| Plan Review Stops For Permit 21070078 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-11-01 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-08-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-08-31 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-08-31 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2021-08-31 16:07:16 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 21070078 | | | ADD: 1540 N. AUSTRALIAN AVE. / CONSTRUCTION SITE | | | BUILDING | | | CONT: BURKE CONSTRUCTION GROUP | | | TEL: 886-88-BURKE | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. JULY 26TH/ 2021 | | | ACTION: DENIED | | | | | | NOTICE 4X FEE / NOTICE!!!!! FLORIDA STATUTE | | | 553.80(2)(B) WITH RESPECT TO EVALUATION OF DESIGN | | | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS | | | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE | | | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | | REVIEW. | | | | | | | | | | | | | | | 1) COMPLIED. | | | | | | 2) 2ND REQUEST. THE SUBMITTED PLANS FOR MODULAR | | | BUILDINGS DOES NOT HAVE STATE APPROVAL PURSUANT TO | | | 553.77(5) AND RULE 61-41.009 F. A. C. STATE APPROVED | | | PLANS ARE ALSO REQUIRED BY THE 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION CODE 107.3 EXCEPTION (1). | | | | | | 3) 2ND REQUEST. FOUNDATION PLANS ARE NOT STATE | | | APPROVED. FOUNDATION PLANS ARE SITE SPECIFIC AND | | | REQUIRE A ENGINEERS SIGNATURE AND SEAL. 61G15-23.002(2) | | | FL. ADMIN. CODE. PLANS SIGNED & SEALED BY A | | | PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: NAME, | | | ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, THE NAME | | | AND LICENSE NUMBER OF THE ENGINEER AND THE NAME, | | | ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER IS | | | PRACTICING (471.025 F.S. AND 471.023 F.S.). | | | | | | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ | | | RETIRED. | | | | | | MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE | | | WORKING FROM CITY HALL | | | MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ RETIRED. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-07-26 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-07-26 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2021-07-26 17:37:55 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 21070078 | | | ADD: 1540 N. AUSTRALIAN AVE. / CONSTRUCTION SITE | | | BUILDING | | | CONT: BURKE CONSTRUCTION GROUP | | | TEL: 886-88-BURKE | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. JULY 26TH/ 2021 | | | ACTION: DENIED | | | 1) MISSING SITE PLAN. 2020 FLORIDA BUILDING CODE W 2020 | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: 107.3.5 | | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND OR | | | STRUCTURES. | | | 107.3.5.1 COMMERCIAL BUILDINGS | | | 107.3.5.1.1. BUILDING | | | MISSING CODE DATA: | | | 1. SITE REQUIREMENTS: | | | PARKING | | | FIRE ACCESS | | | VEHICLE LOADING | | | DRIVING/ TURNING RADIUS | | | FIRE HYDRANT/ WATER SUPPLY/ POST INDICATOR VALVE (PIV) | | | SET BACK/ SEPARATION (ASSUMED PROPERTY LINES | | | LOCATION OF SEWERS, WATER LINES AND SEWER LINES | | | FLOOD HAZARD AREAS, FLOOD ZONES, DESIGN FLOOD | | | ELEVATIONS | | | PROPOSED ELEVATION CERTIFICATES IN SPECIAL FLOOD HAZARD | | | AREAS | | | | | | 2) THE SUBMITTED PLANS FOR MODULAR BUILDINGS DOES NOT | | | HAVE STATE APPROVAL PURSUANT TO 553.77(5) AND RULE | | | 61-41.009 F. A. C. STATE APPROVED PLANS ARE ALSO | | | REQUIRED BY THE 2020 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION CODE | | | 107.3 EXCEPTION (1). | | | | | | 3) FOUNDATION PLANS ARE NOT STATE APPROVED. FOUNDATION | | | PLANS ARE SITE SPECIFIC AND REQUIRE A ENGINEERS | | | SIGNATURE AND SEAL. 61G15-23.002(2) FL. ADMIN. CODE. | | | PLANS SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL | | | INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF | | | THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE | | | ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS | | | THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S. | | | AND 471.023 F.S.). | | | | | | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ | | | RETIRED. | | | | | | MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE | | | WORKING FROM CITY HALL | | | MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ RETIRED. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-09-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-23 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-23 |
Time |
12:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-07-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-23 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-23 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2021-07-23 10:27:06 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PLEASE SUBMIT A RISER DIAGRAM SHOWING THE SERVICE AND | | | FEEDER SIZES. 215.5 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2021-10-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-10-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-10-28 |
Time |
11:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2021-08-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-08-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-08-24 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2021-08-24 10:18:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE PROPOSED TRAILER LOCATION APPEARS TO BE TOO | | | CLOSE TO THE PROPOSED BUILDING PER THE NFPA 241 | | | REQUIREMENT. | | | | | | THE FOUNDATION PLAN INDICATES A LENGTH OF 44', PER THE | | | NFPA 241 TABLE, THE TRAILER IS REQUIRED TO BE SEPARATED | | | FROM THE PROPSED BUILDING AT LEAST 40'. SHOULD FIRE | | | SPRINKLERS BE INSTALLED , A 75% REDUCTION IN THAT WIDTH | | | CAN BE APPLIED. | | | | | | PLEASE REVIEW AND CORRECT. (FYI - ABC DRY CHEMICAL | | | SPRINKLERS CAN BE ACCEPTED IN LIEU OF WATER FIRE | | | SPRINKLERS IF INSTALLED ACCORDING TO MANUFACTURERS | | | SPECIFICATIONS.) | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2021-07-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-07-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-07-12 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2021-07-12 13:44:32 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO SITE PLAN SHOWING THE LOCATION OF THE | | | TRAILER. | | | | | | INCLUDE THE PROPOSED LOCATION, WITH DISTANCES TO | | | PROPERTY LINES, EXISTING BUILIDNGS AND PROPOSED | | | BUILDINGS. | | | | | | | | | 1A) PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; | | | TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE | | | REQUIRED IN EACH TRAILER. | | | | | | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER | | | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH | | | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER | | | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS | | | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE | | | IN ACCORDANCE WITH TABLE 4.2.1. | | | | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | NOTES: | | | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY | | | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION | | | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE | | | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING | | | WALL LENGTHS OF THE TEMPORARY STRUCTURES. | | | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES | | | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL | | | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO | | | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE | | | APPLYING THIS TABLE, IS 3600 MM (144 IN.). | | | | | | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | | | | PLEASE ENSURE COMPLIANCE | | | | | | | | | 1B) THERE ARE NO INDICATIONS OF STAIRS NOR RAMPS. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-11-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-11-20 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-10-27 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-23 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-19 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-07-26 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-07-09 |
Time |
12:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-22 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-22 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2021-07-22 13:11:32 | FBC 107.3 EXCEPTION 1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-09-09 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-09-09 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-09 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2021-09-09 10:06:10 | 09/09/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-19 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-07-19 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-07-19 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2021-07-19 18:34:29 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21070078 | | | 7/19/2021 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH | | | EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH | | | EDITION 2020 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1. PROVIDE DOCUMENTATION OF STATE APPROVAL FOR A | | | MODULAR BUILDING. PER WEST PALM BEACH AMENDMENTS TO FBC | | | 107.3. | | | | | | 2. SHOW LOCATION AND SIZE OF SANITARY HOLDING TANKS ON | | | SITE PLAN. PER WEST PALM BEACH AMENDMENTS TO FBC | | | 107.2.1. | | | | | | 3. PROVIDE DOCUMENTATION OF PUMPOUT SCHEDULE FOR | | | SANITARY HOLING TANKS. WEST PALM BEACH AMENDMENTS TO | | | FBC 107.2.1. | | | | | | 4. SHOW LOCATION AND SIZE OF WATER SERVICE AND | | | BACKFLOWS FOR EACH TRAILER. PER WPB AMEND TO FBC | | | 107.2.1. | | | | | | 5. PLEASE PLACE NOTE ON SITE PLAN A BACKFLOW IS | | | REQUIRED AT THE WATER METER AND SHALL HAVE SEPARATE | | | PERMIT. PER WPB CROSS CONNECTION MANUAL. PER WEST PALM | | | BEACH AMENDMENTS TO FBC 107.2.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-11-01 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-09-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-23 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-23 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-07-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-23 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-23 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2021-07-23 10:29:16 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) PLAN IS NOT DIGITALLY SIGNED BY THE DESIGNER OF | | | RECORD | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-11-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2021-11-19 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-08-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2021-08-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-08-30 10:55:18 | ****CONSTRUCTION TRAILER****** | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-16 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-07-16 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2021-07-15 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2021-07-16 11:52:59 | ************************ZONING REVIEW | | | FAILED******************************* | | | | | | PROVIDE A COPY OF SURVEY SHOWING THE LOCATION OF THE | | | TRAILER. | | | | | | ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW. | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|