| 2021-07-20 10:34:22 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:21070252 |
| | ADD: 529 S. FLAGLER DR. # 29E |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 19TH/ 2021 |
| | ACTION: DENIED |
| | 1) SHEET S-1, SITE PLAN BY COVENANT ENGINEERING, INC. / |
| | EDWARD J. KRANZ PE: |
| | 1A) THE SITE PLAN IS LOCKED AND CAN NOT CHECK |
| | ELECTRONIC SIGNATURE. 61G15-23.005 PROCEDURES FOR |
| | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS |
| | (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | |
| | 1B) THE SITE PLAN INDICATES THE LOCATION IS IN FT. |
| | LAUDERDALE FL. WRONG MUNICIPALITY. WEST PALM BEACH, FL. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1C) THE EXPOSURE CATEGORY IS LISTED AS C. PLEASE REVIEW |
| | SECTION 1609.4.3 EXPOSURE CATEGORIES FOR D. IF S RAY IS |
| | SHOOT OUT OVER THE WATER AND TRAVELS 5000 FT OVER |
| | WATER, AND THE SAME RAY DOES NOT TRAVEL OVER LAND MORE |
| | THAN 600 FT, THE LOCATION IS TO BE CONSIDERED AN D |
| | EXPOSURE. THAT BEING SAID, THERE ARE 2 BUILDINGS ON |
| | THIS SITE AND THE LOCATION WHERE THE GLAZING IS TO BE |
| | INSTALLED DOES NOT INDICATE WHICH BUILDING AND THE |
| | RELATIONSHIP TO THE INTERCOSTAL WATERWAY. THAT WILL BE |
| | THE FINAL DETERMINATION IF THIS IS A C OR D EXPOSURE. |
| | IN THE PAST THIS BUILDING HAS ALWAYS BEEN CONSIDERED A |
| | D EXPOSURE. |
| | |
| | 1D) THE DESIGNER OF RECORD HAS GIVEN PRESURES FOR |
| | OPENINGS A, B, & C. INCORPORATED IN THE FLOOR PLAN |
| | THERE IS A SCHEDULE FOR THESE 3 OPENINGS WITH PRESURES |
| | FOR ZONE 4 AND ZONE 5. THE DESIGNER OF RECORD HAS NOT |
| | HIGHLIGHTED OR SHOWN WHICH PREURES ARE RELEVANT TO THIS |
| | PROJECT, HE LEAVES IT UP TO THE CONTRACTOR. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1E) THE DESIGNER OF RECORD IN THE WIND DESIGN HAS LEFT |
| | OUT IF THE PREURES GIVEN ARE FOR INTERNAL PRESSURE |
| | COEFFICIENT. NOTE OPENINGS 1 & 2 ARE FOR OPENINGS IN |
| | WALLS WHERE OPENING 3 IS OUT IN THE OPEN NOT IN A |
| | ENCLOSED ENVIROMENT. 1603.1.4 WIND DESIGN DATA. UNTIL |
| | THESE ISSUES CAN BE CLEARED UP THE PRODUCT APPROVALS |
| | CAN NOT BE REVIEWED. |
| | |
| | 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| | WORKING FROM CITY HALL |
| | MY WORK HOURS ARE MON. & TUES. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |