Plan Review Details - Permit 21070481
Plan Review Stops For Permit 21070481
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-10 Cont ID  
Sent By jgomez Date 2021-12-10 Time 13:36 Rev Time 0.00
Received By jgomez Date 2021-12-10 Time 13:32 Sent To  
Notes
2021-12-10 13:37:32BUILDING REVIEW APPROVED WITH PROVISO
 (NOTE: SUBMIT FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICT/DELAYS):
 1)MUD ROOM ADDITION: NEED COMPLETE ROOF FRAMING PLAN
 FOR CONVENTIONAL FRAMING. SHOW ALL STRUCTURAL FRAMING
 MEMBERS AND CONNECTORS AT EACH END.
  
 2)WALL SECTION (SHEET A202):PROVIDE ROOF SHEATHING
 COMPLETE INFORMATION. PLYWOOD THICKNESS AND FASTENING.
 SEE SEC. R803 FBC-RESIDENTIAL. NOTE: COORDINATE WITH
 CURRENT CEDAR SHINGLES PRODUCT APPROVAL. PROVIDE
 COMPLETE SPECS FOR WALL SHEATHING, EXTERIOR FINISH,
 FLOOR JOISTS CONNECTION TO NEW STEM WALL AND EXISTING
 WALL. PROVIDE COMPLETE SPECS FOR STEM WALL BEAM, ETC.
  
 3)PROVIDE COMPLETE PRODUCT APPROVAL (NEED COVER PAGE &
 COMPLETE INSTALLATION DWGS)FOR:
 A)CEDAR SHINGLES. PROVIDE COMPLETE CURRENT PRODUCT
 APPROVAL SHOWING COMPLIANCE WITH SEC. R905.7
 FBC-RESIDENTIAL.
 B)SKYLIGHT.
 C)WINDOW MULLIONS. NOTE: NEED TO SPECIFY MULLION SIZE.
 D)CASEMENT WINDOWS. NOTE: MULLION HIGHLIGHTED ON SHEET
 13 OF 28 DOESN'T MEET THE CALCULATED DESIGN PRESSURES.
 NEED TO REVISE SIZE.
 E)DOUBLE HUNG WINDOWS.
 F)EXTERIOR DOORS.
 G)FIXED WINDOWS. IF REPLACED.
 D)HURRICANE SHUTTERS AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 4)ARCHITECT OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT
 APPROVALS.
  
 5)PROVIDE STAIRWAY, STAIRS, HANDRAILS, GUARDRAILS SHOP
 DRAWINGS REVIEWED BY ARCHITECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-11-17 Cont ID  
Sent By jgomez Date 2021-11-17 Time 16:10 Rev Time 0.00
Received By jgomez Date 2021-11-17 Time 10:12 Sent To  
Notes
2021-11-17 16:15:29BUILDING REVIEW APPROVED WITH PROVISO
 (NOTE: SUBMIT FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICT/DELAYS):
 1)MUD ROOM ADDITION: NEED COMPLETE ROOF FRAMING PLAN
 FOR CONVENTIONAL FRAMING. SHOW ALL STRUCTURAL FRAMING
 MEMBERS AND CONNECTORS AT EACH END.
  
 2)WALL SECTION (SHEET A202):PROVIDE ROOF SHEATHING
 COMPLETE INFORMATION. PLYWOOD THICKNESS AND FASTENING.
 SEE SEC. R803 FBC-RESIDENTIAL. NOTE: COORDINATE WITH
 CURRENT CEDAR SHINGLES PRODUCT APPROVAL. PROVIDE
 COMPLETE SPECS FOR WALL SHEATHING, EXTERIOR FINISH,
 FLOOR JOISTS CONNECTION TO NEW STEM WALL AND EXISTING
 WALL. PROVIDE COMPLETE SPECS FOR STEM WALL BEAM, ETC.
  
 3)PROVIDE COMPLETE PRODUCT APPROVAL (NEED COVER PAGE &
 COMPLETE INSTALLATION DWGS)FOR:
 A)CEDAR SHINGLES. PROVIDE COMPLETE CURRENT PRODUCT
 APPROVAL SHOWING COMPLIANCE WITH SEC. R905.7
 FBC-RESIDENTIAL.
 B)SKYLIGHT.
 C)WINDOW MULLIONS. NOTE: NEED TO SPECIFY MULLION SIZE.
 D)CASEMENT WINDOWS. NOTE: MULLION HIGHLIGHTED ON SHEET
 13 OF 28 DOESN'T MEET THE CALCULATED DESIGN PRESSURES.
 NEED TO REVISE SIZE.
 E)DOUBLE HUNG WINDOWS.
 F)EXTERIOR DOORS.
 G)FIXED WINDOWS. IF REPLACED.
 D)HURRICANE SHUTTERS AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 4)ARCHITECT OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT
 APPROVALS.
  
 5)PROVIDE STAIRWAY, STAIRS, HANDRAILS, GUARDRAILS SHOP
 DRAWINGS REVIEWED BY ARCHITECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-08 Cont ID  
Sent By jgomez Date 2021-10-08 Time 16:29 Rev Time 0.00
Received By jgomez Date 2021-10-08 Time 10:45 Sent To  
Notes
2021-10-08 16:30:25RESIDENTIAL (R3) ALTERATION. SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21070481
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- ARCHITECT TO PROVIDE ALL THE WIND DESIGN CRITERIA AS
 REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE
 ULTIMATE AND NOMINAL WIND LOAD, BUILDING EXPOSURE,
 BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE COMPONENTS
 AND CLADDING DESIGN PRESSURES FOR DOORS AND WINDOWS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- OK
 3- OK
  
 ORIGINAL COMMENT.
 4- SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE
 FINISHED FLOOR.
 CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE
 WINDOW SILL IS LESS THAN 24" ABOVE THE FINISH FLOOR.
 SEE SEC. 702.4 FBC-EXISTING BUILDING CODE.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. BASED ON THE WINDOW
 SCHEDULE, IT LOOKS LIKE SOME WINDOWS WILL NEED OPENING
 CONTROL DEVICES. PLEASE IDENTIFY OPENINGS WITH WINDOW
 SILL LESS THAN 2'-0".
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)EXTERIOR DOORS. (IF REPLACED). OR NEW DOOR.
 B)WINDOWS (IF REPLACED). SINGLE HUNG, CASEMENT AND
 FIXED WINDOWS. OR NEW WINDOWS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)ROOFING MATERIAL SPECIFIED ON PLANS.
 F)ROOFING UNDERLAYMENT AS SPECIFIED ON PLANS AND
 APPROVED FOR PROPOSED ROOFING.
 F)SKYLIGHT AS SHOWN ON PLANS.
  
 ORIGINAL COMMENT:
 6- INTERIOR DEMOLITION PERMIT SHOWS ROOFING REMOVAL.
 ARCHITECT OF RECORD TO SPECIFY ROOFING UNDERLAYMENT
 SHOWING COMPLIANCE WITH SEC. R905.1.1.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISED PLANS SPECIFY ALASKAN YELLOW CEDAR SHINGLES.
 ARCHITECT OF RECORD NEEDS TO SPECIFY ONE OF THE
 UNDERLAYMENT METHODS SHOWING COMPLIANCE WITH SEC.
 R905.1.1.3 FBC-RESIDENTIAL. ICE & WATER SHIELD
 SPECIFIED ON THE WALL SECTION ON SHEET A202 IS NOT
 SPECIFIED ON THE NEW CODE SECTION. REVISE AS REQUIRED.
  
 7- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 8- DEMOLITION PLANS SHOW REMOVAL OF WALLS BY THE
 STAIRWAY. NO INFORMATION WAS PROVIDED FOR THE NEW
 GUARDRAIL AND HANDRAIL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R312.1
 FBC-RESIDENTIAL AND SEC. R311.7.8 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 9- OK.
 10- OK.
  
 ORIGINAL COMMENT:
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 REVISE VALUATION TO INCLUDE ALL THE SCOPE OF WORK.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENTS BASED ON REVISED PLANS SUBMITTED:
 12- NEW PLANS SHOW A MUDROOM ADDITION. PROVIDE
 FOUNDATION, FLOOR FRAMING AND ROOF FRAMING PLANS WITH
 COMPLETE DETAILS AND SPECIFICATIONS. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS AT EACH END. SPECIFY
 ROOF SHEATHING FASTENING. SEC. R301.1 FBC-RESIDENTIAL.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 13- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW SKYLIGHT, NEW DOOR AND NEW WINDOW. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL. SEC. 107.3.5.3 CITY AMENDMENTS.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE NEW FIREPLACE AND CHIMNEY AS SHOWN
 ON PLANS. SEC. R301.1 FBC-RESIDENTIAL. SEC. 107.3.5.3
 CITY AMENDMENTS.
  
 15- ARCHITECT TO PROVIDE SPECIFICATIONS FOR PROTECTION
 OF NEW FLOOR JOISTS AGAINST DECAY AS REQUIRED BY SEC.
 R317.1 FBC-RESIDENTIAL.
  
 16- SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 17- WINDOW SCHEDULE ON SHEET A601:
 IT IS NOT CLEAR WHY THERE IS A MISCELLANEOUS NOTE
 STATING "NOT APPROVED BY W.P.B. H.P.B". CLARIFY WHAT IS
 THIS NOTE FOR?
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-18 Cont ID  
Sent By jgomez Date 2021-08-18 Time 15:52 Rev Time 0.00
Received By jgomez Date 2021-08-18 Time 08:48 Sent To  
Notes
2021-08-18 15:53:40RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21070481
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- ARCHITECT TO PROVIDE ALL THE WIND DESIGN CRITERIA AS
 REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE
 ULTIMATE AND NOMINAL WIND LOAD, BUILDING EXPOSURE,
 BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE COMPONENTS
 AND CLADDING DESIGN PRESSURES FOR DOORS AND WINDOWS.
  
 2- THE DEMOLITION PLANS SUBMITTED UNDER THIS
 APPLICATION AND THE DEMOLITION PLANS SHOWN UNDER PERMIT
 #21080674 DON'T MATCH. REVISE AS REQUIRED TO MATCH TO
 AVOID CONFLICTS/DELAYS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SCOPE OF WORK IS NOT CLEAR. SEC. 107.2.1 CITY
 AMENDMENTS.
 ARE EXISTING WINDOWS AND EXTERIOR DOORS GOING TO BE
 REPLACED?. IF SO, THEN SPECIFIC THE EXISTING WINDOW
 TYPE AND SIZE AND SPECIFY PROPOSED WINDOW TYPE AND SIZE
 TO VERIFY COMPLIANCE WITH SEC. 7025 FBC-EXISTING
 BUILDING. FOR EXTERIOR SWING DOORS, SPECIFY EXISTING
 DOOR SIZE AND PROPOSED SIZE.
  
 4- SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE
 FINISHED FLOOR.
 CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE
 WINDOW SILL IS LESS THAN 24" ABOVE THE FINISH FLOOR.
 SEE SEC. 702.4 FBC-EXISTING BUILDING CODE.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)EXTERIOR DOORS. (IF REPLACED).
 B)WINDOWS (IF REPLACED)
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)ROOFING MATERIAL.
  
 6- INTERIOR DEMOLITION PERMIT SHOWS ROOFING REMOVAL.
 ARCHITECT OF RECORD TO SPECIFY ROOFING UNDERLAYMENT
 SHOWING COMPLIANCE WITH SEC. R905.1.1.1
 FBC-RESIDENTIAL.
  
 7- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- DEMOLITION PLANS SHOW REMOVAL OF WALLS BY THE
 STAIRWAY. NO INFORMATION WAS PROVIDED FOR THE NEW
 GUARDRAIL AND HANDRAIL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R312.1
 FBC-RESIDENTIAL AND SEC. R311.7.8 FBC-RESIDENTIAL.
  
 9- DEMOLITION PLANS CALLS FOR REMOVAL OF WALLS BY THE
 MASTER BEDROOM ENTRY AREA. NEED TO PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE NEW WALLS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 10- PROPOSED FIRST FLOOR PLAN SHOWS THE CONVERSION OF
 THE FLORIDA ROOM
 TO BAR LOUNGE. THE FLORIDA ROOM WAS NOT PART OF THE
 HEATED (AND AIR CONDITIONED) SPACE OF THE MAIN HOUSE.
 BASED ON THE PROPOSED PLAN, IT LOOKS LIKE NOW THE BAR
 LOUNGE IS GONG TO BE PART OF THE HEATED SPACE OF THE
 MAIN HOUSE. ARCHITECT TO PROVIDE DETAILS/SPECIFICATIONS
 SHOWING HOW THIS ROOM IS GOING TO BE HEATED AS REQUIRED
 BY SEC. R303.10 FBC-RESIDENTIAL.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 REVISE VALUATION TO INCLUDE ALL THE SCOPE OF WORK.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-12-09 Cont ID  
Sent By jleahy Date 2021-12-09 Time 15:29 Rev Time 0.00
Received By jleahy Date 2021-12-09 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-10-18 Cont ID  
Sent By jleahy Date 2021-10-18 Time 11:50 Rev Time 0.00
Received By jleahy Date 2021-10-18 Time 11:50 Sent To  
Notes
2021-10-18 11:51:34SEE PERMIT #21081237 FOR THE ELECTRICAL WORK FOR THIS
 PROJECT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-10-11 Cont ID  
Sent By fgiaquin Date 2021-10-11 Time 19:41 Rev Time 0.00
Received By fgiaquin Date 2021-10-11 Time 18:36 Sent To  
Notes
2021-10-11 19:40:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SMOKE/CO ALARMS REQUIRED PER FBC-RE 314 AND 315
  
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
  
 3. ARC-FAULT PROTECTION REQUIRED PER NEC 210.12A,
 210.12B
  
 4. TAMPERPROOF RECEPTACLES REQUIRED PER NEC 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-29 Cont ID  
Sent By fgiaquin Date 2021-07-29 Time 20:14 Rev Time 0.00
Received By fgiaquin Date 2021-07-29 Time 19:18 Sent To  
Notes
2021-07-29 20:14:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. . FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-12-10 Cont ID  
Sent By ccole Date 2021-12-10 Time 11:26 Rev Time 0.00
Received By ccole Date 2021-12-10 Time 08:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-11-02 Cont ID  
Sent By ccole Date 2021-11-02 Time 17:24 Rev Time 0.00
Received By ccole Date 2021-11-02 Time 16:08 Sent To  
Notes
2021-11-02 17:25:582ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21070481
 11/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A100 GAS RISER: PLEASE CORRECT THE NOTE
 INDICATING A 1 PSI SYSTEM AT THE SERVICE REGULATOR-
 SECTION G2413.1 FBC RES.
  
 2) A100 GAS RISER: PLEASE INDICATE THE SIZE OF THE PIPE
 FROM THE METER TO THE FIRST TEE- G24313.3 FBC RES.
  
 3) A100: CONCERNING COMBUSTION AIR FOR THE RANGE PLEASE
 USE ONE OF THE METHODS LISTED UNDER SECTION G2407.1 FBC
 RES. THE RESPONSE NARRATIVE IS INDICATING THE MAKEUP
 AIR FOR THE EXHAUST HOOD IS THE SOURCE OF THE
 COMBUSTION AIR, HOWEVER THE MAKEUP AIR IS DEDICATED FOR
 REPLACEMENT OF THE HOOD EXHAUST AIR.
  
 4) A100: COMMENT #5 FROM THE 1ST REVIEW PRINTED BELOW
 WAS PARTIALLY ADDRESSED. PLEASE PROVIDE THE REQUESTED
 MANUFACTURER'S SPECIFICATIONS AND VENTING PLAN.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW FIREPLACE
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL - SECTION G2434.1 FBC RES. PROVIDE
 COMBUSTION AIR AND VENTING PLANS FOR THE FIREPLACE IN
 ACCORDANCE WITH MANUFACTURER?S GUIDELINES. PLEASE
 INCLUDE COMBUSTION AIR CALCULATIONS, AND A VENTING
 DIAGRAM WHICH SHOWS THE TYPE AND SIZE OF VENT
 PIPES/DUCTS, VENT RUN LENGTHS AND VENT TERMINATION
 LOCATION- REFER TO SPECS AND SECTION G2427 FBC RES.
  
 6) A101: SHOW THE GAS DRYER VENT RUN AND SPECIFICTIONS,
 AND INDICATE HOW AIR IS BEING PROVIDED TO THE
 APPLIANCE- SECTION G2439.1 & G2439.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By ccole Date 2021-09-30 Time 08:27 Rev Time 0.00
Received By ccole Date 2021-09-29 Time 17:18 Sent To  
Notes
2021-09-30 08:28:011ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21070481
 9/28/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A100 & A101: THE GAS PIPING AND APPLIANCE
 INSTALLATIONS FOR THE PROPOSED PROJECT SHALL BE
 DESIGNED AND INSTALLED IN ACCORDANCE WITH THE FBC- 2020
 7TH EDITION RESIDENTIAL CODE. PLEASE PROVIDE DESIGN
 CRITERIA ON THE PLANS.
  
 2) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL SHOW:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 3) PLEASE NOTE THAT THE MOST RECENT GAS PERMIT AT THE
 RESIDENCE WAS PERMIT #04121077. WPB BUILDING DEPT.
 RECORDS INDICATE A 505,000 BTU SYSTEM WITH AN EXISTING
 RANGE, STORAGE TYPE WATER HEATER AND A NEW POOL HEATER.
 THERE IS NO RECORD OF AN EXTERIOR TANKLESS GAS-FIRED
 WATER HEATER BEING LEGALLY PERMITTED THEREFORE IT SHALL
 BE REVIEWED AS A NEW WATER HEATER. PLEASE SUBMIT
 MANUFACTURER?S SPECIFICATIONS AND INSTALLATION MANUAL
 FOR THE WATER HEATER. PROVIDE AN EQUIPMENT SCHEDULE ON
 THE PLAN INDICATING THE MAKE AND MODEL, BTUH LOAD, AND
 EFFICIENCY RATING- TABLE C404.2 FBC EC. PROVIDE A
 DETAIL SHOWING THE INSTALLATION LOCATION AND REQUIRED
 CLEARANCES AS RECOMMENDED BY THE MANUFACTURER- SECTIONS
 G2406.1 & G2448.1 FBC RES.
  
 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW RANGE AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION G2447.1
 FBC RES. PROVIDE COMBUSTION AIR CALCULATIONS AND
 INDICATE HOW THE AIR WILL BE PROVIDED- SECTION G2407.1
 FBC RES.
  
 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW FIREPLACE
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL - SECTION G2434.1 FBC RES. PROVIDE
 COMBUSTION AIR AND VENTING PLANS FOR THE FIREPLACE IN
 ACCORDANCE WITH MANUFACTURER?S GUIDELINES. PLEASE
 INCLUDE COMBUSTION AIR CALCULATIONS, AND A VENTING
 DIAGRAM WHICH SHOWS THE TYPE AND SIZE OF VENT
 PIPES/DUCTS, VENT RUN LENGTHS AND VENT TERMINATION
 LOCATION- REFER TO SPECS AND SECTION G2427 FBC RES.
  
 6) INDICATE THE MAKES AND MODELS OF REGULATORS TO BE
 INSTALLED ON THE SYSTEM AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS MARKED UP TO SHOW THE SELECTED MODELS,
 AND INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION
 G2421.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-10-18 Cont ID  
Sent By fmittner Date 2021-10-18 Time 13:29 Rev Time 0.00
Received By fmittner Date 2021-10-18 Time 13:29 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-08-24 Cont ID  
Sent By fmittner Date 2021-08-24 Time 08:40 Rev Time 0.00
Received By fmittner Date 2021-08-24 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-10 Cont ID  
Sent By jgomez Date 2021-12-10 Time 13:51 Rev Time 0.00
Received By jgomez Date 2021-12-06 Time 14:58 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-17 Cont ID  
Sent By jgomez Date 2021-11-17 Time 16:26 Rev Time 0.00
Received By jgomez Date 2021-10-29 Time 08:42 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-19 Cont ID  
Sent By lmarchan Date 2021-10-19 Time 09:31 Rev Time 0.00
Received By lmarchan Date 2021-09-23 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-08-25 Time   Rev Time 0.00
Received By ccarvaja Date 2021-07-27 Time 13:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By lmarchan Date 2021-12-22 Time 12:34 Rev Time 0.00
Received By lmarchan Date 2021-12-15 Time 08:00 Sent To  
Notes
2021-12-22 09:34:20RECEIPT MU-2021-58870 - $2291.74 PAID
  
2021-12-15 08:01:1312/15/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-08-18 Cont ID  
Sent By jgomez Date 2021-08-18 Time 15:56 Rev Time 0.00
Received By jgomez Date 2021-08-18 Time 15:56 Sent To  
Notes
2021-08-18 15:58:17IMPACT FEES REVIEW:
 CHANGING THE USE OF THE COVERED FLORIDA ROOM TO LIVABLE
 AREA. PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY
 FOR IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-12-10 Cont ID  
Sent By ccole Date 2021-12-10 Time 11:26 Rev Time 0.00
Received By ccole Date 2021-12-10 Time 08:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-11-02 Cont ID  
Sent By ccole Date 2021-11-02 Time 17:26 Rev Time 0.00
Received By ccole Date 2021-11-02 Time 16:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-09-29 Cont ID  
Sent By ccole Date 2021-09-29 Time 17:09 Rev Time 0.00
Received By ccole Date 2021-09-29 Time 16:44 Sent To  
Notes
2021-09-29 17:09:411ST REVIEW FBC-2020 RES.
 PERMIT- 21070481
 9/28/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A100 SANITARY RISER: SHOW A 2-INCH FIXTURE
 DRAIN FOR THE WASHING MACHINE CONNECTING TO A MINIMUM
 3-INCH STACK AND BRANCH DRAIN- SECTION 406.2 FBC P.
  
 2) A101: SHOW THE LOCATIONS OF THE WASHING MACHINE
 SHUTOFF VALVES TO VERIFY THEY WILL BE IN A LOCATION
 WITH ACCESS- SECTION P2903.5.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By ccole Date 2021-07-30 Time 13:11 Rev Time 0.00
Received By ccole Date 2021-07-30 Time 12:17 Sent To  
Notes
2021-07-30 13:11:481ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21070481
 7/30/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE PLUMBING PLANS, SPECIFICATIONS,
 FIXTURE AND APPLIANCE SCHEDULES, AND RISER DRAWINGS FOR
 REVIEW SECTIONS 107.1 AND 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-11-17 Cont ID  
Sent By jgomez Date 2021-11-17 Time 16:16 Rev Time 0.00
Received By jgomez Date 2021-11-17 Time 16:16 Sent To  
Notes
2021-11-17 16:17:50ROOFING REVIEW APPROVED WITH PROVISO
 (NOTE: SUBMIT FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICT/DELAYS):
  
 1)PROVIDE COMPLETE PRODUCT APPROVAL (NEED COVER PAGE &
 COMPLETE INSTALLATION DWGS)FOR:
 A)CEDAR SHINGLES. PROVIDE COMPLETE CURRENT PRODUCT
 APPROVAL SHOWING COMPLIANCE WITH SEC. R905.7
 FBC-RESIDENTIAL.
  
 2)ARCHITECT OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT
 APPROVALS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-10-08 Cont ID  
Sent By jgomez Date 2021-10-08 Time 14:55 Rev Time 0.00
Received By jgomez Date 2021-10-08 Time 14:55 Sent To  
Notes
2021-10-08 14:56:12ROOFING REVIEW:
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOFING MATERIAL SPECIFIED ON PLANS.
 B) ROOFING UNDERLAYMENT AS SPECIFIED ON PLANS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-12-10 Cont ID  
Sent By jgomez Date 2021-12-10 Time 13:50 Rev Time 0.00
Received By jgomez Date 2021-12-10 Time 13:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-17 Cont ID  
Sent By jgomez Date 2021-11-17 Time 16:26 Rev Time 0.00
Received By jgomez Date 2021-11-17 Time 16:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-08 Cont ID  
Sent By jgomez Date 2021-10-08 Time 16:36 Rev Time 0.00
Received By jgomez Date 2021-10-08 Time 16:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-18 Cont ID  
Sent By jgomez Date 2021-08-18 Time 16:05 Rev Time 0.00
Received By jgomez Date 2021-08-18 Time 16:05 Sent To  
Notes
2021-08-18 16:05:25SIGNATURE REVIEW COMMENTS:
  
 1- ALL DRAWINGS NEED ARCHITECT'S ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY SEC. 481 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
 PLANS SUBMITTED HAVE A COPY OF A DIGITAL SIGNATURE.
 PLANS WITH DIGITAL SIGNATURE ARE NOT ALLOWED TO BE
 PRINTED. NEED PLANS SUBMITTED ELECTRONICALLY WITH
 ARCHITECT'S ORIGINAL DIGITAL SIGNATURE OR PROVIDE HARD
 COPY PLANS WITH THE ORIGINAL SEAL AND SIGNATURE.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-10-18 Cont ID  
Sent By fmittner Date 2021-10-18 Time 13:29 Rev Time 0.00
Received By fmittner Date 2021-10-18 Time 13:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-08-24 Cont ID  
Sent By fmittner Date 2021-08-24 Time 08:40 Rev Time 0.00
Received By fmittner Date 2021-08-24 Time 08:40 Sent To  
Notes
***NONE***