| Plan Review Stops For Permit 21070198 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2021-08-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-08-31 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-08-31 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2021-08-31 16:55:03 | PARCEL ADDRESS OK TO REMAIN FOR NEW CONSTRUCTION HOME. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-03-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-30 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-30 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-20 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-19 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2022-01-20 09:03:01 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PLEASE REMOVE NOTE ON SITE PLAN, SP-1 THAT STATES | | | "ALL EQUIPMENTS MOUNTED ABOVE B.F.E" | | | THIS PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA AND DOES NOT HAVE A BASE FLOOF ELEVATION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. REF. PLAN PAGE S1.1, ROOF SHEATHING FASTENER DIAGRAM | | | AND FASTENER SCHEDULE FOR THE FOLLOWING COMMENT: | | | ROOF ZONES SHALL BE IDENTIFIED AS ZONES 1, 2E, 2R & 3 | | | PER FBC R301.2. (7). | | | FASTENERS SHALL BE BASED ON THE DESIGN PRESSURE OF EACH | | | ZONE. | | | R301.2.1.1WIND DESIGN REQUIRED. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-18 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-10-18 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2021-10-18 17:09:02 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A COPY OF THE MOST RECENT BOUNDRY LINE | | | SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE A SITE DRAINGAE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 3. PROVIDE THE FINISHED FLOOR ELEVATION. | | | R403.1.7.3 FOUNDATION ELEVATION. | | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | | PERCENT. | | | ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO THE | | | APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN BE | | | DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | | ALL LOCATIONS ON THE SITE. | | | | | | 4. DESIGNER SHALL SELECT MODEL OF DOORS AND WINDOWS | | | FROM PRODUCT APPROVALS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 5. PLAN PAGE S3.1 SHOWS TYPICAL EXTERIOR WALL WITH | | | DOUBLE BOND BEAM. PLAN PAGE A-3 SHOWS TYPICAL EXTERIOR | | | WALL WITH TIE BEAM. PLEASE CLARIFY? | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-09-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-27 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-27 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-04-01 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-04-01 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-16 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-20 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-23 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-18 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-08-23 |
Time |
11:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-04-07 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-03-30 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2022-04-07 13:56:08 | RECEIPT MU-2022-014994 - $11,623.07 PAID | | 2022-03-30 11:40:22 | 3/30/22 EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-18 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-10-18 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2021-10-18 16:14:31 | IMPACT FEE QUESTIONNAIRE | | | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-25 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-25 |
Time |
07:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-11-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-24 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-24 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-30 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-30 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2021-08-30 13:36:37 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21070198 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ANCHORAGE DETAILS FOR THE | | | CONDENSING UNIT. FBC RES M1307.2 | | | | | | 2) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION | | | LOCATION. FBC RES M1411.3 | | | | | | 3) PLEASE SHOW THE DRYER DUCT AND THE TERMINATION | | | LOCATION. FBC RES M1502 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-09-10 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-10 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2021-09-10 12:33:05 | 09/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2022-03-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-30 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-30 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-18 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-10-18 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-03-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-30 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-30 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-20 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-19 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2022-01-20 08:51:58 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | | | | 1ST REVIEW COMMENTS HAVE NOT BEEN ADDRESSED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | RE: PLAN PAGE C-1 AND ALL STRUCTURAL PLANS SIGNED BY | | | WILLIAM P. STODDARD, P.E. | | | | | | NOTICE: | | | COVER LETTERS FOR DIGITAL SIGNATURES ARE NOT ACCEPTED | | | FOR MULTI-PAGE DOCUMENTS | | | | | | 3 WAYS TO SUBMIT DOCUMENTS WITH DIGITAL SIGNATURES | | | 1. EACH UPLOADED SHEET HAS A DIGITAL SIGNATURE. | | | 2. PROVIDE MULTI PAGE PDF THAT IS DIGITALLY SIGNED BY | | | THE DESIGNERS AND UPLOAD IT INTO THE SIGNATURE FOLDER. | | | THIS SHOULD ONLY BE DONE AFTER ALL CORRECTIONS HAVE | | | BEEN MADE TO THE PLANS. | | | THE MULTI-PAGE PDF SHOULD REFLECT THE MOST CURRENT | | | VERSION OF THE PLANS. | | | 3. PROVIDE ONE ORIGINAL SET OF APPROVED PLANS. | | | | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-10-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-10-07 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-30 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2021-08-30 13:41:14 | ALL DOCUMENTS SIGNED BY WILLIAM STODDARD MUST BE | | | DIGITALLY SIGNED. F.S. 471 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-02-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-02-23 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-02-23 15:11:43 | ZONING APPROVED WITH THE FOLLOWING PROVISO: | | | | | | 1.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, | | | DRIVEWAY, HARDSCAPE/WALKWAYS, AND FENCE/WALL/GATES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-12-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-12-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-12-09 13:39:00 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1. SEPARATE LANDSCAPE PERMIT REQUIRED FOR REQUIRED | | | LANDSCAPE IMPROVEMENTS ON THE PROPERTY. [REPEAT | | | COMMENT: NO SEPARATE LANDSCAPE PERMIT SUBMITTED TO | | | DATE.] | | | | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, DRIVEWAY, | | | FENCE. | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * Z=SF7 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-09-16 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-09-16 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2021-09-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-09-16 11:15:53 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY, | | | SHOWING ALL UTILITY EASEMENTS (IF APPLICABLE), IS | | | MISSING FROM THE PERMIT SUBMITTAL. | | | | | | 2.) ALL BUILDING SETBACKS FROM THE PROPERTY LINE SHALL | | | BE PROVIDED IN THE SITE PLAN. EAST/SIDE AND SOUTH/REAR | | | SETBACKS ARE MISSING. | | | | | | 3.) PER ZLDR S.94-485, A MINIMUM OF 2 PARKING SPACES | | | ARE REQUIRED FOR THE USE. THE SITE PLAN MUST | | | DEMONSTRATE HOW THIS WOULD BE ACCOMMODATED (I.E. | | | DRIVEWAY, GARAGE, ETC.). PLEASE NOTE THAT THERE ARE | | | MINIMUM SETBACK REQUIREMENTS/DIMENSIONAL REQUIREMENTS | | | FOR ALL STRUCTURES, INCLUDING DRIVEWAYS, PAVED AREAS, | | | ETC. PLACEMENT OF SUCH STRUCTURES SHALL COMPLY WITH THE | | | MINIMUM REQUIREMENTS OF THE ZLDRS. [ZLDR S.94-312, | | | S.94-485] | | | | | | 4.) AT LEAST 1,000 SQ. FT. OF LANDSCAPED AREA SHALL BE | | | PROVIDED WITHIN THE FIRST 25 FT. OF 27TH STREET. PLEASE | | | PROVIDE CALCULATIONS TO DEMONSTRATE COMPLIANCE. [ZLDR | | | S.94-482] | | | | | | 5.) PLEASE CHECK LABELING OF THE BUILDING ELEVATIONS, | | | AS THEY SEEM TO BE INCONSISTENT WITH THE OTHER PLANS | | | (I.E. LOCATION OF THE CONDENSER UNIT; ELEVATIONS ARE | | | INCONSISTENT WITH THE FLOOR PLAN, ETC.). | | | | | | 6.) SEPARATE LANDSCAPE PERMIT REQUIRED FOR REQUIRED | | | LANDSCAPE IMPROVEMENTS ON THE PROPERTY. | | | | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|