Plan Review Details - Permit 21070505
Plan Review Stops For Permit 21070505
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By cpuell Date 2021-07-13 Time 13:14 Rev Time 0.00
Received By cpuell Date 2021-07-13 Time 13:14 Sent To  
Notes
2021-08-28 08:41:43T.LARGE ENTERED NAME BY MISTAKE.
2021-07-13 13:16:03ADDRESS CORRECT, HOWEVER ABOVE THE MAIN ENTRANCE THE
 ADDRESS OF 460 SOUTH ROSEMARY AVE SUITE 170E PLEASE
 REMOVE THE E FROM ABOVE THE DOOR.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 14:07 Rev Time 0.00
Received By ccole Date 2021-10-22 Time 14:06 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-10-13 Cont ID  
Sent By rmcphers Date 2021-10-13 Time 07:41 Rev Time 0.00
Received By rmcphers Date 2021-10-13 Time 07:41 Sent To  
Notes
2021-10-13 07:41:41PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-02 Cont ID  
Sent By rmcphers Date 2021-09-02 Time 08:30 Rev Time 0.00
Received By rmcphers Date 2021-09-01 Time 15:36 Sent To  
Notes
2021-09-02 08:35:34PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-06 Cont ID  
Sent By rmcphers Date 2021-12-06 Time 16:27 Rev Time 0.00
Received By rmcphers Date 2021-12-06 Time 16:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-22 Cont ID  
Sent By rmcphers Date 2021-11-22 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2021-11-22 Time 15:06 Sent To  
Notes
2021-11-22 15:09:50BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB
 CHAPTER 1 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE EXTERIOR WALL FRAMING DETAILS -
 SHOW FRAMING DESIGNATION, ON CENTER SPACING, ATTACHMENT
 TYPE AND ON CENTER SPACING OF THE ATTACHMENTS ETC.- FBC
 WPB 107.2.4
  
 DEFERRED SUBMITTALS WILL NEED TO BE LISTED ON THE
 DRAWINGS - FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-13 Cont ID  
Sent By rmcphers Date 2021-10-13 Time 07:39 Rev Time 0.00
Received By rmcphers Date 2021-10-12 Time 16:39 Sent To  
Notes
2021-10-12 17:00:18BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB
 CHAPTER 1 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE EXTERIOR WALL FRAMING DETAILS -
 SHOW FRAMING DESIGNATION, ON CENTER SPACING, ATTACHMENT
 TYPE AND ON CENTER SPACING OF THE ATTACHMENTS ETC.- FBC
 WPB 107.2.4
  
 2) PLEASE SHOW THE EXTERIOR CLADDING DETAILS -
 ATTACHMENT TYPE AND ON CENTER SPACING OF THE
 ATTACHMENTS OR PROVIDE A PRODUCT APPROVAL FOR THE
 EXTERIOR CLADDING. FBC 1405.11.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-02 Cont ID  
Sent By rmcphers Date 2021-09-02 Time 08:31 Rev Time 0.00
Received By rmcphers Date 2021-09-01 Time 15:36 Sent To  
Notes
2021-09-02 08:30:34BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB
 CHAPTER 1 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS THAT ARE
 LISTED ON THE DRAWINGS.
 2) EXTERIOR WALL (EWS02) - PLEASE PROVIDE EFIS
 ATTACHMENT DETAILS - PLEASE SHOW THE STRUCTURAL BACKING
 FOR THE EFIS IF REQUIRED FBC 1408.3 STRUCTURAL DESIGN.
 THE UNDERLYING STRUCTURAL FRAMING AND SUBSTRATE SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST LOADS AS REQUIRED
 BY CHAPTER 16.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-12 Cont ID  
Sent By jleahy Date 2021-10-12 Time 16:11 Rev Time 0.00
Received By jleahy Date 2021-10-12 Time 16:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-25 Cont ID  
Sent By jleahy Date 2021-08-25 Time 16:19 Rev Time 0.00
Received By jleahy Date 2021-08-25 Time 15:32 Sent To  
Notes
2021-08-25 16:25:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-102
  
 GFCI PROTECTION OF KITCHEN OUTLETS PER 210.8(B)(2)
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100
 AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL.
  
 PAGE E-103
  
 FAULT CURRENT CALCULATION REQUIRED FOR SERVICE AND
 PANELS PER 110.9, 110.10

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-10-13 Cont ID  
Sent By pleduc Date 2021-10-13 Time   Rev Time 0.00
Received By pleduc Date 2021-10-13 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-07-26 Cont ID  
Sent By pleduc Date 2021-07-26 Time   Rev Time 0.00
Received By pleduc Date 2021-07-21 Time 10:42 Sent To  
Notes
2021-07-26 11:02:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) LIFE SAFETY SHEET - THE OCCUPANCY LOAD TOTAL FOR
 DINING INDICATES 43. OUTSIDE SEATING SHALL NOT NE
 INCLUDED IN THE OCCUPANCY TOTAL.
  
 630/15= 42
  
 PLEASE CORRECT.
  
  
 1A) LIFE SAFETY SHEET - THE OCCUPANCY LOAD COUNT OF 42
 APPEARS TO BE TOO LARGE FOR THIS AREA. THERE ARE
 APPROX. 16 CHAIRS AND 6 BAR STOOLS INDICATED = 22. HOW
 WOULD 20 MORE CHAIRS FIT?
  
 PLEASE PROVIDE DIMENSIONS OF HOW THE 630SQ FT IS
 CALCULATED.
  
  
 1B) AS THIS IS A PROPOSED DONUT SHOP, IT WOULD APPEAR
 THAT WALKIN SERVICE AND STANDING ROOM IS REQUIRED.
  
 THAT AREA OCCUPANCY LOAD WOULD BE CLACULATED AT 7SQ
 FT/PERSON, NOT 15 FOR THE SEATING AREA.
  
 PLEAE EVIEW AND INDICATED DESIGNATED AREA AND CORRECT.
  
  
  
 2) LIFE SAFETY SHEET - THE BAR COUNT INDICATES 2,
  
 THERE ARE 6 BAR STOOLS INDICATED.
  
 PLEASE CORRECT OR EXPLAIN.
  
  
  
 3) LIFE SAFETY SHEET - THERE IS AN INDICATION UNDER
 GENERAL NOTES #6 & 15; SEE FIRE PROTECTION DRAWINGS FOR
 SPRINKLER LAYOUT.
  
 THIS OCCUPNACY HAS AN EXISTING SPRINKLER PROTECTION
 WITH ODIFICATION BEING REQUIRED.
  
 ANY AND ALL WORK, INCLUDING DEMO, ON THE FIRE SPRINKLER
 SYSTEM SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) THERE ARE INDICATIONS OF HOOD INSTALLATION.
  
 ANY AND ALL WORK ON THE HOOD SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) ELECTRICAL - THERE ARE INDICATIONS OF FIRE ALARM
 DEVICES..
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-10-13 Cont ID  
Sent By pleduc Date 2021-10-13 Time   Rev Time 0.00
Received By pleduc Date 2021-07-21 Time 16:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-11-24 Cont ID  
Sent By ccole Date 2021-11-24 Time 12:57 Rev Time 0.00
Received By ccole Date 2021-11-23 Time 17:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 14:00 Rev Time 0.00
Received By ccole Date 2021-10-21 Time 12:19 Sent To  
Notes
2021-10-22 14:01:122ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070505
 10/22/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC.
  
 PLAN REVIEW RESULTS: DENIED
 FAILED COMMENT #5 IS LISTED BELOW WITH ADDITONAL NOTES
 IN CAP LETTERS.
  
 5) FAILED. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE
 GAS APPLIANCES. FBC-FUEL GAS SEC. 304.1. WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3. I
 WAS NOT ABLE TO LOCATE THE COMBUSTION AIR CALCULATIONS.
 PLEASE INDICATE IN THE RESPONSE NARRATIVE WHICH PLAN
 SHEET SHOWS THE COMBUSTION AIR CALCS AND METHOD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-28 Cont ID  
Sent By tklarge Date 2021-08-28 Time 08:40 Rev Time 0.00
Received By tklarge Date 2021-08-28 Time 07:16 Sent To  
Notes
2021-08-28 07:31:371) SUBMIT THE SIZING TABLE FOR THE PE PIPE FROM THE
 2020 FBC-FUEL GAS CODE. WPB AMEND. TO BC SEC. 107.2.1.
 2) THE 3/4 INCH METALLIC LINE IS UNDERSIZED TO THE TWO
 GAS APPLIANCES. THE SYSTEM IS CAPABLE OF HANDLING A
 MAXIMUM 83 MBTU AT A DISTANCE OF 150 FEET DEVELOPED
 LENGTH. THE PIPING SHALL BE INCREASED TO 1 INCH PER
 FBC-FUEL GAS TABLE 402.4 (2).
 3) A SEPARATE PERMIT IS REQUIRED FOR THE GAS. PLACE A
 NOTE TO THIS EFFECT ON THE PLAN.
 4) SUBMIT COPIES OF THE GAS EQUIPMENT PECIFICATIONS.
 ALL GAS EQUIPMENT/ APPLIANCES SHALL BE LISTED AND
 LABELED PER FBC-FUEL GAS SEC.301.3.
 5) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. FBC-FUEL GAS SEC. 304.1. WHERE COMBUSTION
 AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3.
 6) SHT. P-102. THE PLAN SHOWS THE GAS LINE LABELED AS
 GW. CLARIFY
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-06 Cont ID  
Sent By rmcphers Date 2021-12-06 Time 16:27 Rev Time 0.00
Received By rmcphers Date 2021-12-06 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-11-24 Time   Rev Time 0.00
Received By lmarchan Date 2021-11-03 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-10-22 Time   Rev Time 0.00
Received By aoliver Date 2021-09-23 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-02 Cont ID  
Sent By rmcphers Date 2021-09-02 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2021-07-21 Time 05:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-17 Cont ID  
Sent By lmarchan Date 2021-12-17 Time 12:15 Rev Time 0.00
Received By lmarchan Date 2021-12-10 Time 08:47 Sent To  
Notes
2021-12-16 13:26:04RECEIPT MU-2021-058365 - $102.82 PAID
2021-12-10 08:48:4512/10/21 EMAILED IMPACT FOR REVIEW-AO
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-09-02 Cont ID  
Sent By rmcphers Date 2021-09-02 Time 08:31 Rev Time 0.00
Received By rmcphers Date 2021-09-02 Time 08:31 Sent To  
Notes
2021-09-02 08:32:33PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-10-06 Cont ID  
Sent By medwards Date 2021-10-06 Time 16:43 Rev Time 0.00
Received By medwards Date 2021-10-06 Time 16:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 15:54 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 15:54 Sent To  
Notes
2021-08-20 15:55:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070505
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, DRAWINGS AND REVIEW. THE KITCHEN HOODS
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 REFRIGERATION SYSTEMS WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, DRAWINGS AND REVIEW. THE REFRIGERATION
 SYSTEMS WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) SHEET -M-102: PLEASE BE MORE SPECIFIC WITH THE USE
 OF SPACE FOR THE OUTDOOR AIR CALCULATIONS. USING FBC M
 403.3.1.1 AND TABLE 403.3.1.1 AND USING KITCHEN AND
 DINING ROOM AS THE USE OF SPACES. THE REQUIRED OUTDOOR
 AIR AND KITCHEN EXHAUST IS BELOW:
 KITCHEN- 214 CFM OF OUTDOOR AIR; KITCHEN 550 CFM OF
 EXHAUST; BAR- 211 CFM OF OUTDOOR AIR; DINING- 471 CFM
 OF OUTDOOR AIR.
  
 4) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 COMPLETE MECHANICAL SYSTEM. FBC 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-11-24 Cont ID  
Sent By ccole Date 2021-11-24 Time 15:30 Rev Time 0.00
Received By ccole Date 2021-11-23 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 13:26 Rev Time 0.00
Received By ccole Date 2021-10-21 Time 12:19 Sent To  
Notes
2021-10-22 13:27:562ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21070505
 10/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTED IN
 CAP LETTERS.
  
 8) FAILED. BOTH TOILET ROOMS SHALL BE FULLY ACCESSIBLE
 AND COMPLY WITH FBC-ACCESS. SEC.213.2. SHOW FULL
 COMPLIANCE FOR TOILET ROOM #104 ON THE PLANS. THE
 ARCHITECT IS REFERRING TO SECTION 213.2 EXCEPTION 4 FOR
 CLUSTERED TOILET ROOMS. THE TOILET ROOMS DO NOT APPEAR
 TO MEET THE EXCEPTION BECAUSE IT STATES ?NOT MORE THAN
 50 PERCENT OF THE SINGLE USE TOILET ROOMS FOR EACH USE
 AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603.
 IT APPEARS THE INTENT OF THE SECTION WAS TO ALLOW
 ADDITIONAL TOILET ROOMS OVER AND ABOVE THE MINIMUM
 REQUIREMENTS TO NOT BE ACCESSIBLE WHEN CLUSTERED
 TOGETHER. BASED ON THE 48 OCCUPANT LOAD TWO SEPARATE
 TOILET ROOMS WERE REQUIRED TO BE INSTALLED- ONE F0R
 MALE AND ONE FOR FEMALE USE (EACH USE). THE FACT THAT
 THE PLUMBING CODE WHICH IS A COMPLETELY SEPARATE CODE
 VOLUME ALLOWS THOSE ROOMS TO BE LABELED UNISEX DOES NOT
 APPEAR TO EXEMPT ONE OF THE ROOMS FROM BEING ACCESSIBLE
 AS REQUIRED BY 213.2. IF THE INTENT IS TO STAY WITH
 THIS DESIGN PLEASE PROVIDE A SIGNED AND SEALED LETTER
 FROM THE ARCHITECT OF RECORD PROVIDING EVIDENCE THAT
 THE INTENT OF THE CODE IS BEING MET- SECTION 107.1 WPB
 12) FAILED. SHT. A-400 - DETAIL #9 - THE DOOR SWINGS
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY AND WATER
 CLOSET IN BOTH TOILET ROOMS. COMPLY WITH FBC-ACCESS.
 SEC.603.2.3. TOILET ROOM DOORS ARE NOT PERMITTED TO
 SWING INTO THE CLEAR FLOOR SPACES PROVIDED FOR
 FIXTURES. APPROVAL OF THE DOOR SWINGING INWARD WILL
 DEPEND ON APPROVAL OF THE ROOM AS NON-ACCESSIBLE.
  
 15) FAILED. A HOT WATER RECIRCULATION LINE WILL BE
 REQUIRED PER FBC-PLUMBING SEC.607.2. IN ACCORDANCE WITH
 SECTION C404.5.1 AND TABLE C404.5.1 THE MAXIMUM PIPING
 LENGTH FOR A ?-INCH HOT WATER LINE SUPPLYING A PUBLIC
 LAVATORY IS 2 FT. THE DESIGNER MUST DECIDE TO EITHER
 SPECIFY POINT OF USE WATER HEATERS AT THE LAVATORIES OR
 PROVIDE A RECIRCULATION PUMP FOR THE HW SYSATEM. PLEASE
 NOTE THAT SECTION 419.5 OF THE FBC P ALLOWS EITHER
 TEMPERED OR COLD WATER TO BE SUPPLIED TO A LAVATORY.
  
 16) FAILED. SHT.P-101 - INDICATE ON THE PLAN WHAT
 STANDARD WAS USED IN THE SIZING OF THE GREASE
 INTERCEPTOR. THE PLAN REFERS TO A CH.24-42-6 FOR
 CHANGING DFU'S TO GPM. WHAT STANDARD IS THIS FROM?
 CLARIFY. THE CALCULATION METHOD IS ACCEPTED HOWEVER THE
 HAND SINK AND FLOOR SINK DRAINAGE LOADS HAVE BEEN ADDED
 TO THE CALCULATIONS AND THE DRAINAGE FROM THOSE
 FIXTURES CANNOT GO INTO THE GREASE INTERCEPTOR- SECTION
 1003.3.1 FBC P.
  
 17) FAILED. SUBMIT FACTORY SIZING CALCULATIONS FROM
 SCHIER FOR THE SIZING OF THE GREASE INTERCEPTOR PER
 FBC-PLUMBING SEC. 1003.2. SEE COMMENT NOTES FOR COMMENT
 #16.
  
 19) FAILED. SHT. P-103 - THE HAND SINKS SHALL DISCHARGE
 TO THE SANITARY PER FBC-PLUMBING SEC.1003.3.1. SHEETS
 P103, P105, RS-3.0: REMOVE CLEAR WATER WASTE DRAINAGE
 FROM ALL OF THE HAND SINKS AND THE FLOOR SINKS
 CONVEYING DRAINAGE FROM THE ICE MAKER, WATER DISPENSER,
 RO SYSTEM, ETC.- SECTION 1003.3.1.
  
 23) FAILED. THE WATER SUPPLY LINE TO THE COFFEE
 BREWERS, ICE MACHINES, ESPRESSO MACHINE, WATER
 DISPENSER, REVERSE OSMOSIS SYSTEM SHALL BE PROTECTED
 WITH A BACKFLOW DEVICE COMPLYING WITH FBC-PLUMBING
 TABLE 608.1 & ASSE 1024. SHEET P-106: BACKFLOW
 PREVENTERS FOR LINES SUPPLYING THE RO FILTER AND TANK
 NOT PROVIDED. TO THE ROUGH-IN SCHEDULE OR PROVIDE A
 SEPARATE SCHEDULE LISTING THE MAKES AND MODELS AND
 INSTALLATION LOCATIONS- SECTION 608.3 FBC P.
  
 24) FAILED. ANY CARBONATED BEVERAGE MACHINE SHALL HAVE
 THE WATER SUPPLY LINE PROTECTED AGAINST BACKFLOW IN
 COMPLIANCE WITH FBC-PLUMBING TABLE 608.1 AND ASSE 1022.
 SHEETS P-101 & FS-3.0: TO HELP EXPEDITE THE REVIEW
 PLEASE ADD THE BACKFLOW DEVICES TO THE ROUGH-IN
 SCHEDULE OR PROVIDE A SEPARATE SCHEDULE LISTING THE
 MAKES AND MODELS AND INSTALLATION LOCATIONS- SECTION
 608.3 FBC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-28 Cont ID  
Sent By tklarge Date 2021-08-28 Time 07:13 Rev Time 0.00
Received By tklarge Date 2021-08-27 Time 13:55 Sent To  
Notes
2021-08-27 05:54:561) SHT. G103 - PLUMBING SYSTEMS TABLE LISTS GREASE
 INTERCEPTOR AS "NR" YET ONE IS BEING INSTALLED. LIST
 THE TYPE, MANUFACTURER, AND SIZE OF THE INTERCEPTOR ON
 THIS TABLE.
 2) SHT. G-104 - THE SIDE WALL GRAB BAR SHALL BE LOCATED
 IN ACCORDANCE WITH FBC-ACCESS. SEC.604.5.1 & FIGURE
 604.5.1. THE LENGTH OF THE GRAB BAR SHALL BE A MINIMUM
 OF 42 INCHES.
 3) SHT. G-104 - THE URINAL SCREEN SHALL BEGIN AT A
 HEIGHT NOT MMORE THAN 12 INCHES FROM AND EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FFINISHED FLOOR SURFACE
 PER FBC -BUILDING SEC.1210.3.2. THE PLAN SHOWS THE
 BOTTOM OF THE SCREEN AT 18 INCHES ABOVE THE FINISH
 FLOOR.
 4) SHT. G-104 - WATER COOLER (DOUBLE) - SHOW COMPLIANCE
 WITH FBC-ACCESS. SEC. 602.7 FOR THE SPOUT OUTLET HEIGHT
 FOR STANDING PERSONS.
 5) SHT. G-104 - ROOM SIGNAGE - TACTILE CHARACTERS ON
 SIGNS SHALL BE LOCATED 48 INCHES MINIMUM ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 INCHES
 MMAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASUURED FROM THE BASELINE OF THE HIGHEST TACTILE
 CHARACTER. FBC-ACCESS. SEC. 703.4.1.
 6) SHT. B-101 SHOWS THE OCCUPANT LOAD OF THIS SPACE AS
 49 PERSONS.A BUILDING OR TENANT SPACE USED FOR ASSEMBLY
 PURPOSES WITH AN OCCCUPANT LOAD OF LES THAN 50 PERSONS
 SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.THE PLANS
 CLASSIY THIS OCCUPANCY AS AN A-2 OCUPANCCY. CLARIFY
 7) THE REQUIRED PLUMBING FIXTURES SHALL BE BASED ON A B
 OCCUPANCY PER FBC-PLUMBING TABLE 403.1.
 8) BOTH TOILET ROOMS SHALL BE FULLLY ACCESSIBLE AND
 COMPLY WITH FBC-ACCESS. SEC.213.2. SHOW FULL COMPLIANCE
 FOR TOILET ROOM #104 ON THE PLANS.
 9) SHOW THE LOCATION OF THE REQUIRED DRINKING FOUNTAIN
 ON THE PLAN AND THE REQUIRED CLEAR FLOOR SPACE FOR THE
 FIXTURE PER FBC-ACCESS. SEC.305 & 602.2.
 10) SHT. B-101 NOTES THE SQUARE FOOTAGE OF THIS SPACE
 AS 1797 SQUARE FEET AND SHT. A-001 NOTES THE SQUARE
 FOOTAGE AS 1039 SQUARE FEET. CLARIFY.
 11) SHT. AD-100 IS MISSING A DIGITAL SEAL & SIGNATURE.
 COMPLY WITH FL. ADMIN. CODE RULE 61G1-16.005.
 12) SHT. A-400 - DETAIL #9 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY AND WATER CLOSET IN
 BOTH TTOILET ROOMS. COMPLY WITH FBC-ACCESS.
 SEC.603.2.3.
 13) SHT. A-420 - DEATIL #4 - WHERE IS THIS FIXTURE
 LOCATED? SHOW ON THE PLANS. WPB AMEND. TO FBC SEC.
 107.2.1.
 14) SHT.ID-101 - FINISH MATERIAL CT-2 IS NOT LISTED ON
 THE FINISH SCHEDULE. CLARIFY.
 15) A HOT WATER RECRCULATION LINE WILL BE REQUIRED PER
 FBC-PLUMBING SEC.607.2.
 16) SHT.P-101 - INDICATE ON THE PLAN WHAT STANDARD WAS
 USED IN THE SIZING OF THE GREASE INTERCEPTOR.THE PLAN
 REFERS TO A CH.24-42-6 FOR CHANGING DFU'S TO GPM. WHAT
 STANDARD IS THIS FROM? CLARIFY.
 17) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZING OF THE GREASE INTERCEPTOR PER FBC-PLUMBING
 SEC. 1003.2.
 18) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR THAT IS
 BEING INSTALLED. FBC-PLUMBING SEC. 1003.2.
 19) SHT. P-103 - THE HAND SINKS SHALL DISCHARGE TO THE
 SANITARY PER FBC-PLUMBING SEC.1003.3.1.
 20) TRAP PRIMERS ARE REQUIRED ON THE FLOOR DRAINS PER
 FBC-PLUMBING SEC.1002.4.1.
 21) SHT. P-105 SHOWS THE DRAIN FROM EVAPORATOR W18A
 DISCHARGING TO THE GRESE WASTE SYSTEM. THE CONDENSATE
 SHALL DISCHARGE TO THE SANITARY OR THE STORM SYSTEM.
 FBC-PLUMBING SEC.1003.2.
 22) SHT. P-104 CALLS OUT A NEW 1 1/2 INCH SHUTOFF VALVE
 ON THE WATER SUPPLY LINE BY THE TOILET ROOMS YET P-106
 CALLS OUT THIS LINE AS 1 1/4. CLARIFY.
 23) THE WATER SUPPLY LINE TO THE COFFE BREWERS, ICE
 MACHINES, ESPRESSO MACHINE, WATER DISPENSER, REVERSE
 OSMOSIS SYSTEM SHALL BE PROTECTED WITH A BACKFLOW
 DEVICE COMPLYING WITH FBC-PLUMBING TABLE 608.1 & ASSE
 1024.
 24) ANY CARBONATED BEVERAGE MACHINE SHALL HAVE THE
 WATER SUPPY LINE PROTECTED AGAINST BACKFLOW IN
 COMPLIANCE WITH FBC-PLUMBING TABLE 608.1 AND ASSE 1022.
 25)THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW
 DEVICE. FBC-PLUMBING SEC. 608.16.
 26) THE FOOD SEVICE PLANS ON THEM IN THE LOWER RIGHT
 HAND CORNER THAT READS "NOT FOR CONSTRUCTION". CLARIFY.
 27) THE FOOD SERVICE PLANS HAVE NOT BEEN SIGNED &
 SEALED BY THE ARCHITECT OF RECORD ALTHOUGH THE TITLE
 BLOCK IS ON THE PLANS. COMPLY WITH FL. ADMIN. CODE RULE
 61G1-16.005.
 28) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 KITCHEN EQUIPMENT PER WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 3 Status N Date 2021-11-24 Cont ID  
Sent By ccole Date 2021-11-24 Time 12:56 Rev Time 0.00
Received By ccole Date 2021-11-23 Time 17:28 Sent To  
Notes
2021-11-24 12:57:20A SEPARATE PERMIT IS REQUIRED ROR INSTALLATION OF THE
 GREASE INTERCEPTOR.

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status F Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 14:01 Rev Time 0.00
Received By ccole Date 2021-10-21 Time 12:19 Sent To  
Notes
2021-10-22 14:04:242ND REVIEW FBC-2020 GREASE WASTE
 PERMIT- 21070505
 10/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTED IN
 CAP LETTERS.
  
 16) FAILED. SHT.P-101 - INDICATE ON THE PLAN WHAT
 STANDARD WAS USED IN THE SIZING OF THE GREASE
 INTERCEPTOR. THE PLAN REFERS TO A CH.24-42-6 FOR
 CHANGING DFU'S TO GPM. WHAT STANDARD IS THIS FROM?
 CLARIFY. THE CALCULATION METHOD IS ACCEPTED HOWEVER THE
 HAND SINK AND FLOOR SINK DRAINAGE LOADS HAVE BEEN ADDED
 TO THE CALCULATIONS AND THE DRAINAGE FROM THOSE
 FIXTURES CANNOT GO INTO THE GREASE INTERCEPTOR- SECTION
 1003.3.1 FBC P.
  
 17) FAILED. SUBMIT FACTORY SIZING CALCULATIONS FROM
 SCHIER FOR THE SIZING OF THE GREASE INTERCEPTOR PER
 FBC-PLUMBING SEC. 1003.2. SEE COMMENT NOTES FOR COMMENT
 #16.
  
 19) FAILED. SHT. P-103 - THE HAND SINKS SHALL DISCHARGE
 TO THE SANITARY PER FBC-PLUMBING SEC.1003.3.1. SHEETS
 P103, P105, RS-3.0: REMOVE CLEAR WATER WASTE DRAINAGE
 FROM ALL OF THE HAND SINKS AND THE FLOOR SINKS
 CONVEYING DRAINAGE FROM THE ICE MAKER, WATER DISPENSER,
 RO SYSTEM, ETC.- SECTION 1003.3.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2021-08-28 Cont ID  
Sent By tklarge Date 2021-08-28 Time 07:12 Rev Time 0.00
Received By tklarge Date 2021-08-28 Time 07:12 Sent To  
Notes
2021-08-28 07:14:551) SHT.P-101 - INDICATE ON THE PLAN WHAT STANDARD WAS
 USED IN THE SIZING OF THE GREASE INTERCEPTOR.THE PLAN
 REFERS TO A CH.24-42-6 FOR CHANGING DFU'S TO GPM. WHAT
 STANDARD IS THIS FROM? CLARIFY.
 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE SIZING OF THE GREASE INTERCEPTOR PER FBC-PLUMBING
 SEC. 1003.2.
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE GREASE
 INTERCEPTOR. PLACE THIS NOTE ON THE PLAN.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-12-06 Cont ID  
Sent By rmcphers Date 2021-12-06 Time 16:27 Rev Time 0.00
Received By rmcphers Date 2021-12-06 Time 16:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-22 Cont ID  
Sent By rmcphers Date 2021-11-22 Time 15:18 Rev Time 0.00
Received By rmcphers Date 2021-11-22 Time 15:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-13 Cont ID  
Sent By rmcphers Date 2021-10-13 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2021-10-13 Time 08:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-02 Cont ID  
Sent By rmcphers Date 2021-09-02 Time 08:23 Rev Time 0.00
Received By rmcphers Date 2021-09-02 Time 08:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-10-01 Cont ID  
Sent By ckimmerl Date 2021-10-01 Time 09:53 Rev Time 0.00
Received By ckimmerl Date 2021-10-01 Time 09:52 Sent To  
Notes
2021-10-01 09:53:02PROVISO: SIGNAGE IS UNDER A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By aaponte Date 2021-08-04 Time 15:53 Rev Time 0.00
Received By ckimmerl Date 2021-08-04 Time 15:52 Sent To  
Notes
2021-08-04 16:04:46- PLEASE INDICATE, NOTE, OR SHOW THE ADDITIONAL/TOTAL
 SQUARE FOOTAGE GAINED FROM THE REMOVAL OF THE RECESSED
 DOOR AREA (D08 & D03 ON AD-100 - CENTER LEFT OF
 BUILDING) THAT'S PROPOSED AS INTERIOR SPACE AND IS
 FLUSH WITH THE FACADE ALONG ROSEMARY AVE.
  
 - SIGNAGE IS UNDER A SEPARATE PERMIT.