Plan Review Details - Permit 21070334
Plan Review Stops For Permit 21070334
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-26 Cont ID  
Sent By jleahy Date 2021-07-26 Time 07:29 Rev Time 0.00
Received By jleahy Date 2021-07-26 Time 07:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-08-13 Time   Rev Time 0.00
Received By bdolan Date 2021-08-13 Time 14:42 Sent To  
Notes
2021-08-13 14:48:17LETTER ADDRESSING CAUSE FOR REPLACEMENT NOTED.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By   Date 2021-08-04 Time   Rev Time 0.00
Received By bdolan Date 2021-08-04 Time 14:12 Sent To  
Notes
2021-08-04 14:13:39PLEASE PROVIDE REASON FOR REPLACEING SMOKE
 DETECTOR WITH HEAT DETECTOR.
 OCCUPANCY HAS RESIDENTIAL UNITS LOCATED ON UPPER FLOOR.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By   Date 2021-07-14 Time   Rev Time 0.00
Received By bdolan Date 2021-07-14 Time 12:29 Sent To  
Notes
2021-07-14 12:34:28LEASE RESUBMIT A PLAN INCLUDING THE CCONTRACTOR
 INFORMATION, IN A STANDARD FORMAT.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-16 Cont ID  
Sent By jleahy Date 2021-08-16 Time 09:01 Rev Time 0.00
Received By jleahy Date 2021-08-12 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By hmoser Date 2021-08-10 Time 11:02 Rev Time 0.00
Received By hmoser Date 2021-08-02 Time 07:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-27 Cont ID  
Sent By medwards Date 2021-07-27 Time 13:44 Rev Time 0.00
Received By medwards Date 2021-07-09 Time 14:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By hmoser Date 2021-08-10 Time 11:01 Rev Time 0.00
Received By hmoser Date 2021-08-10 Time 10:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By medwards Date 2021-07-27 Time 13:41 Rev Time 0.00
Received By medwards Date 2021-07-27 Time 13:41 Sent To  
Notes
2021-07-27 13:43:23DESIGNER OF DRAWING MUST PRINT THEIR NAME AND SIGN THE
 DRAWING.
 PLEASE PROVIDE THE REASON THE SMOKE DETECTOR IS BEING
 CHANGED TO A HEAT DETECTOR. IS THIS A REQUIRED SMOKE
 DETECTOR LOCATION?
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-16 Cont ID  
Sent By jleahy Date 2021-08-16 Time 09:01 Rev Time 0.00
Received By jleahy Date 2021-08-16 Time 09:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By hmoser Date 2021-08-10 Time 11:02 Rev Time 0.00
Received By hmoser Date 2021-08-10 Time 11:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-26 Cont ID  
Sent By jleahy Date 2021-07-26 Time 07:29 Rev Time 0.00
Received By jleahy Date 2021-07-26 Time 07:29 Sent To  
Notes
2021-07-26 07:30:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) PLAN IS NOT DIGITALLY SIGNED BY THE DESIGNER OF
 RECORD
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
  