| 2021-08-11 09:59:28 | 1) SHT. S-1 CALLS OUT THIS OCUPANCY AS MERCANTILE "B". |
| | THERE IS NO SUCH OCCUPANCY CLASSIFICATION IN THE |
| | BUILDING CODE. THIS SPACE WAS PREVIOUSLY CLASIFIED AS |
| | AN A-2 OCCCUPANCY ACORDING TO CITY RECORDS. SEC. |
| | 303.1.1 OF THE FBC-BUILDING STATES A BUILDING OR TENANT |
| | SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD |
| | OF LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP |
| | "B" OCUPANCY.CLARIFY. |
| | 2) SHT. S-1 HAS THE OCUPANT LOAD OF THIS SPACE AS 32 |
| | PERSONS. IF THIS OCCUPANT LOAD IS CORRECT, THEN TWO |
| | SEPARATE TOILET ROOMS ARE REQUIRED PER |
| | FBC-PLUMBING-TABLE 403.1 AND SEC. 403.2. |
| | 3) THE DOOR TO THE ACCESSIBLE TOILET ROOM CANNOT SWING |
| | INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.FBC-ACCESS. |
| | SEC.603.2.3. (SEE EXCEPTION #2). THE PREVIOUS PLANS ON |
| | FILE SHOW THE DOOR WINGING OUT.CLARIFY. |
| | 4) SHOW THE FIXTURE CLEARANCES OF THE TOILET FIXTURES |
| | ON THE FLOOR PLAN FOR THE TOILET ROOM. COMPLY WITH |
| | FBC-ACCESS. SEC.604.2, FBC-PLUMBING SEC.405.3.1. |
| | 5) THE WALL FINISH AROUND THE MOP SINK SHALL COMPLY |
| | WITH FBC-BUILDING SEC. 1210.2.2. |
| | 6) SHT. S-1 -SHOW THE REQUIRED CLEAR FLOOR SPACES FOR |
| | THE HANDICAPPED ACCESSIBLE PLUMBING FIXTURES ON THE |
| | PLAN AND SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES |
| | ON THE PLANS. COMPLY WITH FBC - ACCESS. SECS.604.3..1, |
| | 606.2. |
| | 7) THE HEIGHT OF THE SERVICE COUNTER SHALL COMPLY WITH |
| | FBC-ACCESS. SEC.904.4.1. |
| | 8) INDICATE ON THE PLAN IF THERE WILL BE ANY SEATING AT |
| | THE EXTERIOR PATIO AREA AND COVERED WALWAY ASSOCIATED |
| | WITH THIS BUSINESS. IF SO, THE OCCUPANT LOAD MUST BE |
| | INCLUDED IN THE TOTAL OCCUPANT LOAD. FBC-PLUMBING SEC. |
| | 403.1. |
| | 9) A DRINKING FOUNTAIN IS REQUIRED PER FBC-PLUMBING |
| | SEC.410.3 AND TABLE 403.1. A MINIMUM OF 2 DRINKING |
| | FOUNTAINS ARE REQUIRED. FBC-ACCESS. SEC.211.1, |
| | 10) SHT. S-1 - OCUPANCY CLASSIFICATION NOTE REFERS O |
| | THE 2010 EDITION OF THE FBC. THE 2020 CODE IS IN |
| | EFFECT. |
| | 11) THE EXISTING PLANS FOR THIS SPACE ON FILE WITH THE |
| | CITY SHOW THE GREASE INTERCEPTOR AS A 100 GPM UNIT BUT |
| | THE EQUIPMENT SCHEDULE ON SHT. S-2 SHOWS THE GREASE |
| | INTERCCEPTOR AS 1250 GALLONS. CLARIFY. |
| | 12) INDIATE THE CLASSIFICATION OF WORK ON THE PLANS PER |
| | FBC-EXISTING BUILDING SEC.601.1. ALSO, INDICATE THE |
| | COMPLIANCE METHOD PER FBC-EXISTING SEC.301.3. |
| | 13) IT APPEARS THAT A HAND SINK HAS BEEN REMOVED AND |
| | THE SERVICE SINK RELOCATED BASED ON PLANS FROM THE |
| | PREVIOUS OCCUPANCY. SUBMIT A WATER AND SANITARY RISER |
| | DIAGRAM TO SHOW THE CHANGES TO THE SANITARY SYSTEM. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |