TWO-STORY OPEN | | | STAIR | | | (AND ITS ASSOCIATED EXPOSURE TO THE AREAS THAT ARE | | | OCCUPIED OR FURNISHED, | | | OR BOTH, ON THE GROUND FLOOR) TO SERVE AS PRIMARY MEANS | | | OF | | | ESCAPE FOR NEW SMALL FACILITIES AND EXISTING SMALL | | | FACILITIES (NOT | | | MORE THAN EIGHT RESIDENTS) WITH PROMPT EVACUATION | | | CAPABILITY, | | | PROVIDED THAT THE FACILITY IS SPRINKLERED USING | | | QUICK-RESPONSE OR | | | RESIDENTIAL SPRINKLERS. THIS PROVISION, IN EFFECT, | | | EQUATES SUCH A | | | BOARD AND CARE FACILITY WITH A ONE- OR TWO-FAMILY | | | DWELLING. AN | | | UNENCLOSED INTERIOR STAIR MEETING THE CRITERIA OF THIS | | | PROVISION IS | | | CONSIDERED THE EQUIVALENT OF AN ENCLOSED INTERIOR | | | STAIR. | | | | | | | | | PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED | | | NARRATIVE WITH CODE REFERENCES | | | | | | | | | | | | *****ADDITIONAL COMMENT**** | | | | | | | | | 2) THERE IS AN INDICATION OF A RAMP LEADING TO A PUBLIC | | | WAY; HOWEVER, THERE ARE OPENINGS ALONG THE RAMP ROUTE | | | THAT APPEAR TO BE NORMAL GLAZING. | | | | | | 32.2.2.2 PRIMARY MEANS OF ESCAPE. | | | | | | 32.2.2.2.1 EVERY SLEEPING ROOM AND LIVING AREA SHALL | | | HAVE ACCESS TO A | | | PRIMARY MEANS OF ESCAPE LOCATED TO PROVIDE A SAFE PATH | | | OF TRAVEL TO THE | | | OUTSIDE AT STREET LEVEL OR THE FINISHED GROUND LEVEL. | | | | | | 32.2.2.2.2 WHERE SLEEPING ROOMS OR LIVING AREAS ARE | | | ABOVE OR BELOW | | | THE LEVEL OF EXIT DISCHARGE, THE PRIMARY MEANS OF | | | ESCAPE SHALL BE AN | | | INTERIOR STAIR IN ACCORDANCE WITH 32.2.2.4, AN EXTERIOR | | | STAIR, A HORIZONTAL | | | EXIT, OR A FIRE ESCAPE STAIR | | | | | | 32.1.1.3 GENERAL. THE PROVISIONS OF CHAPTER 4, GENERAL, | | | SHALL APPLY. | | | | | | 4.5.3 MEANS OF EGRESS. | | | 4.5.3.1 NUMBER OF MEANS OF EGRESS. TWO MEANS OF EGRESS, | | | AS A MINIMUM, | | | SHALL BE PROVIDED IN EVERY BUILDING OR STRUCTURE, | | | SECTION, AND AREA | | | WHERE SIZE, OCCUPANCY, AND ARRANGEMENT ENDANGER | | | OCCUPANTS ATTEMPTING | | | TO USE A SINGLE MEANS OF EGRESS THAT IS BLOCKED BY FIRE | | | OR SMOKE. THE | | | TWO MEANS OF EGRESS SHALL BE ARRANGED TO MINIMIZE THE | | | POSSIBILITY THAT | | | BOTH MIGHT BE RENDERED IMPASSABLE BY THE SAME EMERGENCY | | | CONDITION. | | | | | | 4.6.1.2 ANY REQUIREMENTS THAT ARE ESSENTIAL FOR THE | | | SAFETY OF BUILDING | | | OCCUPANTS AND THAT ARE NOT SPECIFICALLY PROVIDED FOR BY | | | THIS CODE SHALL | | | BE DETERMINED BY THE AUTHORITY HAVING JURISDICTION. | | | | | | PER NFPA 101 CH 7 MEANS OF ESCAPE | | | | | | 7.5.3 EXTERIORWAYS OF EXIT ACCESS | | | | | | 7.5.3.3 EXTERIOR EXIT ACCESS BALCONIES SHALL BE | | | SEPARATED FROM THE INTERIOR | | | OF THE BUILDING BY WALLS AND OPENING PROTECTIVES AS | | | REQUIRED FOR CORRIDORS, | | | UNLESS THE EXTERIOR EXIT ACCESS BALCONY IS SERVED BY AT | | | LEAST TWO | | | REMOTE STAIRS THAT CAN BE ACCESSED WITHOUT ANY OCCUPANT | | | TRAVELING PAST | | | AN UNPROTECTED OPENING TO REACH ONE OF THE STAIRS, OR | | | UNLESS DEAD ENDS | | | ON THE EXTERIOR EXIT ACCESS DO NOT EXCEED 20 FT | | | | | | 7.5.4 ACCESSIBLE MEANS OF EGRESS. | | | 7.5.4.1* AREAS ACCESSIBLE TO PEOPLE WITH SEVERE | | | MOBILITY IMPAIRMENT, | | | OTHER THAN IN EXISTING BUILDINGS, SHALL HAVE NOT LESS | | | THAN TWO ACCESSIBLE | | | MEANS OF EGRESS, UNLESS OTHERWISE PROVIDED IN 7.5.4.1.2 | | | THROUGH 7.5.4.1.4 | | | | | | 7.5.4.1.2 A SINGLE ACCESSIBLE MEANS OF EGRESS SHALL BE | | | PERMITTED FROM | | | BUILDINGS OR AREAS OF BUILDINGS PERMITTED TO HAVE A | | | SINGLE EXIT. | | | | | | 7.5.4.6 TO BE CONSIDERED PART OF AN ACCESSIBLE MEANS OF | | | EGRESS, A SMOKE | | | BARRIER IN ACCORDANCE WITH SECTION 8.5 WITH NOT LESS | | | THAN A 1-HOUR FIRE | | | RESISTANCE RATING, OR A HORIZONTAL EXIT IN ACCORDANCE | | | WITH 7.2.4, SHALL | | | DISCHARGE TO AN AREA OF REFUGE IN ACCORDANCE WITH | | | 7.2.12. | | | | | | | | | PERSONS IN WHEELCHAIRS/WALKERS HAVE THEIR SOLE MEANS OF | | | ESCAPE VIA THE RAMP. SHOULD FIRE BREACH THOSE WINDOWS, | | | THEIR ESCAPE IS BLOCKED. | | | | | | | | | PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED | | | NARRATIVE WITH CODE REFERENCES | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2021-08-31 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-08-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-08-31 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2021-08-31 14:17:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE INDICATION OF WHAT APPEARS TO BE SHOWER | | | HANDRAILS; HOWEVER, THERE ARE NO DETAILED INDICATIONS | | | OF MEETING THE REQUIRMENTS OF THE FIRE CODE. | | | | | | PER NFPA 101 | | | | | | 32.2.2.7 WHERE BATHTUBS, BATHTUB-SHOWER COMBINATIONS, | | | OR SHOWERS ARE | | | PRESENT, GRAB BARS SHALL BE PROVIDED IN ACCORDANCE WITH | | | THE PROVISIONS | | | OF 24.2.8. | | | | | | 24.2.8.2.1* BATHTUB END WALL VERTICAL GRAB BARS. END | | | WALL VERTICAL | | | GRAB BARS FOR BATHTUBS SHALL COMPLY WITH ALL OF THE | | | FOLLOWING: | | | (1) VERTICAL GRAB BARS SHALL HAVE A LENGTH OF NOT LESS | | | THAN 36 IN. | | | (914 MM). | | | (2) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 24 IN. | | | (610 MM) AND | | | 27 IN. (686 MM) ABOVE THE FINISHED FLOOR, MEASURED TO | | | THE LOWER END. | | | (3) VERTICAL GRAB BARS SHALL BE INSTALLED AT THE END | | | THAT IS LEAST OBSTRUCTED | | | FOR ENTRY AND EGRESS. | | | (4) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 9 IN. | | | (228 MM) AND | | | 12 IN. (305 MM) FROM THE OPEN ENTRY AND EGRESS SIDE OF | | | THE BATHTUB | | | OR BATHTUB-SHOWER COMBINATION, MEASURED HORIZONTALLY | | | FROM THE | | | EXTERIOR PLANE OF THE BATHTUB OR BATHTUB-SHOWER | | | COMBINATION. | | | | | | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE. | | | | | | | | | | | | | | | 2) THE PRIMARY MEAND OF ESCAPE FROM THE 2ND FLOOR DOES | | | NOT APPEAR TO MEET THE REQUIREMENTS OF UNENCLOSED ON | | | THE 1ST FLOOR. | | | | | | THE 1ST FLOOR PORTION HAS TO BE A 1/2 HOUR PROTECTED | | | ARE WITHOUT FURNITURE. | | | | | | 32.2.2.4.2 STAIRS SHALL COMPLY WITH 7.2.2.5.3. | | | 32.2.2.4.3 THE ENTIRE PRIMARY MEANS OF ESCAPE SHALL BE | | | ARRANGED SO THAT | | | OCCUPANTS ARE NOT REQUIRED TO PASS THROUGH A PORTION OF | | | A STORY ABOVE OR | | | A STORY BELOW, UNLESS THAT ROUTE IS SEPARATED FROM ALL | | | SPACES ON THAT STORY | | | BY CONSTRUCTION HAVING A MINIMUM 1?2-HOUR FIRE | | | RESISTANCE RATING. | | | 32.2.2.4.4 IN BUILDINGS OF CONSTRUCTION OTHER THAN TYPE | | | II(000), | | | TYPE III(200), OR TYPE V(000), THE SUPPORTING | | | CONSTRUCTION SHALL BE | | | PROTECTED TO AFFORD THE REQUIRED FIRE RESISTANCE RATING | | | OF THE SUPPORTED | | | WALL. | | | 32.2.2.4.5 STAIRS THAT CONNECT A STORY AT STREET LEVEL | | | TO ONLY ONE OTHER | | | STORY SHALL BE PERMITTED TO BE OPEN TO THE STORY THAT | | | IS NOT AT STREET LEVEL. | | | 32.2.2.4.6 IN BUILDINGS THREE OR FEWER STORIES IN | | | HEIGHT AND PROTECTED | | | BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH 32.2.3.5, | | | STAIR ENCLOSURES SHALL NOT BE REQUIRED, PROVIDED THAT | | | THERE STILL REMAINS | | | A PRIMARY MEANS OF ESCAPE FROM EACH SLEEPING AREA THAT | | | DOES NOT REQUIRE | | | OCCUPANTS TO PASS THROUGH A PORTION OF A LOWER FLOOR, | | | UNLESS THAT ROUTE | | | IS SEPARATED FROM ALL SPACES ON THAT FLOOR BY | | | CONSTRUCTION HAVING A MINIMUM | | | 1?2-HOUR FIRE RESISTANCE RATING. | | | 32.2.2.4.7 STAIRS SERVING A MAXIMUM OF TWO STORIES IN | | | BUILDINGS PROTECTED | | | WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN | | | ACCORDANCE WITH | | | 32.2.3.5 SHALL BE PERMITTED TO BE UNENCLOSED. | | | | | | ONE OF THE REQUIREMENTS OF THIS CODE TO USE AN | | | UNENCLOSED STAIR IS WITH PROMPT EVACUATION CAPABILITY. | | | | | | THE PROVISIONS OF 32/33.2.2.4.7 PERMIT A TWO-STORY OPEN | | | STAIR | | | (AND ITS ASSOCIATED EXPOSURE TO THE AREAS THAT ARE | | | OCCUPIED OR FURNISHED, | | | OR BOTH, ON THE GROUND FLOOR) TO SERVE AS PRIMARY MEANS | | | OF | | | ESCAPE FOR NEW SMALL FACILITIES AND EXISTING SMALL | | | FACILITIES (NOT | | | MORE THAN EIGHT RESIDENTS) WITH PROMPT EVACUATION | | | CAPABILITY, | | | PROVIDED THAT THE FACILITY IS SPRINKLERED USING | | | QUICK-RESPONSE OR | | | RESIDENTIAL SPRINKLERS. | | | | | | 32.1.5 ACCEPTABILITY OF MEANS OF EGRESS OR ESCAPE. NO | | | MEANS OF | | | ESCAPE OR MEANS OF EGRESS SHALL BE CONSIDERED AS | | | COMPLYING WITH THE | | | MINIMUM CRITERIA FOR ACCEPTANCE, UNLESS EMERGENCY | | | EVACUATION DRILLS | | | ARE REGULARLY CONDUCTED USING THAT ROUTE IN ACCORDANCE | | | WITH THE REQUIREMENTS | | | OF 32.7.3 | | | | | | 3.3.81.2 PROMPT EVACUATION CAPABILITY. THE ABILITY OF A | | | GROUP TO | | | MOVE RELIABLY TO A POINT OF SAFETY IN A TIMELY MANNER | | | THAT IS EQUIVALENT | | | TO THE CAPACITY OF A HOUSEHOLD IN THE GENERAL | | | POPULATION. | | | | | | A.3.3.81 EVACUATION CAPABILITY. THE EVACUATION | | | CAPABILITY OF THE | | | RESIDENTS AND STAFF IS A FUNCTION OF BOTH THE ABILITY | | | OF THE RESIDENTS TO | | | EVACUATE AND THE ASSISTANCE PROVIDED BY THE STAFF. IT | | | IS INTENDED THAT THE | | | EVACUATION CAPABILITY BE DETERMINED BY THE PROCEDURE | | | ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. IT IS ALSO INTENDED THAT | | | THE TIMING OF DRILLS, | | | THE RATING OF RESIDENTS, AND SIMILAR ACTIONS RELATED TO | | | DETERMINING THE | | | EVACUATION CAPABILITY BE PERFORMED BY PERSONS APPROVED | | | BY OR ACCEPTABLE | | | TO THE AUTHORITY HAVING JURISDICTION. THE EVACUATION | | | CAPABILITY CAN | | | BE DETERMINED BY THE USE OF THE DEFINITIONS IN 3.3.81, | | | THE APPLICATION OF | | | NFPA 101A CHAPTER 6, OR A PROGRAM OF DRILLS (TIMED). | | | EVACUATION DOES NOT INCLUDE THE RELOCATION OF OCCUPANTS | | | WITHIN A | | | BUILDING. | | | WHERE DRILLS ARE USED IN DETERMINING EVACUATION | | | CAPABILITY, IT IS | | | SUGGESTED THAT THE FACILITY CONDUCT AND RECORD FIRE | | | DRILLS SIX TIMES PER | | | YEAR ON A BIMONTHLY BASIS, WITH A MINIMUM OF TWO DRILLS | | | CONDUCTED | | | DURING THE NIGHT WHEN RESIDENTS ARE SLEEPING, AND THAT | | | THE FACILITY CONDUCT | | | THE DRILLS IN CONSULTATION WITH THE AUTHORITY HAVING | | | JURISDICTION. RECORDS | | | SHOULD INDICATE THE TIME TAKEN TO REACH A POINT OF | | | SAFETY, DATE AND TIME | | | OF DAY, LOCATION OF SIMULATED FIRE ORIGIN, ESCAPE PATHS | | | USED, AND COMMENTS | | | RELATING TO RESIDENTS WHO RESISTED OR FAILED TO | | | PARTICIPATE IN THE | | | DRILLS. | | | TRANSLATION OF DRILL TIMES TO EVACUATION CAPABILITY IS | | | DETERMINED AS | | | FOLLOWS: | | | (1) 3 MINUTES OR LESS ? PROMPT | | | (2) OVER 3 MINUTES, BUT NOT IN EXCESS OF 13 MINUTES ? | | | SLOW | | | (3) MORE THAN 13 MINUTES ? IMPRACTICAL | | | EVACUATION CAPABILITY, IN ALL CASES, IS BASED ON THE | | | TIME OF DAY OR | | | NIGHT WHEN EVACUATION OF THE FACILITY WOULD BE MOST | | | DIFFICULT, SUCH AS | | | WHEN RESIDENTS ARE SLEEPING OR FEWER STAFF ARE PRESENT. | | | EVACUATION CAPABILITY DETERMINATION IS CONSIDERED SLOW | | | IF THE FOLLOWING | | | CONDITIONS ARE MET: | | | (1) ALL RESIDENTS ARE ABLE TO TRAVEL TO CENTRALIZED | | | DINING FACILITIES WITHOUT | | | CONTINUOUS STAFF ASSISTANCE. | | | (2) THERE IS CONTINUOUS STAFFING WHENEVER THERE ARE | | | RESIDENTS IN THE | | | FACILITY. | | | | | | IT WOULD BE ANTICIPATED THAT THE EVACUATION TIME OF 3 | | | MINUTES WOULD BE FOR CLIENTS WITH NO OR LIMITED | | | PHYISCAL/MENTAL DISABILITES. | | | | | | PLEASE REVIEW AND PROVIDE DETAILS OF THE PROPOSED | | | CLIENTS AND THE ABILITY TO MEET THE PROMPT EVACUATION | | | OR CORRECT AND ENLCOSE THE STAIT EITHER AT THE TOP OR | | | THE BOTTOM. | | | | | | | | | | | | | | | 3) THERE ARE 2 EXTERIOR DOORS/GATES WITHIN THE EGRESS | | | TRAVEL PATH LEADING TO A PUBLIC WAY OR POINT OF SAFETY. | | | | | | 32.2.2.5.5 NO DOOR IN ANY MEANS OF ESCAPE, OTHER THAN | | | THOSE MEETING | | | THE REQUIREMENT OF 32.2.2.5.5.1, 32.2.2.5.5.2, OR | | | 32.2.2.5.5.3, SHALL BE | | | LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. | | | | | | PLEASE PROVIDE DETAILS INDICATING HOW THESE DOORS/GATES | | | WILL COMPLY WITH THE CODE. | | | | | | | | | | | | 4) THERE ARE INDICATIONS OF A 13D FIRE SPRINKLER | | | SYSTEM; HOWEVER, THERE IS ONLY 1 DOMESTIC WATER LINE | | | INDICATED. | | | | | | PER THE WATER UTILITIES DEPARTMENT, A DEDICATED WATER | | | SUPPLY AND WATER METER FOR A FIRE SPRINKLER SYSTEM IS | | | REQUIRED. | | | | | | PLEASE CONTACT THE WATER UTILITIES DEPARTMENT FOR THEIR | | | REQUIERMENTS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT | | | AND PROVIDE REVISION AS AND WHERE REQUIRED PRIOR TO | | | INSTALLATIONS. | | | | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-09 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-09 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-30 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-30 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2021-07-30 12:12:38 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21070558 | | | 7/30/2021 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE | | | LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON | | | THE EXTERIOR OF THE BUILDING- SECTIONS 305.1 & 624.1 | | | FBC FG. | | | | | | 2) P401 & P701: SHOW WH CONDENSATE LINES, | | | NEUTRALIZATION DEVICE AND CONDENSATE LINE DISPOSAL | | | LOCATIONS- SECTION 307.2 FBC FG. | | | | | | 3) P401 & P701: SUBMIT MANUFACTURER'S SPECIFICATIONS | | | FOR THE WATER HEATERS- SECTION 624.1 FBC FG. PROVIDE A | | | BASIC INSTALLATION DIAGRAM ON THE PLAN SHOWING THE | | | REQUIRED CLEARANCES FROM THE UNITS TO GRADE, OVERHEAD | | | CONSTRUCTION AND TO THE ADJACENT WINDOW OPENING- WATER | | | HEATER- SECTIONS 624.1 & 503.8 FBC FG. | | | | | | 4) P601 OR P602: PLEASE PROVIDE A GAS RISER DRAWING- | | | SECTION 107.3.5.1.3 WPB. PLEASE NOTE THE GAS DEMAND | | | SCHEDULE INDICATES 1-INCH PE BRANCHES TO THE WATER | | | HEATERS THAT ARE UNDERSIZED USING THE LONGEST LENGTH | | | METHOD AND THE SPECIFIED SIZING TABLE 402.4(21) FBC FG | | | AND SECTION 402.4.1 FBC FG. GAS RISER: | | | | | | A) TYPE OF GAS- NATURAL OR LP. | | | B) DELIVERY PRESSURE AT THE METER. | | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | D) TYPES AND SIZES OF PIPING. | | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | | UNIONS. | | | H) OUTLET PRESSURES AT REGULATORS. | | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | J) PIPE SIZING TABLES. | | | | | | 5) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE | | | GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR | | | FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES. | | | | | | 6) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR | | | INSTALLATION OF THE GENERATOR- SECTION 105.1 & 107.2.1 | | | WPB, HOWEVER, IN ORDER TO PERFORM A COMPLETE GAS REVIEW | | | AT THIS TIME PLEASE SUBMIT A CUT SHEET FOR THE | | | GENERATOR SHOWING THE BTUH LOAD AND INPUT PRESSURE- | | | SECTIONS 305.1 & 402.2 FBC FG. | | | | | | 7) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-04-26 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-04-08 |
Time |
06:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-25 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-08 |
Time |
07:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-12-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2021-11-18 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-09-01 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-20 |
Time |
06:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-09-01 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-01 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2021-09-01 12:34:09 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | 2021-08-16 17:36:06 | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-25 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-25 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-12-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-02 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-02 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2021-12-02 08:24:10 | REVISED SHEET M701 WAS NOT SUBMITTED IN THIS CYCLE AND | | | THERE IS NO DETAIL 5 ON THE ORIGINAL DRAWING. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-08-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-04 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-04 |
Time |
06:42 |
Sent To |
|
|
| Notes |
| 2021-08-04 06:58:32 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21070558 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC | | | 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS (DIGITALLY SIGNED BY THE ENGINEER) FBC EC | | | R403.7.1 | | | | | | 3) PLEASE SHOW THE TIE DOWN METHOD FOR THE CONDENSING | | | UNITS. FBC RES M1307.2 | | | | | | 4) PLEASE SHOW THE CONDENSATION DRAINS AND THE | | | TERMINATION LOCATION. FBC RES M1411.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-02-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-18 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-18 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-09 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-09 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2021-12-09 13:21:17 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT-21070558 | | | 12/9/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS 2-8 LISTED BELOW | | | WERE NOT ADDRESSED. THE CORRECTED PLANS WERE NOT | | | UPLOADED FOR REVIEW. | | | | | | 2) P301, P302, & P601: PROVIDE 3-INCH DRAIN STACKS AND | | | BRANCH DRAINS FOR THE WASHING MACHINES (WM-1)- SECTION | | | 406.2 FBC P. PLEASE NOTE THE A/P601 STACK CONTINUATION | | | IS UNDERSIZED. | | | | | | 3) P301 & P601: PROVIDE A FLOOR DRAIN FOR THE ICE | | | MACHINE (IM-1) IF REQUIRED BY MANUFACTURER?S | | | SPECIFICATIONS (NOT PROVIDED)- SECTION 412.2 FBC P. | | | | | | 4) P301 & P601: SHOW THE LOCATION OF THE REQUIRED | | | CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND | | | SEWER- SECTION 708.1.2 FBC P. | | | | | | 5) P401 & P602: SHOW THE LOCATIONS OF THE MAIN WATER | | | DISTRIBUTION SHUTOFF VALVES FOR EACH DWELLING UNIT- | | | SECTION 606.1 (2) (6) FBC P. | | | | | | 6) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE | | | LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON | | | THE EXTERIOR OF THE BUILDING- SECTION 502.1 FBC P. | | | | | | 7) P401, P402, P602, P701: THE HWR LINE IS NOT SHOWN IN | | | THE WATER HEATER DETAIL- SECTION 607.2 FBC P. PLEASE | | | PROVIDE HOT WATER PIPIE INSULATION DETAILS- THICKNESS | | | AND R-VALUE- TABLE C403.2.10 FBC EC. | | | | | | 8) P701: THE LOCATION OF THE EXPANSION TANK FOR THE | | | TANKLESS WATER HEATER MUST BE IN ACCORDANCE WITH | | | MANUFACTURER'S SPECIFICATIONS WHICH HAVE NOT BEEN | | | PROVIDED- SECTION 502.1 FBC P. PLEASE NOTE THAT | | | EXPANSION TANKS FOR STORAGE TYPE WATER HEATERS SHALL BE | | | LOCATED DOWNSTREAM OF ALL CHECK VALVES AND PRESSURE | | | REDUCING VALVES- SECTION 607.3 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-30 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-29 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2021-07-30 11:14:55 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21070558 | | | 7/30/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A1.10 & P000: THE CODE RESEARCH DATA ON A1.10 | | | INDICATES THE USE AND OCCUPANCY OF THE BUILDING TO BE | | | R3 WITH COMPLIANCE UNDER THE FBC RES. 2020, HOWEVER IT | | | IS ALSO INDICATING COMPLIANCE WITH THE FBC | | | ACCESSIBILITY CODE WHICH IS NOT COVERED IN THE | | | RESIDENTIAL CODE. THE PLUMBING COMPLIANCE DATA UNDER | | | NOTE #1 (P000) INDICATES COMPLIANCE WITH THE FBC | | | PLUMBING WHICH IS THE COMMERCIAL CODE. DUE TO THESE | | | CONFLICTS THE FOLLOWING REVIEW WILL BE CONDUCTED WITH | | | THE MOST STRINGENT CODES APPLIED. | | | | | | 2) P301, P302, & P601: PROVIDE 3-INCH DRAIN STACKS AND | | | BRANCH DRAINS FOR THE WASHING MACHINES (WM-1)- SECTION | | | 406.2 FBC P. PLEASE NOTE THE A/P601 STACK CONTINUATION | | | IS UNDERSIZED. | | | | | | 3) P301 & P601: PROVIDE A FLOOR DRAIN FOR THE ICE | | | MACHINE (IM-1) IF REQUIRED BY MANUFACTURER?S | | | SPECIFICATIONS (NOT PROVIDED)- SECTION 412.2 FBC P. | | | | | | 4) P301 & P601: SHOW THE LOCATION OF THE REQUIRED | | | CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND | | | SEWER- SECTION 708.1.2 FBC P. | | | | | | 5) P401 & P602: SHOW THE LOCATIONS OF THE MAIN WATER | | | DISTRIBUTION SHUTOFF VALVES FOR EACH DWELLING UNIT- | | | SECTION 606.1 (2) (6) FBC P. | | | | | | 6) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE | | | LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON | | | THE EXTERIOR OF THE BUILDING- SECTION 502.1 FBC P. | | | | | | 7) P401, P402, P602, P701: THE HWR LINE IS NOT SHOWN IN | | | THE WATER HEATER DETAIL- SECTION 607.2 FBC P. PLEASE | | | PROVIDE HOT WATER PIPIE INSULATION DETAILS- THICKNESS | | | AND R-VALUE- TABLE C403.2.10 FBC EC. | | | | | | 8) P701: THE LOCATION OF THE EXPANSION TANK FOR THE | | | TANKLESS WATER HEATER MUST BE IN ACCORDANCE WITH | | | MANUFACTURER'S SPECIFICATIONS WHICH HAVE NOT BEEN | | | PROVIDED- SECTION 502.1 FBC P. PLEASE NOTE THAT | | | EXPANSION TANKS FOR STORAGE TYPE WATER HEATERS SHALL BE | | | LOCATED DOWNSTREAM OF ALL CHECK VALVES AND PRESSURE | | | REDUCING VALVES- SECTION 607.3 FBC P. | | | | | | 9) P701: PLEASE PROVIDE A SHOWER FLOOR AND LINER | | | DETAIL- SECTION 417.5.2 FBC P. | | | | | | 10) SHEET A-410 ACCESSIBLE PLUMBING FIXTURE DETAILS | | | MISSING PER FBC ACC- | | | A) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE WATER | | | CLOSETS- SECTION 604.3. | | | B) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE | | | LAVATORIES- SECTION 606.2. | | | C) TURNING SPACE DIAMETER DIMENSION SECTION 304.3. | | | D) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE SHOWER- | | | SECTION 608.2.1 | | | E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE ACCESSIBLE SHOWERS- SECTION 608.3.2. | | | PLEASE SEE FIGURE 608.3.2 AND CORRECT THE DRAWING. | | | F) VERTICAL GRAB BARS ARE NOT IN COMPLIANCE WITH | | | SECTION 609.4 WHICH REQUIRES GRAB BARS TO BE INSTALLED | | | IN HORIZONTAL POSITIONS. | | | G) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE | | | SHOWER- SECTION 608.5.2. WHERE A SEAT IS PROVIDED, THE | | | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE | | | INSTALLED ON THE BACK WALL ADJACENT TO THE SEAT WALL | | | AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM THE SEAT | | | WALL. | | | H) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. | | | SPECS WERE NOT INCLUDED IN THE FIXTURE SCHEDULE ON | | | P801. | | | I) ACCESSIBLE SHOWER SEAT DETAILS AND FIGURES- SECTIONS | | | 610.3 & 610.3.2. | | | | | | 11) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION | | | 105.1 FBC P. | | | | | | 12) PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR | | | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE | | | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1WPB | | | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL | | | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS | | | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-09 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-09 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2021-12-09 13:15:05 | SEPARATE PERMIT AND PLANS REQUIRED FOR THE IRRIGATION | | | SYSTEM. |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-30 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-30 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2021-07-30 11:20:14 | 1ST REVIEW FBC-2020 IRRIGATION | | | PERMIT- 21070558 | | | 7/30/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE IRRIGATION PLANS- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-08 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-08 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-09-01 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-01 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2021-09-01 12:34:36 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-24 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-24 |
Time |
12:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-09 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-09 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-09-01 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-01 |
Time |
12:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-04-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-04-15 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-15 15:25:57 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED | | | PRIOR TO ZONING APPROVAL OF THIS PERMIT. TO DATE, A | | | LANDSCAPE PERMIT HAS NOT BEEN SUBMITTED. | | | | | | [7/27/21 AND 2/16/21 REPEAT COMMENT: NOT ADDRESSED. | | | STAFF IS STILL WAITING ON THE SUBMISSION OF A LANDSCAPE | | | PERMIT.] | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING, | | | ETC. | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | | | | * ZONING APPROVAL TO USE PROPERTY AS A GROUP HOME | | | SIGNED BY AV. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-02-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-02-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-02-16 10:32:24 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) SIDE CORNER SETBACK HAS BEEN CHANGED AND DOES NOT | | | MEET THE MINIMUM CORNER SIDE SETBACK PER THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDRS). A MINIMUM OF 12.5 | | | FT. SIDE CORNER SETBACK IS REQUIRED ALONG MANNING | | | AVENUE. [ZLDR S.94-72(A.)] | | | | | | 2.) SHOW HEIGHT OF THE BUILDING FROM GRADE (NOT FFE) TO | | | THE HIGHEST POINT OF THE STRUCTURE. THE BUILDING CANNOT | | | EXCEED 30 FT. IN HEIGHT. [ZLDR S.94-72(A)] | | | | | | 3.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED | | | PRIOR TO ZONING APPROVAL OF THIS PERMIT. TO DATE, A | | | LANDSCAPE PERMIT HAS NOT BEEN SUBMITTED. [REPEAT | | | COMMENT: STAFF IS STILL WAITING ON THE SUBMISSION OF A | | | LANDSCAPE PERMIT.] | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING, | | | ETC. | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | | | | * ZONING APPROVAL TO USE PROPERTY AS A GROUP HOME | | | SIGNED BY AV |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-12-08 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-12-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-12-08 16:18:24 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) HAS THE PROPOSED USE RECEIVED (PRELIMININARY) | | | APPROVAL FOR THE PROPERTY TO BE UTLIZED AS A GROUP HOME | | | AS SPECIFIED IN THE PLANS? | | | | | | 2.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED | | | PRIOR TO ZONING APPROVAL OF THIS PERMIT. TO DATE, A | | | LANDSCAPE PERMIT HAS NOT BEEN SUBMITTED. | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING, | | | ETC. | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-27 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-07-27 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2021-07-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-27 15:57:36 | | | | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) ALTHOUGH PROVIDED IN THE SITE DATA TABULAR, PLEASE | | | PROVIDE BUILDING SETBACK DIMENSIONS IN THE SITE PLAN TO | | | DEMONSTRATE COMPLIANCE WITH THE ZLDRS AND CONSISTENCY | | | WITH THE INFORMATION PROVIDED IN THE TABULAR. | | | | | | 2.) PROVIDE SETBACK DIMENSIONS FROM THE PROPOSED | | | MECHANICAL EQUIPMENT PAD (FOR GENERATOR AND A/C | | | COMPRESSOR UNITS) TO THE PROPERTY LINE(S). PLEASE NOTE | | | THAT PER ZLDR S.94-305(B)(4), THE PAD CANNOT PROJECT | | | MORE THAN 4 FT. INTO A REQUIRED SETBACK. THE DIMENSIONS | | | ARE REQUIRED TO DEMONSTRATE COMPLIANCE. | | | | | | 3.) PROVIDE CALCULATIONS IN THE SITE PLAN THAT | | | DEMONSTRATES THAT THERE IS A MINIMUM OF 1,000 SQ. FT. | | | OF LANDSCAPED AREA WITHIN THE REQUIRED FRONT SETBACK | | | (AREA WITHIN THE FIRST 25 FT. OF 54TH STREET). [ZLDR | | | S.94-442(C)(2)] | | | | | | 4.) DRIVEWAY SHALL BE SETBACK A MINIMUM OF 3 FT. FROM | | | THE REAR AND CORNER SIDE PROPERTY LINE. [ZLDR | | | S.94-482(D)] | | | | | | 5.) DRIVEWAY CANNOT EXCEED 20 FT. IN WIDTH AT THE | | | PROPERTY LINE. PROVIDE DIMENSIONS TO DEMONSTATE | | | COMPLIANCE. [ZLDR S.94-312(1)] | | | | | | 6.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED | | | PRIOR TO ZONING APPROVAL OF THIS PERMIT. | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING, | | | ETC. | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 |
|
|