Plan Review Details - Permit 21070155
Plan Review Stops For Permit 21070155
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 15:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By jwitmer Date 2021-08-10 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2021-08-10 Time 13:02 Sent To  
Notes
2021-08-10 13:04:17COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 15:42 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By jwitmer Date 2021-08-10 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2021-08-10 Time 13:02 Sent To  
Notes
2021-08-10 15:12:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21070155
 ADD: 1609 S. DIXIE HWY.
 CONT: MARION CONSTRUCTION
 TEL: 561-324-3163
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 10TH/ 2021
 ACTION: DENIED
  
 1A) SHEET A000 SITE PLAN. THE SUBMITTED SITE PLAN DOES
 NOT INDICATE THE PROPERTY LINES. PERMIT 19070414 AND
 THE PALM BEACH COUNTY PROPERTY APPRAISERS WEBSITE SHOWS
 THE PARKING LOT ON THE NORTH SIDE OF THE BUILDING ALL
 UNDER ONE PROPERTY CONTROL NUMBER. IS THE LOT BEING
 SUB-DIVIDED OR IS THE PARKING LOT JUST NOT SHOWN? 107.
 2.1.2. ADDITIONAL INFORMATION IS REQUIRED. THE OPENINGS
 ON THE NORTH SIDE OF THE BUILDING VERSES THE LOCATION
 OF THE PROPERTY LINE AND AMOUNT OF ALLOWABLE OPENINGS,
 2020FBC-BUILDING CODE TABLE 705.8. MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION.
  
 1B) THE SITE PLAN A000, AND A100 SHEET SHOWS DOOR 105
 LEADING OUT INTO THE ALLEY. THE LIFE SAFETY PLAN A-106
 SHOWS THIS SAME DOORWAY AS A MEANS OF EGRESS, PLEASE
 PROVIDE WHERE THE PROPERTY LINE IS FOR THE OUTSWING
 DOOR. WHAT WOULD PREVENT A TRUCK FROM PARKING AT THE
 DOORWAY BLOCKING THE MEANS OF EGRESS. SHOW COMPLIANCE
 WITH THE 2020 FBC-BUILDING CODE SECTION 3202.2 DOORS
 AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC
 WAY.
  
 2) SHEET A000 SITE PLAN/ CODE RESEARCH LIST THE
 CLASSIFICATION AS ALTERATION LEVEL 3. PLEASE REVIEW THE
 2020 FBC-EXISTING BUILDING CODE SECTION 505.1 SCOPE.
 LEVEL 3 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS
 50 PERCENT OF THE BUILDING AREA. PLEASE ALSO NOTE THIS
 IS A 2-STORY BUILDING, WHEN FIGURING THE AREA. I
 BELIEVE THIS IS A TENANT BUILD-OUT AND A BUILDING
 PARTIAL CHANGE OF OCCUPANCY AND NEEDS TO SHOW
 COMPLIANCE WITH SECTION 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY SECTION 1012 SHALL APPLY.
  
 3A) SHEET A000 SITE PLAN/ CODE RESEARCH LIST OCCUPANCY
 TYPES M AND S-1 AS NON-SEPARATED OCCUPANCIES AND A
 PORTION OF THE S-1 OCCUPANCY TO CHANGE TO F-1
 OCCUPANCY. THE 3 LISTED OCCUPANCY TYPES M, S-1 &
 F-1 DO NOT REQUIRE OCCUPANCY SEPARATION SEE TABLE 508.4
 2020FBC-B. SHEET A106 THE LIFE SAFETY PLAN THE DESIGNER
 OF RECORD IS DESIGNING THIS TENANT SPACE WITH 2 HOUR
 RATED TENANT SEPARATION WALLS AND 2 HOUR DOORS WITHIN
 THE TENANT SEPARATION WALLS. PLEASE PROVIDE EITHER A UL
 LISTING AND ASSEMBLY FOR THE RATED WALL OR GYPSUM
 ASSEMBLY. 2020 FBC-BUILDING 708.3 FIRE RESISTANCE
 RATING.
  
 3B) THE LIFE SAFETY PLAN A106 & A100 THE CONSTRUCTION
 PLAN BOTH SHOW 2-HOUR FIRE RATED DOORS INTO THE NEXT
 TENANT SPACE, PLEASE PROVIDE THE TYPE OF DOOR AND FRAME
 FOR THIS OPENING. THIS TYPE OF CONSTRUCTION EXCEEDS THE
 CODE REQUIREMENTS, BUT THE DESIGNER WOULD NEED TO MEET
 THE REQUIREMENTS FOR DOOR OPENINGS IN FIRE WALLS TABLE
 716.5 OF THE 2020 FBC-B.
  
 4) THE SUBMITTED SITE PLAN A.000 PLANS SHOW OCCUPANCY
 F-1 KITCHEN/ CATERING BUT WITHIN THE SUBMITTED PLAN
 THERE IS NO OVENS SHOWN FOR BAKING. THERE ARE LARGE
 FLOOR MIXERS, WOOD KNEADING TABLE BUT NO OVENS?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET A-104 THE NORTH ELEVATION INDICATES WHAT
 APPEARS TO BE A SHELVING UNIT WITH THE 1ST LEVEL OF
 SHELVING AT 36 INCHES ABOVE FINISH FLOOR. 2020
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) THE SUBMITTED PLANS INDICATE IN THE TITLEBLOCK THEY
 WERE DESIGNED BY ARCHITECT ANGELO DAVILA ARCHITECT LLC.
 THE PLANS ARE NOT SIGNED NOR SEALED. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A DOCUMENT IN
 THE FILE FOLDER, SCANNED, FACSIMILE, DIGITALLY CREATED
 OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT
 BE USED ON DIGITALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 12:57 Rev Time 0.00
Received By jleahy Date 2021-09-27 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-05 Cont ID  
Sent By fgiaquin Date 2021-08-05 Time 20:14 Rev Time 0.00
Received By fgiaquin Date 2021-08-05 Time 18:50 Sent To  
Notes
2021-08-05 20:14:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO OCP SIZE SHOWN FOR WAREHOUSE MAIN. FBC 107.2.1
 NEC 215
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-08 Cont ID  
Sent By pleduc Date 2021-09-08 Time   Rev Time 0.00
Received By pleduc Date 2021-09-08 Time 09:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By pleduc Date 2021-07-14 Time   Rev Time 0.00
Received By pleduc Date 2021-07-14 Time 15:59 Sent To  
Notes
2021-07-14 16:03:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF OCCUPANCY CHANGE TO
 FACTORY.
  
 PLEASE PROVIDE A DETAILED NARRATIVE OF WHAT IS BEING
 PRODUCED, HOW IT IS PRODUCED, HOW IT IS PACJAGED AND
 STORED.
  
  
 1A) THE APPLICATION STATES CATERING; HOWEVER, I DON'T
 SEE ANY COOKING/BAKING EQUIPMENT.
  
 COOKING PRODUCING GREASE LADEN VAPORS REQUIRES A HOOD &
 SUPPRESSION SYSTEM PER NFPA 96 UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE PROVIDE CLARIFICATION AND PROPOSED MENU ITEMS IF
 APPLICABLE.
  
  
  
 2) THERE ARE INDICATIONS OF RACKS; HOWEVER, NO DETAIL
 IS PROVIDED.
  
 PLEASE PROVIDE RACK DETAILS, PRODUCT SHEETS IF
 APPLICABLE, HEIGHT & WIDTH, SHELVING TYPE, AND
 TIE-DOWNINFO.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-08-06 Cont ID  
Sent By fmittner Date 2021-08-06 Time 16:39 Rev Time 0.00
Received By fmittner Date 2021-08-06 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 12:59 Rev Time 0.00
Received By jleahy Date 2021-09-03 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-10 Cont ID  
Sent By jwitmer Date 2021-08-10 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2021-07-08 Time 11:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-09-29 Cont ID  
Sent By lmarchan Date 2021-09-29 Time 14:05 Rev Time 0.00
Received By lmarchan Date 2021-09-28 Time 08:24 Sent To  
Notes
2021-09-29 14:05:32NO IMPACT FEES DUE. LEM
2021-09-28 08:25:019/28/21 EMAILED IMPACT FOR REVIEW-AO
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By jwitmer Date 2021-08-10 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2021-08-10 Time 13:02 Sent To  
Notes
2021-08-10 15:13:21IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-09-07 Cont ID  
Sent By medwards Date 2021-09-07 Time 10:29 Rev Time 0.00
Received By medwards Date 2021-09-07 Time 10:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-05 Cont ID  
Sent By medwards Date 2021-08-05 Time 16:17 Rev Time 0.00
Received By medwards Date 2021-08-05 Time 16:16 Sent To  
Notes
2021-08-05 16:33:281) PLEASE PROVIDE A DETAIL OF WHAT THIS TENANT DOES. IS
 THERE COOKING AT THIS CATERING SPACE? FBC 107.2.1
  
 2) THE FRESH AIR DUCT SUPPLY AHU-2 IS PENETRATING A
 2-HOUR RATED WALL, PLEASE SHOW HOW YOU WILL PROTECT THE
 RATED PENETRATION AT THIS LOCATION. FBC M 607
  
 3) PLEASE ADD A NOTE ON THE DRAWING THAT THE
 REFRIGERATION WILL REQUIRE A SEPERATE PERMIT AND PLAN
 REVIEW AS IT WILL NOT BE REVIEWED WITH THIS PROJECT.
  
 4) PLEASE ADD A NOTE ON THE DRAWING, IF IT APPLIES, THE
 HOOD WILL REQUIRE A SEPERATE PERMIT AND PLAN REVIEW AS
 IT WILL NOT BE REVIEWED WITH THIS PROJECT.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-21 Cont ID  
Sent By abelisle Date 2021-09-21 Time 06:22 Rev Time 0.00
Received By abelisle Date 2021-09-14 Time 05:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-05 Cont ID  
Sent By tklarge Date 2021-08-05 Time 04:07 Rev Time 0.00
Received By tklarge Date 2021-08-02 Time 11:47 Sent To  
Notes
2021-08-03 14:33:021) SHT. A000 - PLUMBING FIXTURE CALCULATION TABLE -
 INDICATE THE OCCUPANCY THAT YOU ARE USING TO CALCULATE
 THE PLUMBING FIXTURE REQUIREMENTS.FOR CALCULATIONS
 INVOLVING MULTIPLE OCCUPANCIES, SUCH FRACTIONAL NUMBERS
 FOR EACH OCCUPANCY SHALL FIRST BE SUMMED AND THEN
 ROUNDED UP TO THE NEXT WHOLE NUMBER.FBC-PLUMBING SEC.
 403.1.1.
 2) THE PLANS ARE NOT SIGNED AND SEALED AS REQUIRED BY
 FL. ADMIN. CODE RULE 61G1-16.003, 61G1-16.005.
 3) THE APPLICATION STATES THAT THIS IS GOING TO BE A
 CATERING BUSINESS BUT THERE IS NO COOKING EQUIPMENT
 SHOWN ON THE PLANS. CLARIFY.
 4) SHT. A100 - THE PLANS SHOW A PAIR OF STACKED WASHER
 / DRYER UNITS. THE WATER SUPPLY VALVES FOR THESE UNITS
 SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING
 SEC.606.33. THE PLANS SHOW THE VALVES BEHIND THE UNITS
 WHICH MAKE THEM INACESSIBLE.
 5) THE PLANS SHOW ONE DRINKING FOUNTAIN. IF A DRINKING
 FOUNTAIN IS TO BE PROVIDED, A MINIMUM OF TWO DRINKING
 FOUNTAINS ARE REQUIRED PER FBC-PLUMBING SEC.410.3 AND
 FBC-ACCESS. SEC.211.2.
 6) SHT. A104 - SHOW THE REQUIRED DISTANCE UNDER THE
 LAVATORY FROM THE FINISH FLOOR.FBC-ACCESS. SEC.
 306.3.1.
 7) SHT. A1105 - SHOW THE HEIGHT OF THE TOILET SEAT
 COVER DISPENSER AND THE PAPER TOWEL DISPENSER. COMPLY
 WITH FBC-ACCESS. SECS.308 & 309. THE OPERABLE PART OF
 THE DISPENSERS SHALL COMPLY.
 8) SHT. A100 - SHOW THE CLEAR FLOOR SPACE DIMENSIONS ON
 THE PLANS (L X W) FOR THE WATER CLOSETS AND LAVATORIES.
 COMPLY WITH FBC-ACCESS. SECS.604.3 AND 606.2.
 9) SHT. P1.1 & SHT.3.1 - SHOW THE PIPING FOR THE
 DRINKING FOUNTAINS AND BOTH TOILET ROOMS ON THE
 SANITARY AND WATER RISER DIAGRAMS.WPB AMEND. TO FBC
 SEC. 107.2.1.
 10) SHT. P0.1 - DETAIL #2 - THE NOTE AT THE INDIRECT
 WASTE PIPE REFERS TO THE 2017 FBC-PLUMBING. THE CODE IN
 EFFECT IS THE 2020 EDITION. PLEASE REVISE THE NOTE.
 11) INDICATE THE INSULATION THICKNESS ON THE WATER
 PIPING.THE THICKNESS SHALL COMPLY WITH FBC-ENERGY
 SEC.C404.4 & TABLE C403.2.10. THE MINIMUM WALL
 THICKNESS SHALL BE 1-INCH.
 12) THE HOT WATER PIPE SIZING SHALL COMPLY WITH THE
 FBC-ENERGY SECS.C404.5 THROUGH C404.5.2.1 DEPENDING ON
 THE COMPLIANCE METHOD CHOSEN.
 13) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING
 MACHINES PER FBC-PLUMBING SEC.1003.6.
 14) SHT. P1.1 - THE 2 COMPARTMENT SINK IN THE
 DISH/PREPARATION ROOM #109 SHALL DISCHARGE THROUGH A
 GREASE INTERCEPTOR. FBC-PLUMBING SEC.1003.1.
 15) SUBMIT GREASE INTERCEPTOR SIZING CALCULATIONS FOR
 THE 2 AND 3 CCOMPARTMENT SINKS TO ENSURE PROPER SIZING.
 FBC-PLUMBING SEC.1003.2.
 16) SHT. P3.1 - THE WASTE STACKS FOR THE WASHING
 MACHINES SHALL BE A MINIMUM OF 3 INCHES PER
 FBC-PLUMBING SEC.406.2.
 17) IT APPEARS THAT A RECIRCULATION LINE IS REQUIRED ON
 THE WATER PIPING SYSTEM PER FBC-PLUMBING SEC.607.2.
 SHOW THE RECIRCULATION LINE ON THE WATER RISER
 DIAGRAM.COMPLY WITH FBC-ENERGY SEC. C404.6.
 18) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 COOKING EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1.
 19) IF ANY OF THE COOKING EQUIPMEENT IS GAS OPERATED,
 SUBMIT A COMPLEETE GAS PLAN AND GAS RISER FIOR
 REVIEW.WPB AMEND. TO FBC SEC. 107.2.1.
 20) OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND
 NOT MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY
 INTO THE CIRCULATION PATH. THIS APPLIES TO THE DRINKING
 FOUNTAINS.FBC-ACCESS. SEC. 307.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 12:57 Rev Time 0.00
Received By jleahy Date 2021-09-27 Time 12:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By jwitmer Date 2021-08-10 Time 15:11 Rev Time 0.00
Received By jwitmer Date 2021-08-10 Time 13:02 Sent To  
Notes
2021-08-10 15:10:56THE SUBMITTED PLANS INDICATE IN THE TITLEBLOCK THEY
 WERE DESIGNED BY ARCHITECT ANGELO DAVILA ARCHITECT LLC.
 THE PLANS ARE NOT SIGNED NOR SEALED. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A DOCUMENT IN
 THE FILE FOLDER, SCANNED, FACSIMILE, DIGITALLY CREATED
 OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT
 BE USED ON DIGITALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-08-06 Cont ID  
Sent By llouie Date 2021-08-06 Time 16:39 Rev Time 0.00
Received By fmittner Date 2021-08-06 Time 16:39 Sent To  
Notes
***NONE***