Plan Review Details - Permit 21070178
Plan Review Stops For Permit 21070178
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 12:22 Rev Time 0.00
Received By shill Date 2021-08-21 Time 12:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-18 Cont ID  
Sent By rmcphers Date 2021-08-18 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2021-08-18 Time 13:21 Sent To  
Notes
2021-08-18 13:33:17FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 THE TEST REPORT PROVIDED INCLUDES A DROP CEILING WITH
 DRYWALL AND INSULATION IN THE "SPECIMEN DESCRIPTION" ON
 THE TEST REPORT - THE UNIT BELOW YOU WILL NEED TO HAVE
 A DROP CEILING THAT MATCHES THE "SPECIMEN DESCRIPTION"
 - PLEASE PROVIDE A TEST REPORT WITH THE "SPECIMEN OR
 TESTED ASSEMBLY" DESCRIPTION WITH CONCRETE SLAB,
 UNDERLAYMENT, FLOORING TYPE ONLY. A FLAME SPREAD TEST
 REPORT IS ALSO REQUIRED - SEE BELOW
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 09:22 Rev Time 0.00
Received By rmcphers Date 2021-08-02 Time 09:16 Sent To  
Notes
2021-08-02 09:22:17FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF
 THE FLOORING TO BE INSTALLED.
 2) PLEASE SHOW THE TYPE OF FLOORING ON THE FLOOR PLAN
 TO BE INSTALLED.
 3) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 4). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-08-24 Cont ID  
Sent By pleduc Date 2021-08-24 Time   Rev Time 0.00
Received By pleduc Date 2021-08-24 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By pleduc Date 2021-08-10 Time   Rev Time 0.00
Received By pleduc Date 2021-08-10 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-23 Cont ID  
Sent By pleduc Date 2021-07-23 Time   Rev Time 0.00
Received By pleduc Date 2021-07-23 Time 10:04 Sent To  
Notes
2021-07-23 10:08:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO ADDRESS NOR DESCRIPTION OF WORK ON THE
 PERMIT APPLICATION, AS WELL AS, NO FLOOR PLAN SHOWING
 THE AREAS OF INSTALL.
  
 PLEASE REVIEW AND CORRECT AND PROVIDE A DETAILED FLOOR
 PLAN OF WHERE THE FLOOR WILL BE INSTALLED.
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-08-25 Time   Rev Time 0.00
Received By lmarchan Date 2021-08-19 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-18 Cont ID  
Sent By rmcphers Date 2021-08-18 Time 13:34 Rev Time 0.00
Received By rmcphers Date 2021-08-09 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 09:22 Rev Time 0.00
Received By rmcphers Date 2021-07-21 Time 07:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 09:22 Rev Time 0.00
Received By rmcphers Date 2021-08-02 Time 09:22 Sent To  
Notes
***NONE***