Plan Review Details - Permit 21070374
Plan Review Stops For Permit 21070374
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-07-09 Cont ID  
Sent By cpuell Date 2021-07-09 Time 13:12 Rev Time 0.00
Received By cpuell Date 2021-07-09 Time 13:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-11-01 Cont ID  
Sent By rmcphers Date 2021-11-01 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2021-11-01 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-28 Cont ID  
Sent By rmcphers Date 2021-07-28 Time 12:17 Rev Time 0.00
Received By rmcphers Date 2021-07-28 Time 11:04 Sent To  
Notes
2021-07-28 12:24:562ND FLOOR TRELLIS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING A001 NOTE NUMBER 1 - SHOWS DESIGN PER 2017
 FBC - SHOULD BE 2020 FBC.
 2) PLEASE SHOW THE EXISTING BUILDING CONSTRUCTION TYPE
 PER FBC CHAPTER 6
 3) WOOD FRAMING MAY NEED TO BE FIRE RETARDANT PER FBC
 602.2 TYPES I AND II.
 TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS
 PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-29 Cont ID  
Sent By jleahy Date 2021-07-29 Time 07:03 Rev Time 0.00
Received By jleahy Date 2021-07-29 Time 06:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-27 Cont ID  
Sent By pleduc Date 2021-10-27 Time   Rev Time 0.00
Received By pleduc Date 2021-10-26 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By pleduc Date 2021-07-13 Time   Rev Time 0.00
Received By pleduc Date 2021-07-13 Time 11:44 Sent To  
Notes
2021-07-13 11:55:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PROPOSED TRELLIS INSTALLATION APPEARS TO IMPACT
 AND OBSTRUCTT THE EXISTING FIRE SPRINKLER PROTECTION
 SYSTEM.
  
 A REVIEW BY A CERTIFIED FIRE SPRINKLER CONTRACTOR IS
 REQUIRED.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM, INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
 1A) SHEET A 501 - WITHIN THE LEGEND DIAMOND NOTE # 9
 INDICATES THE EXISTING FIRE SPRINKLERS TO REMAIN.
  
 THE DIAMOND # 9 COULD NOT BE FROUND IN ANY OF THE
 CALL-OUTS SECTIONS.
  
 THOUGH EXISTING SPRINKLERS MAY REMAIN ABOVE THE
 TRELLIS, THEY ARE NOT IDENTIFIED CORRECTLY, AND
 SPRINKLER PROTECTION MAY BE REQUIRED TO EXTEND UNDER
 THE TRELLIS
  
 PLEASE REVIEW AND CORRECT AND ADDRESS # 1 ABOVE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-01 Cont ID  
Sent By rmcphers Date 2021-11-01 Time 14:46 Rev Time 0.00
Received By rmcphers Date 2021-10-22 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-16 Cont ID  
Sent By lmarchan Date 2021-08-16 Time 16:42 Rev Time 0.00
Received By lmarchan Date 2021-07-09 Time 12:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-28 Cont ID  
Sent By rmcphers Date 2021-07-28 Time 12:25 Rev Time 0.00
Received By rmcphers Date 2021-07-28 Time 12:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-10-27 Cont ID  
Sent By eschneid Date 2021-10-27 Time 16:08 Rev Time 0.25
Received By eschneid Date 2021-10-27 Time 16:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-16 Cont ID  
Sent By eshneide Date 2021-08-16 Time 16:13 Rev Time 0.25
Received By eschneid Date 2021-08-16 Time 16:13 Sent To  
Notes
2021-08-16 16:14:50FAILED
  
 THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS
 REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A
 LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES
 THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]