Plan Review Details - Permit 21070162
Plan Review Stops For Permit 21070162
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-10-01 Cont ID  
Sent By rmcphers Date 2021-10-01 Time 13:23 Rev Time 0.00
Received By rmcphers Date 2021-10-01 Time 13:23 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-09-10 Cont ID  
Sent By pvalenti Date 2021-09-10 Time 16:31 Rev Time 0.00
Received By pvalenti Date 2021-09-10 Time 16:31 Sent To  
Notes
2021-09-10 16:33:58****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS COMMENTS:
  
 FAILED PLAN REVIEW
 :
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 10:19 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 10:18 Sent To  
Notes
2021-08-10 10:20:02PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-10-28 Cont ID  
Sent By rmcphers Date 2021-10-28 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2021-10-28 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-10-01 Cont ID  
Sent By rmcphers Date 2021-10-01 Time 14:28 Rev Time 0.00
Received By rmcphers Date 2021-10-01 Time 14:05 Sent To  
Notes
2021-10-01 14:09:22BUILDING RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SHOW THAT THE FLOOR COVERINGS (VINYL AND
 TILE) ARE BEING INSTALLED - THE FOLLOWING ACUSTICAL
 TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-11 Cont ID  
Sent By pvalenti Date 2021-09-11 Time 13:20 Rev Time 0.00
Received By pvalenti Date 2021-09-10 Time 16:35 Sent To  
Notes
2021-09-11 14:01:37****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 803.11, PLEASE SHOW THE FIRE CLASSIFICATION
 FOR WALL AND CEILING FINISHES. PLAN SHEET A800.A.
 GENERAL NOTES REFER TO (IBC) CODE SECTIONS. THE
 REQUIRED FIRE CLASSIFICATION NEEDS TO BE ON THE FINISH
 SCHEDULES FOR WALL AND CEILING AREAS.
 2) FBC B 1004.4, PLEASE SHOW, UNDER DESIGN OCCUPANT
 LOAD ON PLAN SHEET GN100, THE OCCUPANT LOAD FOR THE 1ST
 FLOOR COMMUNITY ROOM.
 3) FBC B 107.2.1, PLEASE ADD NOTE, UNDER SCOPE OF WORK
 ON PLAN SHEET GN100, NO FLOORING WILL BE REPLACED AND
 REMOVE THE FLOORING TILE SECTIONS FROM TILE SCHEDULE ON
 SHEET A800.A OR PROVIDE ON PLAN THE UNDERLAYMENT THAT
 WILL BE USED FOR FLOORING REPLACEMENT INCLUDING THE
 TEST REPORTS FOR SOUND AND FLAME SPREAD IN ACCORDANCE
 WITH FBC B 1207.2, 1207.3 & 603.1.
 4) OK, AS DEFERRED SUBMITTAL HAS BEEN INDICATED ON
 PLAN.
 5) FBC B 107.2.1, PLEASE PROVIDE THE, DESIGNER OF
 RECORD REVIEW STAMP APPROVED, PRODUCT APPROVALS FOR THE
 NEW EXTERIOR WINDOWS, DOORS, LOUVERS AND ROOFING
 SYSTEMS & MATERIALS.
 6) NOTE: ALL SHOP DRAWINGS AND PRODUCT APPROVALS MUST
 BE REVIEWED/APPROVED BY DESIGNER OF RECORD
 (ACKNOWLEDGED ON RESPONSE SHEET).
 7) OK, THE CONSTRUCTION TYPE HAS BEEN ADDED TO PLAN
 SHEET GN100.
 8) NOTE: WPB/FBC B 107.3.4.1, DEFERRED SUBMITTAL
 REQUIREMENTS HAVE BEEN ACKNOWLEDGED BY ENGINEER JEREMY
 M. CASE P.E.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 10:20 Rev Time 0.00
Received By rmcphers Date 2021-08-09 Time 14:45 Sent To  
Notes
2021-08-10 09:42:20BUILDING RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE REQUIRED FIRE CLASSIFICATION FOR THE
 WALL AND CEILING FINISHES PER FBC 803.11
 2) PLEASE SHOW THE OCCUPANT LOAD FOR THE 1ST FLOOR
 COMMUNITY ROOM. FBC 1004.4
  
 3) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 4) PLEASE PROVIDE DRAWINGS FOR THE ALUMINUM CANOPY,
 ALUMINUM LATTICE, EXTERIOR ALUMINUM WALL PANELS SHOWING
 COMPONENTS AND ATTACHMENTS TO COMPLY WITH THE WIND
 LOADS PER FBC 1609
 5) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS,
 LOUVERS AND ROOFING SYSTEMS.
 6) ALL SHOP DRAWINGS AND PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD.
 FBC WPB 107.2
 7) CONSTRUCTION TYPE SHOWN SHOULD BE (I A) SEE FBC
 CHAPTER 5
 8) FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-10-06 Cont ID  
Sent By jleahy Date 2021-10-06 Time 14:25 Rev Time 0.00
Received By jleahy Date 2021-10-06 Time 10:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-08 Cont ID  
Sent By jleahy Date 2021-09-08 Time 16:04 Rev Time 0.00
Received By jleahy Date 2021-09-08 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-05 Cont ID  
Sent By jleahy Date 2021-08-05 Time 14:47 Rev Time 0.00
Received By jleahy Date 2021-08-05 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-09-24 Cont ID  
Sent By pleduc Date 2021-09-24 Time   Rev Time 0.00
Received By pleduc Date 2021-09-24 Time 09:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-10 Cont ID  
Sent By pleduc Date 2021-09-10 Time   Rev Time 0.00
Received By pleduc Date 2021-09-08 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By pleduc Date 2021-07-27 Time   Rev Time 0.00
Received By pleduc Date 2021-07-27 Time 13:09 Sent To  
Notes
2021-07-27 13:09:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHOULD IT BE INTENDED FOR THE BUILDING TO REMIAN
 OCCUPIED, THERE ARE NO LIFE SAFETY PLAN SHEETS
 INDICATING HOW THE EXITS/EXIT ROUTES WILL BE MAINTAINED
 DURING CONSTRUCTION.
  
 ADDITIONALLY, WITH ALL THE EXTERIOR WORK HOW WILL THE
 AREA BE PROTECTED FROM FALLING OR ACCUMULATED
 CONSTRUCTION DEBRIS.
  
 PER NFPA 1
  
 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT
 OPERATIONS.
 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE
 PERMITTED TO BE
 OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR
 ADDITIONS ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN
 PLACE AND CONTINUOUSLY MAINTAINED FOR THE PORTION
 OCCUPIED OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION
 ARE IN PLACE.
  
 4.6.10.2 WHERE REQUIRED BY CHAPTERS 11 THROUGH 43,
 CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS SHALL COMPLY WITH
 NFPA 241
  
 4.6.10.3* IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE
 ESCAPE FACILITIES
 SHALL BE MAINTAINED AT ALL TIMES FOR THE USE OF
 CONSTRUCTION WORKERS.
 ESCAPE FACILITIES SHALL CONSIST OF DOORS, WALKWAYS,
 STAIRS, RAMPS, FIRE
 ESCAPES, LADDERS, OR OTHER APPROVED MEANS OR DEVICES
 ARRANGED IN
 ACCORDANCE WITH THE GENERAL PRINCIPLES OF THE CODE
 INSOFAR AS THEY CAN
 REASONABLY BE APPLIED TO BUILDINGS UNDER CONSTRUCTION.
  
 PLEASE PROVIDE SPECIFIC DETAILS PROVIDING LIFE SAFETY.
  
  
  
 2) THE ELECTRICAL PLAN SHEETS INDICATE FIRE ALARM
 EQUIPMENT.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEGEMENT.
  
  
  
 3) ELECTRICAL SHEETS - THERE ARE NO OF SMOKE ALARMS
 WITHIN THE INDIVIDUAL UNIT.
  
 PER NFPA 101 CH 31
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5, SMOKE
 ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA IN
 ACCORDANCE WITH
 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO
 BE BATTERY POWERED.
  
 9.6.2.10.1 WHERE REQUIRED BY ANOTHER SECTION OF THIS
 CODE, SINGLESTATION
 AND MULTIPLE-STATION SMOKE ALARMS SHALL BE IN
 ACCORDANCE WITH
 NFPA 72 UNLESS OTHERWISE PROVIDED IN 9.6.2.10.3,
 9.6.2.10.4, 9.6.2.10.6,
 OR 9.6.2.10.7.
 9.6.2.10.2 WHERE AUTOMATIC SMOKE DETECTION IS REQUIRED
 BY CHAPTERS 11
 THROUGH 43, SMOKE ALARMS SHALL NOT BE USED AS A
 SUBSTITUTE.
 9.6.2.10.3* THE INTERCONNECTION OF SMOKE ALARMS SHALL
 APPLY ONLY TO
 NEW CONSTRUCTION AS PROVIDED IN 9.6.2.10.9.
  
 SHOULD IT BE INTENDED TO PROVIDE NEW SMOKE ALARMS IN
 ALL THE UNITS THEN INTERCONNECTION WOULD APPLY.
  
 9.6.2.10.9* IN NEW CONSTRUCTION, WHERE TWO OR MORE
 SMOKE ALARMS ARE
 REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE THE
 ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT,
 SUITE OF ROOMS, OR
 SIMILAR AREA TO SOUND, UNLESS OTHERWISE PERMITTED BY
 ONE OF THE
 FOLLOWING:
 (1) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY WHERE
 PERMITTED BY
 ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY TO
 CONFIGURATIONS
 THAT PROVIDE EQUIVALENT DISTRIBUTION OF THE ALARM
 SIGNAL.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS
 AND CODE REFERENCES.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 10:43 Rev Time 0.00
Received By lcrespo Date 2021-09-21 Time 10:43 Sent To  
Notes
2021-09-21 10:43:09GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND
 PLANS WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 67. NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS
 TIME AND PROVIDE AN ISOMETIC WITH SPECIFICATION OF NEW
 EQUIPMET, PIPE SIZES, REGUATOR SPECIFICATIONS. THIS
 WILL HAVE THE GAS APPROVE FOR A SUB PERMIT, OR IF YOU
 DECIDED NOT TO ADDRESS THESE COMMENTS, A NOTE HAS BEEN
 PUT ON THE PLANS FOR A GAS HEATER (A SEPARATE PERMIT BY
 A LICENSED CONTRACTOR FOR THE GAS SYSTEM). AN N WILL BE
 PUT ON THIS REVIEW, WHICH STANDS FOR NOT REQUIRED, BUT
 A SUB PERMIT WON'T BE ISSUED ONCE A REVIEW IS DONE FOR
 THAT SUB PERMIT, SO PLEASE BE ADVISED ON THIS
 PROCEDURE.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-28 Cont ID  
Sent By rmcphers Date 2021-10-28 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2021-10-26 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-07 Cont ID  
Sent By lcrespo Date 2021-10-07 Time 15:39 Rev Time 0.00
Received By lcrespo Date 2021-09-23 Time 09:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 09:49 Rev Time 0.00
Received By lcrespo Date 2021-09-07 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-17 Cont ID  
Sent By rmcdouga Date 2021-08-17 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2021-07-22 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-09-27 Cont ID  
Sent By medwards Date 2021-09-27 Time 07:11 Rev Time 0.00
Received By medwards Date 2021-09-27 Time 07:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-09-08 Cont ID  
Sent By medwards Date 2021-09-08 Time 08:47 Rev Time 0.00
Received By medwards Date 2021-09-08 Time 08:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-03 Cont ID  
Sent By medwards Date 2021-08-03 Time 11:10 Rev Time 0.00
Received By medwards Date 2021-08-03 Time 11:10 Sent To  
Notes
2021-08-03 11:12:081ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070162
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET D101 INDICATES A ROOM WITH OFFICES AT THE
 FRONT LEFT CORNER OF THE BUILD. SHEET M101 INDICATES
 ONLY AN EXISTING AC UNIT. WHAT IS THE USE OF THIS SPACE
 NOW? IS THERE GOING TO BE DUCTWORK RAN FROM THE
 EXISTING AC? FBC 107.2.1
  
 2) SHEET M201: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR EACH USE OF SPACE ON THE FIRST-FLOOR
 BUSINESS SIDE. THERE ARE AREAS THAT WERE OPEN AND ARE
 NOW OFFICES. THERE ARE ALSO AREAS THAT WERE OFFICES
 THAT NOW APPEAR TO BE OPEN AREAS. FBC M 403.3.1.1 AND
 TABLE 403.3.1.1
  
 3) SHEET M101: NEW WORK MECHANICAL FOOT NOTE 6 HAS BEEN
 CUT OFF AND CANT BE READ. PLEASE ADJUST. FBC 107.2.1
  
 4) SHEET MD102 AND M102 ARE BOTH LABELED MECHANICAL
 2ND-8TH FLOOR DEMO PLAN, PLEASE LABEL CORRECTLY. FBC M
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2021-10-28 Cont ID  
Sent By rmcphers Date 2021-10-28 Time 13:04 Rev Time 0.00
Received By rmcphers Date 2021-10-28 Time 13:00 Sent To  
Notes
2021-10-28 13:04:45NOT A SUBSTANTIAL IMPROVEMENT
 PALM BEACH COUNTY FLOOD ZONE MAP SHOWS BUILDING IN A
 FLOOD ZONE AE-6
 PALM BEACH COUNTY PROPERTY APPRAISER SHOWS BUILDING
 VALUE OF 12,706,715.00 / 2 = 6,353,357.50
 JOB VALUE OF 6,200,000.00
 5YR CUMULATIVE = 0
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2021-10-01 Cont ID  
Sent By rmcphers Date 2021-10-01 Time 14:11 Rev Time 0.00
Received By rmcphers Date 2021-10-01 Time 14:10 Sent To  
Notes
2021-10-01 14:11:22PALM BEACH COUNTY FLOOD ZONE MAP SHOWS BUILDING IN A
 FLOOD ZONE AE-6
 PALM BEACH COUNTY PROPERTY APPRAISER SHOWS BUILDING
 VALUE OF 12,007,976.00 / 2 = 6,003,988.00
 JOB VALUE OF 6,200,000.00
 JOB IS A SUBSTANTIAL IMPROVEMENT - FBC EXISTING
 BUILDING 701.3
 AS A SUBSTANTIAL IMPROVEMENT THE BUILDINGS "LOWEST
 FLOOR" ELEVATION WILL NEED TO BE AT OR ABOVE 8.00 NAVD
 - CITY ORDINANCE NO. 4729-17
 PLEASE PROVIDE A SURVEY OR ELEVATION CERTIFICATE USING
 THE LATEST FIRM THAT SHOWS THE BUILDINGS LOWEST FLOOR.
 AN INDEPENDENT APPRAISAL CAN BE PROVIDED SHOWING THE
 BUILDING ONLY AS IS VALUE.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-09-10 Cont ID  
Sent By pvalenti Date 2021-09-10 Time 16:02 Rev Time 0.00
Received By pvalenti Date 2021-09-10 Time 16:02 Sent To  
Notes
2021-09-10 16:10:16****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 NFIP REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE CLARIFY AND SHOW THE APPRAISED
 CASH VALUE. THE LAST REVIEW SHOWED THE VALUE TO BE
 $12,007,976.00 PER THE PALM BEACH COUNTY APPRAISER'S
 SITE. IF THAT VALUE IS DIFFERENT, PLEASE SHOW WHAT THE
 APPRAISED CASH VALUE OF THE BUILDING IS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 09:57 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 09:57 Sent To  
Notes
2021-08-10 09:52:02PALM BEACH COUNTY FLOOD ZONE MAP SHOWS BUILDING IN A
 FLOOD ZONE AE-6
 PALM BEACH COUNTY PROPERTY APPRAISER SHOWS BUILDING
 VALUE OF 12,007,976.00 / 2 = 6,003,988.00
 JOB VALUE OF 6,200,000.00
 JOB IS A SUBSTANTIAL IMPROVEMENT - FBC EXISTING
 BUILDING 701.3
 AS A SUBSTANTIAL IMPROVEMENT THE BUILDINGS "LOWEST
 FLOOR" ELEVATION WILL NEED TO BE AT OR ABOVE 8.00 NAVD
 - CITY ORDINANCE NO. 4729-17
 PLEASE PROVIDE A SURVEY OR ELEVATION CERTIFICATE USING
 THE LATEST FIRM THAT SHOWS THE BUILDINGS LOWEST FLOOR.
 AN INDEPENDENT APPRAISAL CAN BE PROVIDED SHOWING THE
 BUILDING ONLY AS IS VALUE.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-10-07 Cont ID  
Sent By lcrespo Date 2021-10-07 Time 15:37 Rev Time 0.00
Received By lcrespo Date 2021-10-07 Time 15:02 Sent To  
Notes
2021-10-07 15:39:1310/07/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 09:48 Rev Time 0.00
Received By lcrespo Date 2021-09-21 Time 09:48 Sent To  
Notes
2021-09-21 09:49:0609/21/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By lcrespo Date 2021-08-11 Time 17:05 Rev Time 0.00
Received By lcrespo Date 2021-08-06 Time 09:49 Sent To  
Notes
2021-08-11 17:03:1508/11/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET GN-100, THE 2017 ICC ANSI A117 ACCESSIBLE
 AND USABLE BUILDING AND FACILITIES DOES NOT HAVE THE
 YEAR 2009 ON IT HAS 2017, WHICH IS NOT CORRECT. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET GN-102;
  
 A. UNDER TYPE TOILET AND BATHING FACILITIES # ONE, THE
 A17.1 SHOULD BE A117.1, AND THE SECTION SAYS 1003.1,
 AND IT SHOULD BE 1003.11. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. NUMBER TWO SAYS 1003.11. AND IT SHOULD BE 1003.11.1.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE ARE TWO NUMBER FIVES ON THIS SECTION. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. NUMBER FIVE, THE SECOND ONE, SAY 1004.11.2.4, AND
 THERE IS NO SUCH SECTION. IT SHOULD BE 1003.11.2.4.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE WATER CLOSET CLEAR FLOOR REQUIREMENTS SHOW 48
 INCHES BY 66 INCHES, AND IT SHOULD BE 60 INCHES BY 66
 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. THE REINFORCEMENT FOR SEAT REFERS TO 608.2.2.3, AND
 IT SHOULD BE 610.4. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. PLEASE SHOW THE LOCATION FOR CONTROLS STANDARD
 ROLL-IN SHOWER ON THE BACK WALL PER THE ANSI
 A117.1-2009 SECTION 608.4.2.
  
 H. THE NEW FLOOR DRAIN REQUIRES A TRAP PRIMER, SO WOULD
 YOU PLEASE ADD THAT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 3. ON SHEET GN-101;
  
  
 A. DETAIL #20 HAS;
  
 1. THE MINIMUM UNDER LAV AT 29 INCHES SHOULD BE 27
 INCHES PER THE A117.1-2009 SECTION 306.3.4. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. MIRRORS SHALL HAVE THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES. WOULD YOU PLEASE ADD THIS PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THERE IS NO DETAIL FOR THE CONTROLS PER THE
 A117.1-2009 SECTION 608.4.2. WOULD YOU PLEASE ADD THIS
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE IS NO DETAIL FOR THE DIMENSION OF THE GAB BARS
 BACKING MAXIMUM FROM THE SIDEWALL AND THE FLOOR PER THE
 A117.1-2009 SECTION 608.3.2 9 (OPTIONAL). WOULD YOU
 PLEASE PROVIDE DETAIL FOR THEM PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 D. THERE IS NO DETAIL FOR THE HEIGHT OF THE VERTICAL
 GRAB BARS REINFORCEMENT. WOULD YOU PLEASE PROVIDE
 DETAIL FOR THEM PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET A101;
  
 A. WOULD YOU PLEASE LABEL UNIT 3 AS AN FHA ALONG WITH
 TYPE A PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. IN UNIT THREE, THE LAV IS NOT SHOWN. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. IN THE COMMUNITY LOUNGE 109, THERE IS A SINK. PLEASE
 SHOW THE CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES PER
 THE 2020 FBC ACCESSIBILITY CODE 7 EDITION.
  
 D. WOULD YOU PLEASE PROVIDE A SECTIONAL VIEW FOR THE
 LOUNGE, UNISEX BATH, MEN'S AND WOMAN'S RESTROOM. WOULD
 YOU PLEASE PROVIDE THE GRAB BARS ELEVATION OF ALL
 ACCESSIBILITY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. UNDER GENERAL NOTES, IT CALLS FOR FLOOR DRAINS IN
 ALL BATHROOMS. WOULD YOU PLEASE ADD VERBIAGE OF A TRAP
 PRIMER AS WELL PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 F. IN THE WOMEN'S AND MEN'S RESTROOMS, THE WOMEN'S
 ACCESSIBLE WATER CLOSET REQUIRES A LAV SINCE IT HAS
 BEEN MOVED. WHERE LAVATORIES ARE PROVIDED, AT LEAST ONE
 SHALL COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A
 TOILET COMPARTMENT, TOILET COMPARTMENT SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE AT LEAST
 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL SIZE, AND
 WALL-MOUNTED PER THE 2020 FBC ACC SEC. 604.8.1.6
 LAVATORY.
  
 G. ACCESSIBLE WATER CLOSET WITHIN THE
 WHEELCHAIR-ACCESSIBLE COMPARTMENT SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR PER THE 2020 FBC ACC
 SEC. 604.8.1.7 WATER CLOSET.
  
 5. IN SHEET A102, WOULD YOU PLEASE LABEL UNIT 3 AS AN
 FHA ALONG WITH TYPE A PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 6. ON SHEET A105;
  
 A. THE TYPE A UNIT FIVE HAS THE WATER CLOSET CLEAR
 REQUIREMENTS ARE NOT SHOWN, AND IT SHOULD BE 60 INCHES
 BY 66 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU
 PLEASE CORRECT ON THIS PAGE AND ALL OTHER PAGES PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE KITCHEN SINK HAS A CLEAR FLOOR SPACE DIMENSION,
 BUT THE BATHROOM DOES NOT. THE REFRIGERATOR DOES NOT
 HAVE CLEAR FLOOR SPACE. WOULD YOU PLEASE PROVIDE ON
 THIS PAGE AND ALL ARCHITECTURAL PAGES PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE ADD FHA TO DETAIL FIVE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. UNDER GENERAL NOTES, IT CALLS FOR FLOOR DRAINS IN
 ALL BATHROOMS. WOULD YOU PLEASE ADD VERBIAGE OF A TRAP
 PRIMER AS WELL PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 7. ON SHEET A805;
  
 A. THE TYPE A UNIT FIVE HAS THE WATER CLOSET CLEAR
 REQUIREMENTS ARE NOT SHOWN, AND IT SHOULD BE 60 INCHES
 BY 66 INCHES PER THE 1003.1.2.4.4 EXCEPTION. WOULD YOU
 PLEASE CORRECT ON THIS PAGE AND ALL OTHER PAGES PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE KITCHEN SINK HAS A CLEAR FLOOR SPACE DIMENSION,
 BUT THE BATHROOM DOES NOT. THE REFRIGERATOR DOES NOT
 HAVE THE CLEAR FLOOR SPACE. WOULD YOU PLEASE PROVIDE ON
 THIS PAGE AND ALL ARCHITECTURAL PAGES PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE ADD FHA TO DETAIL FIVE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET A813, WOULD YOU PLEASE THE CLEAR FLOOR
 SPACE FOR THE KITCHEN SINK PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 9. ON SHEET A820 ON DETAIL 3 AND 4;
  
 A. THE MINIMUM UNDER LAV AT 29 INCHES, AND IT SHOULD BE
 27 INCHES PER THE A117.1-2009 SECTION 306.3.4. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. MIRRORS SHALL HAVE THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES. WOULD YOU PLEASE ADD THIS PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 10. ON SHEET P001, THE REFERENCE STANDARD FOR GAS IS
 NOT REQUIRED, BUT THE ACCESSIBILITY IS MISSING. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. ON SHEET P101;
  
 A. THE ARCHITECTURAL DRAWING SHOWS A DIFFERENT LAYOUT
 FOR THE MEN'S AND WOMEN'S RESTROOMS. THERE IS A LAYOUT
 IN A101 THAT SHOWS THE WOMEN'S TOILETS MOVED. THIS
 CONSTITUTES NEW CONSTRUCTION, AND THE ACCESSIBILITY
 CODE MUST COMPLY WITH A LAV IN THE TOILET ROOM. WOULD
 YOU PLEASE CLARIFY AND CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. THERE ARE FLOOR DRAINS MOTIONED ON EVERY
 ARCHITECTURAL PAGE, BUT NO CONNECTION IS SHOWN ON THIS
 PLUMBING PAGE. WOULD YOU PLEASE CLARIFY AND CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. PLEASE LABEL ALL UNITS AND RESTROOMS PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. THE FHA UNIT FIVE HAS HAD THE LOCATION OF THE LAV
 AND TOILET MOVE ALONG WITH A FLOOR DRAIN ADDED, AND IT
 IS NOT SHOWN. WOULD YOU PLEASE ADD AND CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 12. ON SHEET P105, THE RESTROOM FOR WOMEN'S AND MEN'S
 SAY INSTALL NEW FIXTURES ON EX ROUGH, BUT ON A101 FOR
 WOMEN'S, IT HAS A DIFFERENT LAYOUT, THE SAME AS COMMENT
 11. WOULD YOU PLEASE CORRECT OR CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 13. ON SHEET P201, IT SHOWS A GAS WATER HEATER SCHEDULE
 BUT COULD NOT FIND ITS LOCATION. WOULD YOU PLEASE
 CLARIFY OR CORRECT IF AN ELECTRIC HEATER IS BEING USED
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 14. ON SHEET P301, PLEASE PROVIDE LISTED FIRE-STOPPING
 DETAILS FOR THE PIPPING THROUGH RATED THE FLOORS.
 PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS FOR THE UL
 SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 15. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 FOR THE CHANGES MADE TO UNIT FIVE TO THE SHIFT OF LAV
 AND WATER CLOSET LOCATION PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 IF YOU WOULD LIKE TO CONTACT ME AND DISCUSS
 CLARIFICATION ON QUESTION COMMENTS IN THIS REVIEW TO
 MOVE IT ALONG, PLEASE FEEL FREE TO SO.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-10-01 Cont ID  
Sent By rmcphers Date 2021-10-01 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2021-10-01 Time 14:09 Sent To  
Notes
2021-10-01 14:10:04ROOFING TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-09-11 Cont ID  
Sent By pvalenti Date 2021-09-11 Time 13:15 Rev Time 0.00
Received By pvalenti Date 2021-09-11 Time 13:15 Sent To  
Notes
2021-09-11 13:20:14****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE THE (DESIGNER OF RECORD
 REVIEW STAMP APPROVED) PRODUCT APPROVALS FOR ALL
 ROOFING SYSTEMS & MATERIALS TO BE USED.
 NOTE: A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF
 WORK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-10-28 Cont ID  
Sent By rmcphers Date 2021-10-28 Time 13:11 Rev Time 0.00
Received By rmcphers Date 2021-10-28 Time 13:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-09-27 Cont ID  
Sent By medwards Date 2021-09-27 Time 07:12 Rev Time 0.00
Received By medwards Date 2021-09-27 Time 07:12 Sent To  
Notes
2021-09-27 07:13:59THE FOLLOWING SHEETS STILL NEDD A DIGITAL SIGNATURE.
 A103
 A814
 A820.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-08 Cont ID  
Sent By medwards Date 2021-09-08 Time 08:46 Rev Time 0.00
Received By medwards Date 2021-09-08 Time 08:46 Sent To  
Notes
2021-09-08 08:47:07PLEASE RESPOND TO 1ST CYCLE REVIEW COMMENT BELOW:
  
 PLEASE PROVIDE DIGITALLY SIGNED AND SEALED DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-03 Cont ID  
Sent By medwards Date 2021-08-03 Time 11:14 Rev Time 0.00
Received By medwards Date 2021-08-03 Time 11:14 Sent To  
Notes
2021-08-03 11:15:18PLEASE PROVIDE DIGITALLY SIGNED AND SEALED DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2021-10-28 Cont ID  
Sent By rmcphers Date 2021-10-28 Time 13:05 Rev Time 0.00
Received By rmcphers Date 2021-10-28 Time 13:05 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2021-10-01 Cont ID  
Sent By rmcphers Date 2021-10-01 Time 14:28 Rev Time 0.00
Received By rmcphers Date 2021-10-01 Time 14:12 Sent To  
Notes
2021-10-01 14:18:24THRESHOLD BUILDING
  
 PLEASE PROVIDE THE FORM ON PAGE 8 OF THE "GUIDELINES
 AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL
 INSPECTORS" WHICH IS THE CONTRACTORS AND OWNERS
 SIGNATURE TO THE TERMS OF THE AGREEMENT.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2021-09-11 Cont ID  
Sent By pvalenti Date 2021-09-11 Time 14:13 Rev Time 0.00
Received By pvalenti Date 2021-09-11 Time 14:13 Sent To  
Notes
2021-09-11 14:23:46****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THRESHOLD REVIEW DENIED:
  
 PLEASE CAREFULLY READ THE REQUIREMENTS OF THE
 THRESHOLD/SPECIAL INSPECTOR AGREEMENT. ALL SECTIONS
 MUST BE COMPLETED AND SIGNED BY ALL MEMBERS INVOLVED
 INCLUDING: OWNER, SPECIAL INSPECTOR, LICENSED
 INSPECTORS, & CONTRACTOR. RESUMES ARE ALSO REQUIRED.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By rmcphers Date 2021-08-10 Time 10:09 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 10:01 Sent To  
Notes
2021-08-10 10:09:41CONCRETE RESTORATION -
 PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL BE
 HAPPY TO SEND YOU A COPY OF THE" GUIDELINES AND
 POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL
 INSPECTORS AND RESIDENT INSPECTORS". PLEASE READ AND
 FILL OUT THE FORMS.
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1) ANY REPAIRS TO THRESHOLD BUILDINGS ARE REQUIRED TO
 COMPLY WITH FS 553.79. THRESHOLD BLDG. REQUIRED
 STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 FLORIDA STATUTES.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-10-05 Cont ID  
Sent By ckimmerl Date 2021-10-05 Time 13:54 Rev Time 0.00
Received By ckimmerl Date 2021-10-05 Time 13:54 Sent To  
Notes
2021-09-29 13:24:521. WILL REQUIRE A SEPARATE SUBMITTED LANDSCAPE PERMIT
 OR LANDSCAPE APPLICATION BEFORE PASSING ZONING.
  
 ZONING PROVISOS:
  
 1. ANY SIGNS ON THE EXTERIOR OF BUILDING WILL REQUIRE A
 SEPARATE PERMIT.
 2. ANY NEW OR REPLACED MECHANICAL EQUIPMENT ON THE ROOF
 SHALL REQUIRE VISIBILITY SCREENING, AT LEAST EQUAL IN
 HEIGHT TO THE NEWLY PROPOSED MECHANICAL EQUIPMENT.
 3. PLEASE INCLUDE AN ADDITIONAL TREE WITHIN THE PARKING
 ISLAND ON THE SOUTH WESTERN CORNER OF THE LANDSCAPE
 PLAN.

Review Stop Z ZONING
Rev No 2 Status F Date 2021-09-16 Cont ID  
Sent By ckimmerl Date 2021-09-16 Time 08:59 Rev Time 0.00
Received By ckimmerl Date 2021-09-16 Time 08:53 Sent To  
Notes
2021-09-16 08:59:231. SHOULD ANY EXISTING EQUIPMENT ON THE ROOF BE
 REPLACED DUE TO ITS CONDITION BEING UNREPAIRABLE, OR
 ANY NEWLY INSTALLED MECHANICAL EQUIPMENT, THE
 REPLACEMENT/NEWLY INSTALLED EQUIPMENT SHALL BE SCREENED
 FROM VIEW.
  
 2. PLEASE PROVIDE COPIES OF THE APPROVED SITE PLAN AND
 LANDSCAPE PLANS FOR THE EXISTING BUILDINGS TO
 CONFIRM/DETERMINE IF ALL ORIGINAL LANDSCAPING (TREES,
 SHRUBS, ETC.) OF THE APPROVED PLANS ARE
 INCLUDED/EXISTING ONSITE.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-16 Cont ID  
Sent By aaponte Date 2021-08-16 Time 15:44 Rev Time 0.00
Received By ckimmerl Date 2021-08-16 Time 15:44 Sent To  
Notes
2021-08-16 15:44:16- LANDSCAPE AND STREETSCAPE REQUIRES IMPROVEMENTS, DUE
 TO THE PERMIT VALUE EXCEEDING 50% OF THE ASSESSED
 IMPROVEMENT VALUE OF THE PROPERTY. SITE SHALL BE
 BROUGHT INTO COMPLIANCE WITH THE CODE; SPECIFICALLY
 REGARDING LIGHT FIXTURES ON SIDEWALK, PLANTING OF SHADE
 TREES ALONG FRONTAGE, PARKING STRIPING, TERMINAL
 ISLANDS, AND OTHER LANDSCAPE/STREETSCAPE IMPROVEMENTS.
 STAFF RECOMMENDS SEPARATE MEETING TO DISCUSS CHANGES
 AND ACTIONS NECESSARY.
  
 - WITH THE REPLACEMENT OF THE ROOF, ANY NEW MECHANICAL
 EQUIPMENT SHALL BE SCREENED.
  
 - SIGNAGE WILL ALSO REQUIRE A SEPARATE PERMIT.
  
 - PLEASE PROVIDE HEIGHT/VERTICAL CLEARANCE
 DIMENSION/MEASUREMENT FROM THE SIDEWALK ELEVATION FOR
 THE PROPOSED COLONNADE/CANOPY.