Plan Review Details - Permit 21070537
Plan Review Stops For Permit 21070537
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-09-24 Cont ID  
Sent By shill Date 2021-09-24 Time 16:33 Rev Time 0.00
Received By shill Date 2021-09-24 Time 16:33 Sent To  
Notes
2021-09-24 16:33:29PROVISO - ADDRESS PLUMBING COMMENTS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-07 Cont ID  
Sent By shill Date 2021-09-07 Time 14:42 Rev Time 0.00
Received By shill Date 2021-09-07 Time 14:42 Sent To  
Notes
2021-09-07 14:45:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SCOPE NOT CLEAR. A LETTER WAS SUBMITTED STATING THAT
 THE BUILDING ALLOWED THE CONTRACTOR TO REMOVE THE
 EXISTING FLOORING INSTALLED WITHOUT A PERMIT AND THAT
 THE NEW OWNER DOESN'T WANT A WOOD FLOOR.
  
 REMOVAL OF THE FLOOR REQUIRES A PERMIT. THE BUILDING
 MANAGEMENT DOES NOT ISSUE PERMITS.
  
 IS THE SCOPE OF THIS APPLICATION TO REMOVE THE EXISTING
 FLOOR, FLOOR TO BE INSTALLED UNDER SEPARATE PERMIT? IF
 YES, SUBMIT A NEW PERMIT APPLICATION.
  
 FBC 107
  
 2. WHISPERMAT CS DOES NOT HAVE A FLAME SPREAD TEST FOR
 WOOD. IF YOU PROPOSE TO INSTALL THIS PRODUCT, PLEASE
 ADVISE IF THE WHISPERMAT UNDER WOOD IS FIXED TO THE
 FLOOR OR IF IT IS FLOATING.
  
 SEE PREVIOUS LIST FOR CODE REFERENCES, TEST REPORTS
 REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 08:57 Rev Time 0.00
Received By shill Date 2021-07-21 Time 08:57 Sent To  
Notes
2021-07-21 08:58:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FOR THE UNDERLAYMENT, PROVIDE THE FOLLOWING TEST
 REPORTS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-01 Cont ID  
Sent By pleduc Date 2021-09-01 Time   Rev Time 0.00
Received By pleduc Date 2021-09-01 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By pleduc Date 2021-07-14 Time   Rev Time 0.00
Received By pleduc Date 2021-07-14 Time 15:22 Sent To  
Notes
2021-07-14 15:45:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF FLOOR UNDERLAYMENT AND WOOD
 FLOORING BUT NO SPECIFICATIONS SHEETS THAT INDICATE
 MEETING THE REQUIREMENTS PER NFPA'
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
  
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE FLOORING PRODUCT SPEC SHEETS.
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-07 Cont ID  
Sent By lcrespo Date 2021-10-07 Time 12:24 Rev Time 0.00
Received By lcrespo Date 2021-09-22 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-16 Cont ID  
Sent By lcrespo Date 2021-09-16 Time 15:42 Rev Time 0.00
Received By lcrespo Date 2021-08-31 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 08:58 Rev Time 0.00
Received By shill Date 2021-07-13 Time 08:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-07 Cont ID  
Sent By lcrespo Date 2021-10-07 Time 12:23 Rev Time 0.00
Received By lcrespo Date 2021-10-07 Time 12:23 Sent To  
Notes
2021-10-07 12:23:3710/07/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-16 Cont ID  
Sent By lcrespo Date 2021-09-16 Time 15:41 Rev Time 0.00
Received By lcrespo Date 2021-09-16 Time 15:07 Sent To  
Notes
2021-09-16 15:41:4809/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BUILDING WAS CONSTRUCTED UNDER THE FAIR HOUSING
 ACT. PLEASE INDICATE ON PLANS WHICH DESIGN
 SPECIFICATION ( ?A? OR ?B? OF THE ACT) WAS USED IN THE
 ORIGINAL DESIGN OF THESE UNITS. TELL US WHICH USABLE
 BATHROOM IN THE DWELLING UNITS, THE ALTERATION THAT IS
 PROPOSED IN THE BATHROOM SHALL ALSO BE IN COMPLIANCE
 WITH THE FAIR HOUSING ACT. THIS NEEDS TO BE DETERMINED
 BY RESEARCHING WHEN THE BUILDING WAS BUILT AND
 REQUESTING PLANS FROM THIS CITY'S WEBSITE. THIS MAY
 INCUR A FEE AND TIME TO RETRIEVE ALL THIS INFORMATION
 AND DETERMINE IF THE LEVEL OF ACCESSIBILITY IS ALTERED.
 WE REQUIRE TO SHOW THE DIMENSION OF THE CLEAR FLOOR
 SPACE IN THE BATHROOM IN FRONT OF EACH FIXTURE IN THAT
 BATHROOM.
  
 2. BY LOOKING AND THE PLANS SUBMITTED IN THIS CASE THE
 BATHROOM LOOKS LIKE SPECIFICATION A WHICH REQUIRE A
 FORWARD APPROACH TO THE TUB. THE SHOWER REQUIRES A
 PARALLEL APPROACH TO IT WHICH ARE USUALLY TYPE B AND
 THAT IS 30 INCHES BY 48 INCHES AND THE TOILET MAY NOT
 ALLOW THAT. IN THE FAIR HOUSING ACT THE ALTERATION DOES
 NOT ALLOW TO CHANGE THE TYPE OF RESTROOM FROM IT
 ORIGINAL DESIGN.
  
 3. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR THE CHANGING OF AN FHA
 COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD
 ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT
 MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT BACK TO
 COMPLIANCE AT THE TIME OF SALE IF SO, REQUESTED BY THE
 BUYER. THIS WILL BE IN A LETTER TYPE FORMAT SIGNED AND
 NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER AND
 IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF THE
 CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN
 EMAIL TO [email protected] AND I WILL SEND A COPY OF THE
 FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 08:58 Rev Time 0.00
Received By shill Date 2021-07-21 Time 08:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-07-15 Cont ID  
Sent By ajones Date 2021-07-15 Time 15:17 Rev Time 0.00
Received By ajones Date 2021-07-15 Time 15:17 Sent To  
Notes
***NONE***