Plan Review Details - Permit 21070345
Plan Review Stops For Permit 21070345
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 13:53 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-16 Cont ID  
Sent By rmcphers Date 2021-07-16 Time 08:28 Rev Time 0.00
Received By rmcphers Date 2021-07-16 Time 08:23 Sent To  
Notes
2021-07-16 08:28:46REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) ENERGY CALCS. HAVE BEEN REVISED - YOU WILL NEED TO
 REVISE THE DRAWINGS TO SHOW THE CORRECT INSULATION TO
 MATCH THE ENERGY CALCS.
 2) ENERGY CALCS. SHOW R30 IN THE CEILING - R30 BAT
 INSULATION IN A 2 X 10 RAFTER WILL NOT ALLOW FOR THE
 REQUIRED 1 INCH VENTILATION GAP PER FBC R 806.3 VENT
 AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-28 Cont ID  
Sent By medwards Date 2021-07-28 Time 15:45 Rev Time 0.00
Received By medwards Date 2021-07-23 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-19 Cont ID  
Sent By medwards Date 2021-07-19 Time 08:08 Rev Time 0.00
Received By medwards Date 2021-07-09 Time 10:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-07-28 Cont ID  
Sent By medwards Date 2021-07-28 Time 15:44 Rev Time 0.00
Received By medwards Date 2021-07-28 Time 15:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By medwards Date 2021-07-19 Time 08:04 Rev Time 0.00
Received By medwards Date 2021-07-19 Time 08:04 Sent To  
Notes
2021-07-19 08:07:05PLEASE EXPLAIN THIS REVISION. THE MASTER PERMIT21010170
 IS FOR POOL HOUSE EXPANSION. THE ORIGINAL DRAWINGS SHOW
 1 AHU. IS THIS REVISION CHANGING THIS? IF SO PLEASE
 PROVIDE DRAWINGS SHOWING THE CHANGES. THESE DRAWINGS
 MUST ALSO SHOW THE LOCATION OF THE ODU AND SECURING
 DETAILS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 13:53 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 13:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-16 Cont ID  
Sent By rmcphers Date 2021-07-16 Time 08:29 Rev Time 0.00
Received By rmcphers Date 2021-07-16 Time 08:29 Sent To  
Notes
***NONE***